Networkable VAV Controller 

Specification and Installation Instructions 

 

www.neptronic.com 

EVCB14NIT4X 

Page | 13

 

Operation Menus  

This menu is accessible through normal operation mode. The Mode Selector jumper (JP1) of the thermostat must be set to the 
“RUN” position (Operation Mode). Refer to Wiring on page 5.  
 
1.  Press the 

[*]

 and 

[

buttons simultaneously for 5 seconds. The 

“Enter Password”

 screen appears. 

2.  Enter the password within 1 minute by using the arrow keys to increase or decrease the value and the 

[*]

 and 

[

]

 buttons to 

toggle between the digits.  

a.  Password 

372

 = Temperature Offset Menu 

b.  Password 

637

 = Network Settings Menu 

c. 

Password 

757

 = Airflow Balance Mode 

3.  If

 

you enter the wrong password, the 

thermostat displays “

Eror

” and returns to Operation Mode. The thermostat will return to 

normal mode if you navigate through the entire menu and do not make any selection, or if you do not press any key for 5 
minutes. The changed values will be saved automatically. 

Menu 372 

– Temperature Offset 

1.

 

“Intern Temp Sensor Offset” 

 

 

Range: 

 

Offset: 
Increment: 

10 to 40ºC  

[50 to 104ºF]   

Max ± 5ºC  

 

0.1ºC    

 

[0.2ºF] 

Compare the displayed temperature reading with a known value from a thermometer. To offset or calibrate the sensor, use the 
arrows key to set the desired temperature reading. This is useful for thermostats installed in areas where the temperature read 
is s

lightly different than the room’s actual temperature. For example, a thermostat placed right under the air diffuser.  

If the thermostat is set to use an external temperature sensor (

EtS

), the thermostat displays “OFF”.  

2.

 

“Extern Temper Sensor Offset” 

 

 

Range: 

 

Offset: 
Increment: 

0 to 50ºC   

[41 to 122ºF]   

Max  ± 5ºC 
 0.1ºC   

 

[0.2ºF] 

This option appears if you’ve set one of the analog inputs to 

EtS

 (External temperature sensor). When the thermostat is 

connected to the appropriate analog input, the display shows the temperature read by the external temperature sensor. Adjust 
the offset by comparing it with a known value (e.g. thermometer). If the sensor is not connected or short circuited, then the unit 
displays the sensor's limit.

 

  

3.

 

“Input3 Reading” 

 

 

Range: 

 

250mV (0") to 4000mV (1")   

Displays the voltage output value in mV of the pressure sensor. 

4.

 

“Input3 Minimum Reading 

 

 

Range: 

 

Default: 

10mV to 180mV 
60mV 

This setting represents the deadband of the pressure sensor in mV. For advanced users or special applications only. We 
recommend that you use the default setting of 60mV. 

Menu 637 

– Network Settings 

 

End 

(exit menu)

CPYc 

(copy config)

bAC 

(BACnet)

mOd 

(Modbus)

Network Config

tYPe 

(Type)

= scroll menu items

Network Choice

bAC 

(BACnet)

mOd

 (Modbus)

= select / set value

Modbus Auto Baud Rate

No 

(Manual)

Yes

 

(Automatic)

= select / set value

BACnet Auto Baud Rate

No 

(Manual)

Yes

 

(Automatic)

= select / set value

= select / set value

Start Address

(0-254)

If type = bAC, menu contains 
“tYpe”, “bAC” and “CPYc”

If type = mOd, menu contains 
“tYpe and “mOd”

Modbus Baud Rate

57.6k 

(9.6k, 19.2k, 38.4, 57.6k)

Bacnet Baud Rate

76.8k 

(9.6k, 19.2k, 38.4, 76.8k)

MSTP MAC Address

(0-254)

Modifiable only if Auto Baud Rate 
set to “No”.

Modifiable only if Auto Baud Rate 
set to “No”.

Modifiable only if all DS1 DIP 

switches are set to OFF.

0153000

(device instance)

Go to 

“CPYc"

MSTP MAX Master

127 

(1-127)

OP1s

 (odd parity, 1 stop bit)

Modbus Comport Config

NP2s

 (no parity, 2 stop bits)

EP1s

 (even parity, 1 stop bit)

Modbus Address

(1-246)

Modifiable only if all DS1 DIP 

switches are set to OFF.

Returns to run mode

End Address

(0-254: max=start + 63)

Confirm Copy Config

No

 (cancel)

Yes

 (confirm)

Copy Config

in 

(in progress)

Returns to run mode

Copy Config Result

Succeed

1001

AV.166

AV.165

1000

BV.90

AV.167

Exit menu and return 

to normal operation

Go to “BACnet Auto Baud Rate"

Go to “Modbus Auto Baud Rate"

Returns to 
run mode

*** You must press the       button to save any changes *** 
*** Pressing the       button returns to the previous step without saving ***

Note: The BACnet Schedule is 
not copied during the 

Copy 

Config

 operation. 

Содержание EVCB14NIT4X/TRL24 Series

Страница 1: ...play Network service port via on board mini USB connector Manual night set back or no occupancy override Multi level lockable access menu and setpoint Selectable Fahrenheit or Celsius scale 3 wire con...

Страница 2: ...Nm 4 Slide the mounting bracket under the actuator Ensure free movement of the slot at the base of the actuator Place the bracket pin at mid distance of the slot 5 Affix the bracket to the ductwork w...

Страница 3: ...by 90 Display resolution 1 ppm Electrical connection 3 wires to VAV controller and 2 wires to BACnet Modbus network 0 8 mm2 18 AWG minimum Network service port Mini USB connector Power supply 24Vac o...

Страница 4: ...the screw BACnet or Modbus Address DIP Switch DS1 MAC address for communication are selectable by DIP switch using binary logic If you do not change device instance in program mode it will be automati...

Страница 5: ...g DI2 Override normally cool heat DI1 OCC open close NSB open close 3 2 1 COM 24Vac input TO2 TO1 TO1 4 TO2 7 6 5 COM 24Vac input TO3 TO4 TO3 8 TO4 4 TRIAC outputs config Cool 1 or 2 heat 1 or 2 CO2 O...

Страница 6: ...tion Motor Minimum Pos Cooling 10 0 100 Motor Minimum Pos Heating 10 0 100 ClHt cool heat Control Apps Cl cool only scroll menu items APPS APPS YES confirm Confirm Control apps NO cancel The APPS repr...

Страница 7: ...ange 2000 ppm CO2 Setpnt 800 ppm Go to AI2 Go to AI2 Go to AI2 ASt Air supply temp sensor CO2 carbon dioxide StFl setpnt airflow 0 10Vdc AI2 Signal Type EtS external temp sensor OFF disabled NoHt norm...

Страница 8: ...Networkable VAV Controller Specification and Installation Instructions www neptronic com EVCB14NIT4X Page 8 TRIAC Outputs Menu 3 of 7 TO1 and TO2...

Страница 9: ...DIR direct REV reverse Go to AO1 MSV 30 MSV 32 AV 81 AV 76 AV 83 AV 82 AV 84 BV 31 BV 34 BV 35 If CO2 was selected Go to TO4 Close Percent ANLg analog 0 10Vdc CH1 cool heat 1 CO2 carbon dioxide Hr2 he...

Страница 10: ...R direct REV reverse CO2 carbon dioxide Hr2 heating ramp 2 Hr1 heating ramp 1 Cr2 cooling ramp 2 Cr1 cooling ramp 1 AO2 Ramp OFF select set value AO2 Minimum Voltage 0 0 Vdc Go to tmp AO2 Maximum Volt...

Страница 11: ...Networkable VAV Controller Specification and Installation Instructions www neptronic com EVCB14NIT4X Page 11 Settings Menu 6 of 7 Temp Motor and Settings...

Страница 12: ...nth 1 1 12 Day 1 1 31 Go to OPt scroll menu items 1001 AV 166 AV 165 1000 BV 90 AV 167 Local Time Local Date Local Time Local Date Local Date Refer to Copy Config Annnex for a complete list of message...

Страница 13: ...shows the temperature read by the external temperature sensor Adjust the offset by comparing it with a known value e g thermometer If the sensor is not connected or short circuited then the unit disp...

Страница 14: ...s 1 10 100 Maximum Cooling Airflow 1000 Min cool airflow to Kfactor Airflow Setting COOl HEAt Minimum Cooling Airflow 200 0 to max cool airflow Maximum Heating Airflow 1000 Min heat airflow to Kfactor...

Страница 15: ...ustment has been locked Setpnt Locked the lock symbol appears Humidity If enabled in the Options menu see Settings Menu 7 of 7 Ramps Network Time and Options on page 12 the thermostat displays the tem...

Страница 16: ...ers NSB or No Occupancy Mode the symbol appears and uses the NSB or OCC heating and cooling setpoints If not locked you can override the night set back or no occupancy mode for a predetermined period...

Страница 17: ...ype On Off On Off On Off On Off On Off On Off On Off TO3 Close Pos 40 40 40 40 40 40 40 TO3 Open Pos 0 0 0 0 0 0 0 TO4 Ramp HR2 HR2 HR2 HR1 OFF HR1 HR1 TO4 Signal Type Pulse On Off Pulse On Off On Off...

Страница 18: ...Notes...

Страница 19: ...Notes...

Страница 20: ...need to find the nearest Neptronic authorized distributor please consult www neptronic com 400 Lebeau blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 51...

Отзывы: