Networkable VAV Controller

Specification and Installation Instructions

 

www.neptronic.com 

EVCB Standard 

Page | 2

 

Controller Specifications 

Description 

EVCB Series

Torque 

70 in.lb. [8 Nm] at rated voltage

 

Power consumption 

10 VA max 

Running time through 90º 

90 seconds 

Power supply 

22 to 26 Vac 50/60 Hz 

Inputs 

2 Universal inputs (Thermistor 10KΩ Type 3, digital 24Vac/dry contact, or 0-10Vdc) 
2 digital inputs 

On-board differential pressure sensor 

0-1.0” WC (available on pressure independent models) 

Outputs 

2 analog outputs (0-10 Vdc or 2-10Vdc; selectable) 
Up to 4 TRIAC outputs 24 Vac, 500mA max thermal fuse in series with each TRIAC output (on/off, pulse, 
or 2 floating outputs) 

Real Time Clock 

Real-time clock (RTC) with super capacitor backup (approximately 3 days) 

BACnet 

BACnet

®

 MS/TP @ 9600, 19200, 38400 or 76800 bps (B-ASC) 

Modbus 

Modbus RTU slave @ 9600, 19200, 38400 or 57600. Selectable parity and stop bit configuration: 
No parity, 2 stop bit | Even parity, 1 stop bit | Odd parity, 1 stop bit  

Communication connection 

24 AWG twisted-shield cable (Belden 9841 or equivalent).  
Maximum 50ft (15m) between controller and thermostat 

Electrical connection 

0.8 mm

[18 AWG] minimum 

Operating temperature 

0ºC to 50ºC [32ºF to 122ºF] 

Storage temperature 

-30ºC to 50ºC [-22ºF to 122ºF] 

Relative Humidity 

5 to 95% non condensing 

Weight 

1.8 kg. [4 lb] 

 

The actuator performs an auto-stroke on power up. When changing the actuator adjustment screws, cycle power to initiate the 
auto-stroke.  

EVC with a built-in 70 in. lb. Actuator 

 

Dimensions

A = 2.85” | 73mm 
B = 4.85” | 123mm 
C = 1.00” | 24mm 
D = 2.36” | 60mm 
E = 3.27” | 83mm

 

Thermostat Specifications 

Description 

TRL24 and TDU Series

Temperature Sensor (TRL24 and TDU) 

Setpoint range 

10ºC to 40ºC [50ºF to 104ºF] 

Control accuracy 

Temperature: ±0.4ºC [0.8ºF] 

Display resolution 

±0.1ºC [0.2ºF] 

Humidity Sensor

 

(TRLH24, TRLGH24 and TDU models with Humidity Sensors)

 

Sensor range 

5 to 95%RH 

Display resolution 

0.1% 

CO

2

 Sensor (TRLG24, TRLGH24 and TDU models with CO

2

 Sensors) 

Operating principle 

Self-calibrating, Non-Dispersive Infrared (NDIR) 

Sensor Range 

0 to 2000 ppm 

Setpoint range 

100 to 2000 ppm 

Accuracy 

±30 ppm ±3% of reading  

Response time 

2 minutes by 90% 

Display resolution 

1 ppm 

Other

 

Electrical connection 

3 wires to VAV controller and 2 wires to BACnet/Modbus network  |  0.8 mm

[18 AWG] minimum 

Network service port 

Mini USB connector 

Power supply 

24Vac  

Power consumption 

1VA 

Operating temperature 

0ºC to 50ºC [32ºF to 122ºF] 

Storage temperature 

-30ºC to 50ºC [-22ºF to 122ºF] 

Relative humidity 

5 to 95 % non condensing 

Enclosure protection 

IP 30 (EN 60529) 

Weight 

120 g. [0.25 lb] 

 

 

C

A

B

D

Содержание EVCB14NDT4S

Страница 1: ...angeover Supply exhaust requires an additional EVC Features Field configured VAV algorithms inputs and outputs Built in actuator 70 lb in On board differential pressure sensor select models Select dir...

Страница 2: ...0 C to 50 C 32 F to 122 F Storage temperature 30 C to 50 C 22 F to 122 F Relative Humidity 5 to 95 non condensing Weight 1 8 kg 4 lb The actuator performs an auto stroke on power up When changing the...

Страница 3: ...ls Model Temp RH CO2 PIR Color TDU10 100 grey LCD white enclosure TDU10 101 TDU10 102 TDU10 103 TDU10 104 TDU10 105 TDU10 106 TDU10 107 TDU10 Series Model Temp RH CO2 PIR Color TDU40 100 black LCD bla...

Страница 4: ...C Celsius Scale F Fahrenheit Scale RH Humidity A Automatic Mode Cooling Heating Fan Mechanical Installation Actuator 1 Manually close the damper blades and position the actuator to 0 or 90 2 Slide the...

Страница 5: ...riate connections D Mount the thermostat onto the wall plate To mount the thermostat correctly place the top of the thermostat on the mounting plate first and push it into the grooves to snap it into...

Страница 6: ...M 2 digital inputs config DI2 Override normally cool heat DI1 OCC open close NSB open close 3 2 1 COM 24Vac input TO2 TO1 TO1 4 TO2 7 6 5 COM 24Vac input TO3 TO4 TO3 8 TO4 4 TRIAC outputs config Cool...

Страница 7: ...er the action button or the button used to access the menus and save changes is different in the thermostats Use the following menu overviews with the appropriate action button as per your thermostat...

Страница 8: ...Configuration ON enabled Pressur Mode Auto Change OFF disabled Motor Minimum Pos Cooling 10 0 100 Motor Minimum Pos Heating 10 0 100 ClHt cool heat Control Apps Cl cool only scroll menu items APPS AP...

Страница 9: ...10Vdc AI2 Signal Type EtS external temp sensor OFF disabled NoHt normally heat NoCl normally cool SENs sensor CH Over Setpnt 24 C select set value AI2 CO2 Maximum Range 2000 ppm CO2 Setpnt 800 ppm Go...

Страница 10: ...llows demand CO2 carbon dioxide Hr2 heating ramp 2 Hr1 heating ramp 1 Cr2 cooling ramp 2 Cr1 cooling ramp 1 TO2 Ramp OFF select set value MSV 27 TO2 Go to TO1 Close Percent Go to TO1 DIR REV OPt Optio...

Страница 11: ...mum Voltage 0 0 Vdc Go to tmp AO2 Maximum Voltage 10 0 Vdc Go to tmp Main Menu Sub Menu Configuration AO1 AO2 TO4 TO3 TO2 Output Config TO1 scroll menu items scroll menu items MSV 20 MSV 22 AV 70 AV 7...

Страница 12: ...0 F 0 5 5 C 1 9 F CR1 Dead Band 0 3 C 0 6 F 0 5 C 0 9 F CR2 Prop Band 2 0 C 4 0 F 0 5 5 C 1 9 F CR2 Dead Band 0 3 C 0 6 F 0 5 C 0 9 F Hr1 Prop Band 2 0 C 4 0 F 0 5 5 C 1 9 F Hr1 Dead Band 0 3 C 0 6 F...

Страница 13: ...in in progress Go to HrS Copy Config Result Succeed Go to HrS select set value Hours 12 0 23 or 1 12 am pm Minutes 00 00 59 Year 15 15 99 Set Time Display format 24 24 hour format 12 AM PM format Mont...

Страница 14: ...tS External temperature sensor When the thermostat is connected to the appropriate analog input the display shows the temperature read by the external temperature sensor Adjust the offset by comparing...

Страница 15: ...inheat airflowto Kfactor Minimum Heating Airflow 200 0to max heat airflow Go to bAL Airflow Balance CLOs close Min minimum flow mA maximum flow OPEn fully opened Close Motor 130 see note Minimum Airfl...

Страница 16: ...rough the following values Airflow Airflow Setpoint Actual Damper Pos Percent Air Supply Temp appears only in pressure independent mode appears only if AST is selected for the Analog Input Signal Type...

Страница 17: ...emp After 5 seconds without any action the thermostat returns to operation mode The air supply temperature appears only if analog input AI1 or AI2 are configured with the AST option Not available on t...

Страница 18: ...Type On Off On Off On Off On Off On Off On Off On Off TO3 Close Pos 40 40 40 40 40 40 40 TO3 Open Pos 0 0 0 0 0 0 0 TO4 Ramp HR2 HR2 HR2 HR1 OFF HR1 HR1 TO4 Signal Type Pulse On Off Pulse On Off On O...

Страница 19: ...Notes...

Страница 20: ...need to find the nearest Neptronic authorized distributor please consult www neptronic com 400 Lebeau blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 51...

Отзывы: