5
The device will immediately send a version packet and the report data with the status and voltage.
Data will be reported by default setting before any configuration.
Default setting:
Max Interval: 3600s
Min Interval: 3600s (Detect the reed state every Min Interval by default setting)
Battery Change :0x01 (0.1V)
R313CC status:
When the R313CC status changes, it will send a report.
Window / Door sensor open: 1
Window / Door sensor close: 0
The reported data is decoded by the Netvox LoRaWAN Application Command document and
http://loraresolver.netvoxcloud.com:8888/page/index
Sleeping Mode
The device is on and in the
network
Sleeping period: Min Interval.
When the reportchange exceeds setting value or the state changes: send a data
report according to Min Interval.
Low Voltage Warning
Low Voltage
2.4V
5.
Data Report
Data report configuration and sending period are as following:
Min Interval
(Unit:second)
Max Interval
(Unit:second)
Reportable Change
Current Change
≥
Reportable Change
Current Change
<
Reportable Change
Any number
between 1~65535
Any number
between 1~65535
Can not be 0.
Report
per Min Interval
Report
per Max Interval