TRO24T4XYZ3
Specification & Installation Instructions
15
Step Display
Description
Values
8I
C
MO
Monday schedule programming Event 3 heating set point:
Display shows
“adjust event 3 heating setpnt”
and the value of the
heating set point temperature during this period.
MO
, half sun, moon and
heating symbols are also displayed.
Select the desired heating set point temperature for the Event 3 period.
The maximum value is restricted by the Event 3 cooling set point. (step #
8H)
Set point range:
10 to 40ºC [50 to 104ºF]
Increment: 0.5ºC [1ºF]
Default value: 20ºC [68ºF]
8J
MO
..
..
Monday schedule programming Event 4:
Display shows
“23:45:”
and
E4
.
MO
and moon symbols are also displayed.
Note: Event 4 temperature setting will be effective between the time set at
this step until the time set for Tuesday Event 1.
Please select the time you wish Event 4 to begin for Monday.
Range: Monday Event 3 +15
minutes
to Monday 23:45
Increment: 15 minutes
Default value: 23:45
8K
C
MO
Monday schedule programming Event 4 cooling set point:
Display shows
“adjust event 4 cooling setpnt”
and the value of the
cooling set point temperature during this period.
MO
, moon and cooling
symbols are also displayed.
Select the desired cooling temperature set point for the Event 4 period.
The minimum value is restricted by the Event 4 heating set point. (step #
8L)
If Off is selected, the thermostat will be in off mode during this period. (If Off
is selected, skip to Step #9)
Set point range:
10 to 40ºC [50 to 104ºF] or Off
Increment: 0.5ºC [1ºF]
Default value: 28ºC [72ºF]
8L
C
MO
Monday schedule programming Event 4 heating set point:
Display shows
“adjust event 4 heating setpnt”
and the value of the
heating set point temperature during this period.
MO
, moon and heating
symbols are also displayed.
Please select the desired heating set point temperature for the Event 4
period.
The maximum value is restricted by the Event 4 cooling set point. (step #
8K)
Set point range:
10 to 40ºC [50 to 104ºF]
Increment: 0.5ºC [1ºF]
Default value: 16ºC [68ºF]
9
MO TU WE
Copy schedule:
Display shows
“copy schedul”
. You can copy the schedule from a
previously programmed day to another day.
Day programmed will appear and day to copy to will flash. If many days
have been programmed, you can select the day you want to copy. If you
want to copy, select “yes”. If you don’t want to copy, select “no”.
Ex.: for Wednesday scheduling, you can press on the or button to
choose between
MO
“yes”
,
TU
“yes”
,
MO TU
“no”
If you have selected
“no”
repeat step #8 with the new day. Repeat this step
with all the day. If you go back in the menu, you can see the entire
scheduling step #8 even if you copied before. This operation enables you
to revise your value or to modify some parameters
When every day has a schedule established,
Go to step #10.
Ex.: for Wednesday
MO TU
TU WE
MO
WE
Default value: NO
10
Locking the set point derogation:
Display shows
“user setpnt overide locked”
and the status of the function.
You can lock or unlock the set point derogation by end user.
If locked,
“yes”
and lock symbol will appear and user can’t derogate the set
point.
Default value:
Unlocked (NO)
11
Adjust the control mode:
Display shows
“adjust temper control mode”
.
Cooling and heating
symbols are also displayed.
Select which control mode you want to authorize:
Automatic
cooling and heating
, cooling or heating, heating only or cooling
only.
If you want to authorize this entire mode, choose Automatic mode.
Default value:
Automatic cooling and heating