Neptronic EVCB14NDT4S Скачать руководство пользователя страница 14

Networkable VAV Controller

Specification and Installation Instructions

 

www.neptronic.com 

EVCB Standard 

Page | 14

 

Operation Menus  

This menu is accessible through normal operation mode. The Mode Selector jumper (JP1) of the thermostat must be set to the 
“RUN” position (Operation Mode). Refer to Wiring on page 6.  
Note: Since the action buttons are different on TRL and TDU thermostat series, both buttons have been included in the instructions. 
Refer to the Action Buttons on Thermostat section to know and use the button as available on your thermostat.  
1.  Press the 

[

 /

]

 and 

[

 ] 

buttons simultaneously for 5 seconds. The 

“Enter Password”

 screen appears. 

2.  Enter the password within 1 minute by using the arrow keys to increase or decrease the value and the 

[

 /

]

 and 

[

 ]

 

buttons to toggle between the digits.  

a.  Password 

372

 = Temperature Offset Menu 

b.  Password 

637

 = Network Settings Menu 

c.  Password 

757

 = Airflow Balance Mode 

3.  If

 

you enter the wrong password, the thermostat displays “

Eror

” and returns to Operation Mode. The thermostat will return to 

normal mode if you navigate through the entire menu and do not make any selection, or if you do not press any key for 5 
minutes. The changed values will be saved automatically. 

Menu 372 – Temperature Offset 

1.

 

“Intern Temp Sensor Offset” 

 

 

Range: 

 

Offset: 
Increment: 

10 to 40ºC  

[50 to 104ºF]   

Max ± 5ºC  

 

0.1ºC    

 

[0.2ºF] 

Compare the displayed temperature reading with a known value from a thermometer. To offset or calibrate the sensor, use the 
arrows key to set the desired temperature reading. This is useful for thermostats installed in areas where the temperature read 
is slightly different than the room’s actual temperature. For example, a thermostat placed right under the air diffuser.  
If the thermostat is set to use an external temperature sensor (EtS), the thermostat displays “OFF”.  

2.

 

“Extern Temper Sensor Offset” 

 

 

Range: 

 

Offset: 
Increment: 

0 to 50ºC   

[41 to 122ºF]   

Max  ± 5ºC 
 0.1ºC   

 

[0.2ºF] 

This option appears if you’ve set one of the analog inputs to 

EtS

 (External temperature sensor). When the thermostat is 

connected to the appropriate analog input, the display shows the temperature read by the external temperature sensor. Adjust 
the offset by comparing it with a known value (e.g. thermometer). If the sensor is not connected or short circuited, then the unit 
displays the sensor's limit.

 

  

3.

 

“Input3 Reading” 

 

 

Range: 

 

250mV (0") to 4000mV (1")   

Displays the voltage output value in mV of the pressure sensor. Does not appear for EVCB14NDT4S (pressure dependent). 

4.

 

“Input3 Minimum Reading 

 

 

Range: 

 

Default: 

10mV to 180mV 
60mV 

This setting represents the deadband of the pressure sensor in mV. For advanced users or special applications only. We 
recommend that you use the default setting of 60mV. Does not appear for EVCB14NDT4S (pressure dependent) model. 

Menu 637 – Network Settings 

 

End 

(exit menu)

CPYc 

(copy config)

bAC 

(BACnet)

mOd 

(Modbus)

Network Config

tYPe 

(Type)

=  scroll menu items

Network Choice

bAC 

(BACnet)

mOd

 (Modbus)

= select / set value

Modbus Auto Baud Rate

No 

(Manual)

Yes

 

(Automatic)

= select / set value

BACnet Auto Baud Rate

No 

(Manual)

Yes

 

(Automatic)

= select / set value

= select / set value

Start Address

(0-254)

If type  = bAC, menu contains 

"

tYpe

"

"

bAC

"

 and 

"

CPYc

"

If type  = mOd , menu contains 

"

tYpe

"

and 

"

mOd

"

Modbus Baud Rate

57.6k 

(9.6k, 19.2k, 38.4, 57.6k)

Bacnet Baud Rate

76.8k 

(9.6k, 19.2k, 38.4, 76.8k)

MSTP MAC Address

(0-254)

Modifiable only if Auto Baud Rate 
set to "No".

Modifiable only if Auto Baud Rate 
set to "No".

Modifiable only if all DS1 DIP 
switches are set to OFF .

0153000

(device instance)

Go to 

"CPYc"

MSTP MAX Master

127 

(1-127)

OP1s

 (odd parity, 1 stop bit)

Modbus Comport Config

NP2s

 (no parity,  2 stop bits)

EP1s

 (even parity,  1 stop bit)

Modbus Address

(1-246)

Modifiable only if all DS1 DIP 
switches are set to OFF .

Returns to run mode

End Address

(0-254: max=start + 63)

Confirm Copy Config

No

(cancel)

Yes

(confirm)

Copy Config

in 

(in progress)

Returns to run mode

Copy Config Result

Succeed

1001

AV.166

AV.165

1000

BV.90

AV.167

Exit menu and return 

to normal operation

Go to "BACnet Auto Baud Rate "

Go to  "Modbus Auto Baud Rate"

Returns to 
run mode

*** To save any changes , press         on TRL and       on TDU  *** 
*** To the previous step without saving , press

on TRL and TDU ***

Содержание EVCB14NDT4S

Страница 1: ...angeover Supply exhaust requires an additional EVC Features Field configured VAV algorithms inputs and outputs Built in actuator 70 lb in On board differential pressure sensor select models Select dir...

Страница 2: ...0 C to 50 C 32 F to 122 F Storage temperature 30 C to 50 C 22 F to 122 F Relative Humidity 5 to 95 non condensing Weight 1 8 kg 4 lb The actuator performs an auto stroke on power up When changing the...

Страница 3: ...ls Model Temp RH CO2 PIR Color TDU10 100 grey LCD white enclosure TDU10 101 TDU10 102 TDU10 103 TDU10 104 TDU10 105 TDU10 106 TDU10 107 TDU10 Series Model Temp RH CO2 PIR Color TDU40 100 black LCD bla...

Страница 4: ...C Celsius Scale F Fahrenheit Scale RH Humidity A Automatic Mode Cooling Heating Fan Mechanical Installation Actuator 1 Manually close the damper blades and position the actuator to 0 or 90 2 Slide the...

Страница 5: ...riate connections D Mount the thermostat onto the wall plate To mount the thermostat correctly place the top of the thermostat on the mounting plate first and push it into the grooves to snap it into...

Страница 6: ...M 2 digital inputs config DI2 Override normally cool heat DI1 OCC open close NSB open close 3 2 1 COM 24Vac input TO2 TO1 TO1 4 TO2 7 6 5 COM 24Vac input TO3 TO4 TO3 8 TO4 4 TRIAC outputs config Cool...

Страница 7: ...er the action button or the button used to access the menus and save changes is different in the thermostats Use the following menu overviews with the appropriate action button as per your thermostat...

Страница 8: ...Configuration ON enabled Pressur Mode Auto Change OFF disabled Motor Minimum Pos Cooling 10 0 100 Motor Minimum Pos Heating 10 0 100 ClHt cool heat Control Apps Cl cool only scroll menu items APPS AP...

Страница 9: ...10Vdc AI2 Signal Type EtS external temp sensor OFF disabled NoHt normally heat NoCl normally cool SENs sensor CH Over Setpnt 24 C select set value AI2 CO2 Maximum Range 2000 ppm CO2 Setpnt 800 ppm Go...

Страница 10: ...llows demand CO2 carbon dioxide Hr2 heating ramp 2 Hr1 heating ramp 1 Cr2 cooling ramp 2 Cr1 cooling ramp 1 TO2 Ramp OFF select set value MSV 27 TO2 Go to TO1 Close Percent Go to TO1 DIR REV OPt Optio...

Страница 11: ...mum Voltage 0 0 Vdc Go to tmp AO2 Maximum Voltage 10 0 Vdc Go to tmp Main Menu Sub Menu Configuration AO1 AO2 TO4 TO3 TO2 Output Config TO1 scroll menu items scroll menu items MSV 20 MSV 22 AV 70 AV 7...

Страница 12: ...0 F 0 5 5 C 1 9 F CR1 Dead Band 0 3 C 0 6 F 0 5 C 0 9 F CR2 Prop Band 2 0 C 4 0 F 0 5 5 C 1 9 F CR2 Dead Band 0 3 C 0 6 F 0 5 C 0 9 F Hr1 Prop Band 2 0 C 4 0 F 0 5 5 C 1 9 F Hr1 Dead Band 0 3 C 0 6 F...

Страница 13: ...in in progress Go to HrS Copy Config Result Succeed Go to HrS select set value Hours 12 0 23 or 1 12 am pm Minutes 00 00 59 Year 15 15 99 Set Time Display format 24 24 hour format 12 AM PM format Mont...

Страница 14: ...tS External temperature sensor When the thermostat is connected to the appropriate analog input the display shows the temperature read by the external temperature sensor Adjust the offset by comparing...

Страница 15: ...inheat airflowto Kfactor Minimum Heating Airflow 200 0to max heat airflow Go to bAL Airflow Balance CLOs close Min minimum flow mA maximum flow OPEn fully opened Close Motor 130 see note Minimum Airfl...

Страница 16: ...rough the following values Airflow Airflow Setpoint Actual Damper Pos Percent Air Supply Temp appears only in pressure independent mode appears only if AST is selected for the Analog Input Signal Type...

Страница 17: ...emp After 5 seconds without any action the thermostat returns to operation mode The air supply temperature appears only if analog input AI1 or AI2 are configured with the AST option Not available on t...

Страница 18: ...Type On Off On Off On Off On Off On Off On Off On Off TO3 Close Pos 40 40 40 40 40 40 40 TO3 Open Pos 0 0 0 0 0 0 0 TO4 Ramp HR2 HR2 HR2 HR1 OFF HR1 HR1 TO4 Signal Type Pulse On Off Pulse On Off On O...

Страница 19: ...Notes...

Страница 20: ...need to find the nearest Neptronic authorized distributor please consult www neptronic com 400 Lebeau blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 51...

Отзывы: