Universal Wall-Mount Controller
BACnet Communication Module User Guide
www.neptronic.com
Page | 11
ID
Name
Description
W?
Notes
AV.72
Cfg_ExternHumidityOffset
Configuration value used to calibrate the external relative humidity sensor (Erh).
Present Value
Cov Increment
± 5%, Resolution 0.1% RH
AV.73
HumSetPoint
Configuration value used to set the actual user humidity setpoint of the zone in occupied/day
operation mode. This value may be locked to prevent the user from changing the setpoint (BV.26).
This object is commandable, relinquish default will be saved to non-volatile memory.
Present Value
Relinquish_Default
Cov Increment
10% RH to 90% RH (AV.74 to AV.75)
Resolution 0.5% RH
AV.74
Cfg_HumMinSetPoint
Configuration value used to set the minimum relative humidity setpoint of the zone in occupied/day
operation mode allowed by the user.
Present Value
Cov Increment
10% RH to 90% RH (10% to AV.75)
Resolution 0.5% RH
AV.75
Cfg_HumMaxSetPoint
Configuration value used to set the maximum relative humidity setpoint of the zone in
occupied/day operation mode allowed by the user.
Present Value
Cov Increment
10% RH to 90% RH (AV.74 to 90%)
Resolution 0.5% RH
AV.76
DehumdifySPNoOccNSB
Configuration value of the highest relative humidity allowed when in night setback or unoccupied
mode. Set BV.35 value to setpoint for the value to be active.
Present Value
Cov Increment
10% RH to 65% RH (AV.77 to 65%)
Resolution 0.5% RH
AV.77
HumidifySPNoOccNSB
Configuration value of the lowest relative humidity allowed when in night setback or unoccupied
mode. Set BV.35 value to setpoint
for the value to be active.
Present Value
Cov Increment
10% RH to 65% RH (10% to AV.76)
Resolution 0.5% RH
AV.78
HumidifyDemand
Status value that represents the humidifier modulation, based on relative humidity.
Cov Increment
0% RH to 100% RH, Resolution 1% RH
AV.79
DehumidifyDemand
Status value that represents the dehumidification percentage, based on relative humidity.
Cov Increment
0% RH to 100% RH, Resolution 1% RH
AV.80
Cfg_HumPropBand
Configuration value that represents the range through which the controller modulates the
humidifier or dehumidification output from 0 to 100%.
Present Value
Cov Increment
3% RH to 10% RH, Resolution 0.5% RH
AV.81
Cfg_HumDeadBand
Configuration value that represents the range at which the controller will not take action when
below or above the humidity setpoint.
Present Value
Cov Increment
0% RH to 5% RH, Resolution 0.5% RH
AV.85
Cfg_NSBOverrideDelay
Maximum configuration time in mins when in night setback mode and an override has been
activated on the controller.
Present Value
Cov Increment
0 to 180 minutes, Resolution 15 minutes
AV.86
Cfg_NoOccOverrideDelay
Maximum configuration time in mins when in unoccupied mode and an override has been
activated on the controller. Each time the user presses the fan button, an increment of 15 mins is
added up to this value.
Present Value
Cov Increment
0 to 180 minutes, Resolution 15 minutes
AV.87
Cfg_NoOccOvCountDown
Time in mins before the state of the input changes from Occupied to Unoccupied mode. There is
no time to change the state from Unoccupied to Occupied.
Cov Increment
0 to 180 minutes (0-AV.86), Resolution 1 minute
AV.88
Cfg_OccupancyMinTime
Time in mins before the state of the input changes from Occupied to Unoccupied mode. Used
when motion detector is not equipped with an internal timer.
Present Value
Cov Increment
0 to 240 minutes, Resolution 1 minute
AV.90
Cfg_BinaryInput1Delay
Configuration time in secs. Once the time has expired, the controller changes the state of the
input.
Present Value
Cov Increment
0 to 3,600 seconds, Resolution 10 seconds
AV.91
Cfg_BinaryInput2Delay
See AV.90
Present Value
Cov Increment
0 to 3,600 seconds, Resolution 10 seconds
AV.92
Cfg_AnalogInput1Delay
See AV.90
Present Value
Cov Increment
0 to 3,600 seconds, Resolution 10 seconds
AV.93
Cfg_AnalogInput2Delay
See AV.90
Present Value
Cov Increment
0 to 3,600 seconds, Resolution 10 seconds
AV.95
CO2SensorValue
Status of the carbon dioxide sensor (CO2). This is the value read by the CO2 sensor in parts per
million (PPM) when MSV.35 or MSV.36 is set to CO2 sensor. AV.96 (Range) and AV.97 (Setpoint
must be configured for proper reading).
Out of Service
Cov Increment
0 to 5,000 PPM, Resolution 1 PPM
AV.96
Cfg_CO2Range
Configuration value that represents the maximum range of the CO2 sensor (PPM).
Present Value
Cov Increment
100 to 5,000 PPM, Resolution 50 PPM
AV.97
CO2Setpoint
Configuration value that represents the maximum limit of CO2 concentration before the controller
sends an alarm.
Present Value
Cov Increment
100 to 2,000 PPM, Resolution 10 PPM