SKG4-E Gas Fired Humidifier
Installation Instructions and User Manual
Page | - 26 -
3 Module Humidifiers: SKG4-E2503 to SKG4-E3003
Ø
½” (15mm)
Ø3" (76mm) (x3)
Ø5" (125mm)
Min. 7° pipe slope
Insulated pipe
Air Duct
Static pr
2" (50mm)
min
7° p
ipe s
lope
Total length of steam conduit must not exceed 16ft (5m)
Illustration 25 - Multi-Steam Steam Pipe Work (SKG4-E2503 to 3003)
Three Ø76mm steam outlets attached to a single Ø125mm feed pipe must be connected to a Multi-
Steam with a suitable reduction at the lowest point to allow a Ø15mm condensate drain from the main
steam supply.
4 Module Humidifiers: SKG4-E3504 to SKG4-E4004
min
7° p
ipe s
lope
ؽ
” (15mm)
Static pr
2" (50mm)
ؾ
” (20mm)
Min. 7° pipe slope
Insulated pipe
Air Duct
Ø3"
(76mm)
(x2)
Ø4"
(100mm)
x2
Total length of steam conduit must not exceed 16ft (5m)
Illustration 26 - Multi-Steam Steam Pipe Work (SKG4-E3504 to 4004)
Two Ø76mm steam outlets attached to a single Ø100mm feed pipe must be connected to a single
Multi-Steam with a suitable reduction at the lowest point to allow a Ø15mm condensate drain from the
main steam supply. This must be reproduced two times.
If the two Ø15mm condensate pipes are connected, the common condensate drain must be Ø20mm.