Standalone Wall-Mount Controller
Specification and Installation Instructions
www.neptronic.com
Page | 12
"BO3 Contact Delay Minutes"
Default:
Range:
Increment:
0 minute
0 to 15 minutes
1 minute
This option does not appear if the signal ramp for BO3 is set to
OFF
(Step 36, "BO3 Ramp"). Select the closing delay for BO3
output.
“BO3 Signal Type”
Default:
Range:
OnO
F
(On/Off)
tPm (Pulsing), OnO
F
(On/Off), FLot (Floating)
This option does not appear if the signal ramp for BO3 is set to
OFF
(Step 36, "BO3 Ramp"). Select the signal type for BO3 to
either Pulsing, On/Off or Floating.
Binary Output 4 (BO4)
The Binary Output 4 settings appear only if you have selected either fan speed 1 or 2 at Step 28, "Fan Spd Signal" or
VFdP, VFdt or FAN at Step 17, "AO2 Ramp".
"BO4 Ramp"
Default:
Range:
OFF
Cr1, Cr2, Hr1, Hr2 (heat with fan), Hr2 (heat without fan), CH1, HU, CO2, OFF, COr
Select the desired ramp from the available options. Same as BO3 options.
If you select
OFF
, Steps 43 to 46 will not be available.
"BO4 Close Percent"
Default:
Range:
Increment:
20% of the demand
15 to 80%
1%
This option does not appear if the signal ramp for BO4 is set to
OFF
(Step 42, "BO4 Ramp"). Select the percentage at which
you want BO4 to close (at % of demand of the ramp selected at Step 42, "BO4 Ramp").
"BO4 Open Percent"
Default:
Range:
Increment:
0% of the demand
0 to (BO4 Close)-4%
1%
This option does not appear if the signal ramp for BO4 is set to
OFF
(Step 42, "BO4 Ramp"). Select the percentage at which
you want BO4 to open (at % of demand of the ramp selected at Step 42, "BO4 Ramp").
"BO4 Dirrev"
Default:
Range:
dir (Direct)
dir (Direct), rEV (Reverse)
This option does not appear if the signal ramp for BO4 is set to
OFF
(Step 42, "BO4 Ramp"). Set the direction of the binary
signal to either Direct or Reverse.
"BO4 Contact Delay Minutes"
Default:
Range:
Increment:
0 minute
0 to 15 minutes
1 minute
Select the closing delay for BO4 output.
“BO4 Signal Type”
Default:
Range:
OnO
F
(On/Off)
tPm (Pulsing), OnO
F
(On/Off), FLot (Floating)
This option does not appear if the signal ramp for BO4 is set to
OFF
(Step 42, "BO4 Ramp"). Select the signal type BO4 to
either Pulsing or On/Off. If BO3 signal type is set to Floating, then BO4 signal type will also be set to Floating.