Neptronic TRO24T4XYZ3 Скачать руководство пользователя страница 8

TRO24T4XYZ3 

Specification & Installation Instructions

 

 

Step Display 

Description 

Values 

33 

C

 

Proportional band of changeover ramp:

 

Display shows 

“control ramp Ch over”

 and the value of the changeover 

ramp proportional band, cooling and heating symbols are also displayed. 
Please select the desired value of changeover ramp proportional band.

 

Proportional band range :  
0.5 to 5.0ºC [1 to 10ºF] 
Increment: 0.5ºC [1ºF] 

Default value: 2.0ºC [4ºF] 

34 

C

 

Proportional band of heating ramp1:

 

Display shows 

“control ramp 1 HEATing”

 and the value of the heating 

ramp1 proportional band, heating symbol is also displayed. 
Please select the desired value of heating ramp1 proportional band.

 

Proportional band range :  
0.5 to 5.0ºC [1 to 10ºF] 
Increment: 0.5ºC [1ºF] 

Default value: 2.0ºC [4ºF] 

35 

C

 

Proportional band of heating ramp2:

 

Display shows 

“control ramp 2 HEATing”

 and the value of the heating 

ramp2 proportional band, heating symbol is also displayed. 
Please select the desired value of heating ramp2 proportional band.

 

Proportional band range :  
0.5 to 5.0ºC [1 to 10ºF] 
Increment: 0.5ºC [1ºF] 

Default value: 2.0ºC [4ºF] 

36 

C

 

Proportional band of cooling ramp1:

 

Display shows 

“control ramp 1 cooling”

 and the value of the cooling 

ramp1proportional band, cooling symbol is also displayed. 
Please select the desired value of cooling ramp1proportional band. 

Proportional band range :  
0.5 to 5.0ºC [1 to 10ºF] 
Increment: 0.5ºC [1ºF] 

Default value: 2.0ºC [4ºF]

 

37 

C

 

Proportional band of cooling ramp2:

 

Display shows 

“control ramp 2 cooling”

 and the value of the cooling 

ramp2 proportional band, cooling symbol is also displayed. 
Please select the desired value of cooling ramp2 proportional band. 

Proportional band range :  
0.5 to 5.0ºC [1 to 10ºF] 
Increment: 0.5ºC [1ºF] 

Default value: 2.0ºC [4ºF]

 

38 

C

 

Dead band of changeover ramp: 

Display shows 

“control dead band Ch over”

 and the value of the 

changeover ramp dead band, cooling and heating symbols are also 
displayed. 
Please select the desired value of changeover ramp dead band.

 

Dead band range :  
0.0 to 5.0ºC [0.0 to 10.0ºF] 
Increment: 0.1ºC [0.2ºF] 

Default value: 0.3ºC [0.6ºF]

 

39 

C

 

Dead band of heating ramp1: 

Display shows 

“control dead band 1 heating”

 and the value of the 

heating ramp1 dead band, heating symbol is also displayed. 
Please select the desired value of heating ramp1 dead band.

 

Dead band range :  
0.0 to 5.0ºC [0.0 to 10.0ºF] 
Increment: 0.1ºC [0.2ºF] 

Default value: 0.3ºC [0.6ºF]

 

40 

C

Dead band of heating ramp2: 

Display shows 

“control dead band 2 heating”

 and the value of the 

heating ramp2 dead band, heating symbol is also displayed. 
Please select the desired value of heating ramp2 dead band.

 

Dead band range :  
0.0 to 5.0ºC [0.0 to 10.0ºF] 
Increment: 0.1ºC [0.2ºF] 

Default value: 0.3ºC [0.6ºF]

 

41 

C

 

Dead band in cooling ramp1: 

Display shows 

“control dead band 1 cooling”

 and the value of the 

cooling ramp1dead band, cooling symbol is also displayed. 
Please select the desired value of cooling ramp1 dead band. 

Dead band range :  
0.0 to 5.0ºC [0.0 to 10.0ºF] 
Increment: 0.1ºC [0.2ºF] 

Default value: 0.3ºC [0.6ºF]

 

Содержание TRO24T4XYZ3

Страница 1: ...30 EN 60529 Weight 160 g 0 36 lb Dimensions A B C D E F C A 2 85 73mm B 4 85 123mm C 1 00 24mm D 2 36 60mm E 3 27 83mm Interface C F RH MO TU WE TH FR SA SU AM PM Symbols on display Cooling ON 33 66 1...

Страница 2: ...ut 3 TO3 TO3 close 2 10 Triac output Common TO3 TO4 11 Triac output 4 TO4 TO4 open 12 Analog input 1 AI1 13 Analog input 2 AI2 14 Analog input 3 AI3 15 Analog output 1 AO1 16 Analog output 2 AO2 Setti...

Страница 3: ...TO2 open Default value floating 4 Set TO1 signal ramp Display shows select TO1 ramp Select which ramp you want for TO1 You can choose Changeover ramp Heating ramp 1 Heating ramp 2 Cooling ramp 1 Cool...

Страница 4: ...t will automatically open at 0 of the demand Range 20 40 60 80 Increment 20 Default value 40 40 of the demand 11 Set TO3 output signal Display shows select TO3 output signal Select which signal output...

Страница 5: ...e signal output Default value on off 17 Set TO4 signal ramp Display shows select TO4 ramp Select which ramp you want for TO4 You can choose Changeover ramp Heating ramp 1 Heating ramp 2 Cooling ramp 1...

Страница 6: ...fault value 10 0 Volt 23 Minimum position of AO1 output Only if OFF hasn t been selected at step 19 Display shows min POS ao1 output percent and the value of the minimum position of the AO1 output Ple...

Страница 7: ...ame function AI2 will not be functional Default value OFF 29 Set AI3 input signal Display shows select AI3 input signal Select which signal you want for AI3 input You can choose Same as AI1 see step 2...

Страница 8: ...ult value 2 0 C 4 F 37 C Proportional band of cooling ramp2 Display shows control ramp 2 cooling and the value of the cooling ramp2 proportional band cooling symbol is also displayed Please select the...

Страница 9: ...ctivate reactivate cooling contact Please select the desired value of the delay cooling contact Range 0 to 15 min Increment 1 min Default value 2 min 44 Integration time factor setting Display shows a...

Страница 10: ...50 to 104 F max offset 5 C Increment 0 1 C 0 2 F F3 C External temperature sensor calibration If EtS has been selected at step 27 28 or 29 of programming mode Display shows extern temper sensor offse...

Страница 11: ...function If you do not need to balance system select No You will leave the balancing menu and return to operation mode If you want to balance system select YES In this case you will leave the balancin...

Страница 12: ...our 2B Actual time setting cont d Display shows set minutes and the value of the actual minute Use the arrows to set the actual time minute Range 00 to 59 min Increment 1 min 2C Actual day setting Dis...

Страница 13: ...effective between the time set at this step until the time set for Tuesday Event 1 Select the time you wish Event 2 to begin for Monday Range Monday Event 1 15 minutes to Monday 23 45 Increment 15 min...

Страница 14: ...15 minutes Increment 15 minutes Default value 20 00 8E C MO Monday schedule programming Event 2 cooling set point Display shows adjust event 2 cooling setpnt and the value of the cooling set point tem...

Страница 15: ...heating setpnt and the value of the heating set point temperature during this period MO moon and heating symbols are also displayed Please select the desired heating set point temperature for the Eve...

Страница 16: ...display and adjustment To display the set point press two times on or Set point will be displayed during 3 seconds To adjust set point press on or while the temperature set point is displayed Note If...

Отзывы: