Networkable Fan Coil Controller 

Specification and Installation Instructions 

 

www.neptronic.com 

 

Page | 6

 

Wiring 

We strongly recommend that all Neptronic products be wired to a separate grounded transformer and that transformer shall service 
only Neptronic products. This precaution will prevent interference with, and/or possible damage to incompatible equipment. 

 

 

 

 

 

 

 

 

 

 

 

ON

1  

2  

3  

4  

5  

6  

7  

8

ON

1  

2  

3  

4

DS2

DS1

Fuse 10A

F1

1
2
3
4
5
6
7

TFL24 and TDU

1

2

3

24Vac

COM

COM BUS

IN B-

IN A+

COM

3

DS1 DIP Switch

1 = AI3
2 = AI4
3 = AI5
4 = AI6

Off: Temp. sensor (10k ohms)
On: Voltage  (0-10Vdc)

DS2 DIP Switch

The 8 DIP switch es 
represent  a binary logic to 
calculate the M AC address .
Default  = all OFF

1

2

Optional: 

connect 

to enable 

service port

To other

BACnet 

device

COM

24Vac

DI1

1

DI2

2

COM

3

DI3

4

DI4

5

AI3

1

AI4

2

COM

3

AI5

4

AI6

5

AI1

1

COM

2

AI2

3

COM

3

AO3

4

AO4

J

P

1

T

O

3

 /

 4

INT   EXT

PWR

STATUS

8

7

6

5

4

3

2

1

J

P

2

T

O

1

 /

 2

IN

T

E

X

T

RET

Line

RET

TB7

TB8

TB9

TB10

TB11

AO1

1

AO2

2

1

2

5

TB6

TB5

T

B

1

T

B

4

JP3

None

120 Ohms

COM

TO4

TO3

TI3 | TI4

COM

TO2

TI1 | TI2

TO1

COM

T

B

3

RET

RET

T

B

2

DO2 (3A)

6

5

4

3

2

1

4

3

2

1

DO1 (3A)

RET

FAN MED (7A)

FAN LOW (7A)

FAN HIGH (7A)

DO3 (3A)

4 analog outputs

(config.)

Cool, heat, reheat, changeover, fan, 
humidify & dehumidify by cooling

0-10Vdc (configurable min /max)
Direct or reverse

4 analog inputs

(config.)

0-10Vdc or 10kOhms
via DIP switch

NSB or OCC Sensor

Power Input

 (24 or 240Vac)

Applies to all relays and digital outputs

3-speed fan

4

3

2

1

RET

DO4 (3A)

4 digital outputs

(config.)

Cool, heat, reheat, changeover , 
humidify  & dehumidify by cooling .

Configurable close /open percent 
Direct or reverse

LD3 = TX

LD4 = RX

4 TRIAC outputs

(config.)

Cool, heat, reheat, & changeover

On/Off (config close /open percent )
Floating  (config float time )
Pulse (heat and reheat only )

Direct or reverse

JP2 TO1 /2

 (Input Voltage )

INT = 24Vac supplied internally  from TB11
EXT = Apply 24Vac to pin  1 of TB1

JP1 TO3 /4

(Input Voltage )

INT = 24Vac supplied internally  from TB11
EXT = Apply 24Vac to pin  5 of TB1

JP3

 (End of line )

None = No end of line
120

Ω = Last node on network

LEDs

POWER

= On when  24Vac applied to TB 11

STATUS 

= Flashes when communicating with thermostat

LD3 

= Flashes when transmitting  (TX) via BACnet 

LD4 

= Flashes when receiving  (RX) via BACnet

EFCB10TU4

24Vac (input)

With low voltage model  (24Vac), TB11 is an 
input that applies to left side of board and all 
TRIAC outputs  (independent of TB 4).

EFCB12TU4

24Vac (output )

With line voltage model  (240Vac ), TB11 
provides a  24Vac low voltage output .

Input

Output

3 digital inputs

(config.)

Override, flow switch , window /door 
contact , dirty filter , overheat , selector 
switch

External Temperature Sensor (10kOhms)

External Temperature Sensor 
(0-10 Vdc or 2-10 Vdc)

Changeover Sensor

Содержание TFL24

Страница 1: ...floating pulse or modulating 0 10 Vdc Cool Heat Reheat Reheat with fan Changeover Fan Humidify and Dehumidify by cooling Features Built in configurable fan coil algorithms Up to 10 inputs and 15 outputs configurable Select direction on digital inputs and all outputs Selectable proportional control band and dead band Selectable fan speed contacts No occupancy and NSB override Independent cool heat ...

Страница 2: ...ature 0ºC to 50ºC 32ºF to 122ºF Storage temperature 30ºC to 50ºC 22ºF to 122ºF Relative Humidity 5 to 95 non condensing Enclosure protection IP 30 EN 60529 Weight 635 g 1 4 lb Dimensions A 6 30 160mm B 5 00 126mm C 2 25 57mm Thermostat Specifications Description TFL24 and TDU Series Temperature Sensor TFL24 and TDU Setpoint Range 10ºC to 40ºC 50ºF to 104ºF Control Accuracy 0 5ºC 0 9ºF 22ºC 71 6ºF ...

Страница 3: ... Temp RH CO2 PIR Color TDU10 100 grey LCD white enclosure TDU10 101 TDU10 102 TDU10 103 TDU10 104 TDU10 105 TDU10 106 TDU10 107 TDU10 Series Model Temp RH CO2 PIR Color TDU40 100 black LCD black enclosure TDU40 101 TDU40 102 TDU40 103 TDU40 104 TDU40 105 TDU40 106 TDU40 107 TDU40 Series Model Temp RH CO2 PIR Color TDU70 100 black LCD white enclosure TDU70 101 TDU70 102 TDU70 103 TDU70 104 TDU70 10...

Страница 4: ...Saving Mode NSB OCC Schedule Time ppm Parts Per Million C F RH ºC Celsius Scale ºF Fahrenheit Scale RH Humidity A Automatic Mode Cooling Heating Fan Humidify De humidify Mounting Instructions TFL24 CAUTION Remove power to avoid a risk of malfunction A Remove the captive screw that s holding the base and the front cover of the unit together B Lift the front cover of the unit to separate it from the...

Страница 5: ...ostat using the screw supplied BACnet or Modbus Address DIP Switch DS2 MAC address for communication are selectable by DIP switch using binary logic If you do not change device instance in program mode it will be automatically modified according to the MAC address Note Avoid using addresses above 246 when selecting Modbus MAC address MAC Address DS 1 1 DS 2 2 DS 3 4 DS 4 8 DS 5 16 DS 6 32 DS 7 64 ...

Страница 6: ... 10Vdc configurable min max Direct or reverse 4 analog inputs config 0 10Vdc or 10kOhms via DIP switch NSB or OCC Sensor Power Input 24 or 240Vac Applies to all relays and digital outputs 3 speed fan 4 3 2 1 RET DO4 3A 4 digital outputs config Cool heat reheat changeover humidify dehumidify by cooling Configurable close open percent Direct or reverse LD3 TX LD4 RX 4 TRIAC outputs config Cool heat ...

Страница 7: ...r the action button or the button used to access the menus and save changes is different in the thermostats Use the following menu overviews with the appropriate action button as per your thermostat Action Buttons on Thermostat Action Button Task TFL24 TDU Press to access the programming menus and save any changes Press to return to the previous step without saving Mode Selector Jumper RUN Operati...

Страница 8: ...Networkable Fan Coil Controller Specification and Installation Instructions www neptronic com Page 8 Analog Inputs Menu Overview 1 of 8 AI1 and AI3 ...

Страница 9: ...Networkable Fan Coil Controller Specification and Installation Instructions www neptronic com Page 9 Digital Inputs Menu Overview 2 of 8 DI1 to DI4 ...

Страница 10: ...Networkable Fan Coil Controller Specification and Installation Instructions www neptronic com Page 10 TRIAC Outputs Menu Overview 3 of 8 TO1 to TO4 ...

Страница 11: ...Networkable Fan Coil Controller Specification and Installation Instructions www neptronic com Page 11 Analog Outputs Menu Overview 4 of 8 AO1 to AO4 ...

Страница 12: ...Networkable Fan Coil Controller Specification and Installation Instructions www neptronic com Page 12 Digital Outputs Menu Overview 5 of 8 DO1 to DO4 ...

Страница 13: ...Networkable Fan Coil Controller Specification and Installation Instructions www neptronic com Page 13 Settings Menu Overview 6 of 8 Temp Fan Settings and Ramps ...

Страница 14: ...Networkable Fan Coil Controller Specification and Installation Instructions www neptronic com Page 14 Network and Calendar Menu Overview 7 of 8 Network Time and Options ...

Страница 15: ...le Fan Coil Controller Specification and Installation Instructions www neptronic com Page 15 Humidity Menu Overview 8 of 8 Humidity Only available when a humidity sensor thermostat is connected to the controller ...

Страница 16: ...nd Fan speed Low Low Fan speed Low Fan speed Low Medium Fan speed Medium Fan speed Medium High Fan speed High Fan speed High Cool Auto Speed Fan speed cool demand Fan speed Low Low Fan speed Low Fan speed Low Medium Fan speed Medium Fan speed Medium High Fan speed High Fan speed High Auto H C Auto Speed Fan speed heat cool demand Fan speed Low Low Fan speed Low Fan speed Low Medium Fan speed Mediu...

Страница 17: ...Menu b Password 637 Network Settings Menu 4 If you enter the wrong password the thermostat displays Eror and returns to Operation Mode The thermostat will return to normal mode if you navigate through the entire menu and do not make any selection or if you do not press any key for 5 minutes The changed values will be saved automatically Menu 372 Sensor Offset Menu 637 Network Settings Reset to Fac...

Страница 18: ... press both the and keys for 3 seconds To display the setpoint press the or key twice The setpoint appears for 5 seconds To adjust the setpoint press the arrow keys while the temperature is displayed If the setpoint adjustment has been locked the lock symbol appears C Actual demand Room temperature Appears if in Night Setback NSB or Occupancy OCC mode Flashes if overridden by user RH Alternates be...

Страница 19: ...n Automatic speed Available only if enabled in Programming Mode Low speed Medium speed High speed Off Off is not selectable by the user it appears only if the Control Mode is Off and it indicates that the user can not change the speed of the fan Night Setback NSB This function is only available if you ve set DI3 to nSb Night setback contact If the DI3 contact is triggered the thermostat enters NSB...

Страница 20: ... need to find the nearest Neptronic authorized distributor please consult www neptronic com 400 Lebeau blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service fax 514 333 1091 Monday to Friday 8 00am to 5 00pm Eastern time ...

Отзывы: