Standalone Wall-Mount Controller
Specification and Installation Instructions
www.neptronic.com
Page | 6
“Temp Control Mode”
Default:
Range:
COO
L
(Cooling Only)
Auto (Automatic), HEAt (Heating Only), COO
L
(Cooling Only), On (Cooling or Heating),
CLHt (Automatic only)
Select the control mode that you want to authorize to the user. To authorize all the available modes, select Auto (Automatic
Mode). The cooling
and heating symbols are also displayed. The selection made at this step determines the options
available via the Control Mode (see page 30).
“
Enable On Off Control Mode
”
Default:
Range:
yES (Enable)
yES (Enable), No (Disable)
If set to
yES
, the user can set the unit to “Off” via the Control Mode (see page 30). If set to
No
, the “Off” selection does not
appear in the Control Mode.
"Display Info"
Default:
Range:
t - Hu
%RH °C
(temperature, humidity, and cooling heating demand)
t - Hu
%RH °C
(temperature, humidity),
StP
%RH °C
(temperature, humidity setpoint),
OFF
(no display),
t - Hu
%RH °C
(temperature, humidity, and cooling heating demand),
StP
%RH °C
(temperature, humidity setpoint, and cooling
heating demand)
Select the desired information to appear on the display.
Keypad Lock Settings
“Keypad Upper Left Locked”
Default:
Range:
No (Disable)
yES (Enable), No (Disable)
If set to
yES
, the
button is locked and cannot be used by the user. If set to
No
, the
button is unlocked and can be used
by the user.
“Keypad Lower Left Locked”
Default:
Range:
No (Disable)
yES (Enable), No (Disable)
If set to
yES
, the
button is locked and cannot be used by the user. If set to
No
, the
button is unlocked and can be
used by the user.
“Keypad Arrows Locked”
Default:
Range:
No (Disable)
yES (Enable), No (Disable)
If set to
yES
, the
and
buttons are locked and cannot be used by the user. If set to
No
, the
and
buttons are
unlocked and can be used by the user.
Heat Pump Settings
"Heat Pump Option"
Default:
Range:
OFF (Disable)
ON (Enable), OFF (Disable)
Enable or disable the heat pump option.
If you select
OFF
:
•
Heat Pump options (Steps 13 to 15 and 35) will not be available.
•
Binary Output ramps (Steps 36, 42, 48 and 54) will be available.
If you select
ON
:
•
Heat Pump options (Steps 13 to 15 and 35) will be available.
•
Binary Output ramps (Steps 36, 42, 48 and 54) will not be available.