Step Display
Description
Values
5
Number of events/day:
Display shows
“Select 2 or 4 events per day”
.
You can select 2 events
,
or 4 events
,
,
,
per
day. Your selection will be applied for each day of the week.
If you selected 4 events, go directly to step #8.
Default value: 2
events
6A
MO
..
..
Monday schedule programming Event 1:
Display shows
“6:00:”
and
E1
.
MO
and sun symbols are also displayed.
Note: Monday Event 1 temperature setting will be effective between the
time set at this step until the time set for Monday Event 2.
Set the Monday Event 1 start time.
Range: 00:00 to Monday Event 2
start time -15 minutes
Increment: 15 minutes
Default value: 6:00
6B
C
MO
Monday schedule programming Event 1 cooling setpoint:
Display shows
“adjust event 1 cooling setpnt”
and the value of the cooling
set point temperature during this period.
MO
, sun and cooling symbols are
also displayed.
Select the desired cooling temperature set point for the Event 1 period.
The minimum value is restricted by the Event 1 heating set point. (step #
6C)
If Off is selected, the thermostat will be in off mode during this period. (If Off
is selected, skip to Step #6D)
Set point range:
10 to 40ºC [50 to 104ºF] or Off
Increment: 0.5ºC [1ºF]
Default value: 22ºC [72ºF]
6C
C
MO
Monday schedule programming Event 1 heating set point:
Display shows
“adjust event 1 heating setpnt”
and the value of the
heating set point temperature during this period.
MO
, sun and heating
symbols are also displayed.
Select the desired heating set point temperature for the Event 1 period.
The maximum value is restricted by the Event 1 cooling set point. (step #
6B)
Set point range:
10 to 40ºC [50 to 104ºF]
Increment: 0.5ºC [1ºF]
Default value: 20ºC [68ºF]
6D
MO
..
..
Monday schedule programming Event 2:
Display shows
“20:00:”
and
E2
.
MO
and moon symbols are also displayed.
Note: Event 2 temperature setting will be effective between the time set at
this step until the time set for Tuesday Event 1.
Select the time you wish Event 2 to begin for Monday.
Range: Monday Event 1 +15
minutes
to Monday 23:45
Increment: 15 minutes
Default value: 20:00
6E
C
MO
Monday schedule programming Event 2 cooling set point:
Display shows
“adjust event 2 cooling setpnt”
and the value of the
cooling set point temperature during this period.
MO
, moon and cooling
symbols are also displayed.
Select the desired cooling temperature set point for the Event 2 period.
The minimum value is restricted by the Event 2 heating set point. (step #
6F)
If Off is selected, the thermostat will be in off mode during this period. (If Off
is selected, skip to Step #7)
Set point range:
10 to 40ºC [50 to 104ºF] or Off
Increment: 0.5ºC [1ºF]
Default value: 28ºC [72ºF]
6F
C
MO
Monday schedule programming Event 2 heating set point:
Display shows
“adjust event 2 heating setpnt”
and the value of the
heating set point temperature during this period.
MO
, moon and heating
symbols are also displayed.
Please select the desired heating set point temperature for the Event 2
period.
The maximum value is restricted by the Event 2 cooling set point. (step #
6E)
Set point range:
10 to 40ºC [50 to 104ºF]
Increment: 0.5ºC [1ºF]
Default value: 16ºC [68ºF]
7
MO TU WE
Copy schedule:
Display shows
“copy schedul”
. You can copy the schedule from a
previously programmed day to another day. Day programmed will appear
and day to copy to will flash. If many days have been programmed, you
can select the day you want to copy. If you want to copy, select “yes”, If
you don’t want to copy, select “no”.
Ex.: for Wednesday scheduling, you can press on the or button to
choose between
MO
“yes”
,
TU
“yes”
,
MO TU
“no”
If you have selected
“no”
repeat step #6 with the new day.Repeat this step
with all the day. If you go back in the menu, you can see the entire
scheduling step #6 even if you copied before. This operation enables you
to revise your value or to modify some parameters.
When every day has a schedule established,
Go directly to step #10.
Ex.: for Wednesday
MO TU
TU WE
MO
WE
Default value: NO