AlphaDisc CLD user guide V2.0
77
7 Appendix B.
Alarms and Faults List
ALERT
POSSIBLE CAUSE
RECOMMENDED ACTION
LOW BATTERY
LOW BATTERY VOLTAGE
REPLACE ALL 4 CONTROLLER BATTERIES
LOW BATTERY PAUSE
CONTROLLER PAUSED DUE TO LOW
BATTERY VOLTAGE
REPLACE ALL 4 CONTROLLER BATTERIES
HIGH DP ALARM
DP VALUE IS >= HDA THRESHOLD (UNITS:
BAR/100)
ALERT ONLY
HIGH DP FAULT
DP VALUE IS >= HDF THRESHOLD (UNITS:
BAR/100)
ALERT ONLY
CONTINUOUS MODE ALERT
CONTROLLER EXCEEDED NUMBER OF
CONSECUTIVE FLUSHES FOR ALERTS
CHECK CONFIGURATION/CHECK DP: IF HIGH,
PERFORM MANUAL FLUSH WITH DOWNSTREAM
VALVE CLOSED, OPEN THE FILTER FOR
INSPECTION
DFU FAILED
FIRMWARE UPDATE FAIL
VALIDATE CELLULAR RECEPTION AND TRY AGAIN
OUT OF RANGE APP CONNECTION
CONTROLLER OUT OF RANGE DURING
CONNECTION SESSION
GET CLOSER TO THE CONTROLLER WITH THE
SMARTPHONE (WITHIN BLUETOOTH® RANGE)
SENSOR PRESSURE READ FAILED
THE NUMBER OF THE SENSOR THAT
FAILED TO READ. INLET (0), OUTLET (1),
PISTON (2).
IF CONTINUES - CONTACT SUPPORT
THERE IS A VACUUM IN THE SYSTEM
PERFORM AIR RELEASE
EQUIP THE SYSTEM WITH ANTI-
VACUUM VALVE
CAPACITOR CHARGER START
FAILED
UNABLE TO CHARGE CAPACITOR
CONTACT SUPPORT
LOAD CAPACITOR TIMEOUT
CAPACITOR CHARGE TIMEOUT
CHECK BATTERY VOLTAGE LEVEL, CONTACT
SUPPORT
LOW DOWNSTREAM PRESSURE
THE OUTLET PRESSURE IS LESS THAN
1.5 BAR
CHECK THE FILTER AND THE WATER SYSTEM
HIGH UPSTREAM PRESSURE
THE INLET PRESSURE IS GREATER THAN
MAXIMUM ALLOWED PRESSURE FOR THE
FILTER
ADJUST THE WATER SYSTEM INLET PRESSURE
ANTI-FREEZE ACTIVE
FREEZING PROTECTION START, AS
A RESULT OF LOW TEMPERATURE
THRESHOLD
ANTI-FREEZE EXIT
STOP FREEZING PROTECTION
PROCEDURE