Networkable VAV Controller
Specification and Installation Instructions
www.neptronic.com
EVCB Standard
Page | 15
Menu 757 – Airflow Balance Mode
Pressure Independent: models EVCB14NIT0S, EVCB14NIT2S, and EVCB14NIT4S
Note: Refer to
EVCB-Airflow Balance Instructions
on Neptronic website for further information on airflow balancing function.
Pressure dependent model EVCB14NDT4S or other models if in pressure dependent mode
Reset to Factory Default Settings
This will erase all actual configurations and replace them with the factory default settings.
1. The Mode Selector jumper (JP1) of the thermostat must be set to the “RUN” position (Operation Mode). Refer to Wiring on
page 6.
2. During the power up sequence of the controller and thermostat (when the firmware versions are displayed), press and hold
both the
and
buttons.
3. The
“Enter Password”
screen appears. Enter
372
within 1 minute by using the arrow keys to increase or decrease the value and
the
[
/
]
and
buttons to toggle between the digits.
4. Use the arrow buttons to select YES and then press
[
/
]
.
Air Flow Scale
Select Airflow KFactor
1200
"SEtc"
Airflow Intgral time in Min
0 min
(0-60 min)
End
(exit menu)
mot
(motor)
bAL
(balancing)
SEtc
(settings)
VAV Config
COnf
(configuration)
= scroll menu items
Pressur Filter Time In Sec
2 sec
(1-10 sec)
1
10
100
Maximum Cooling Airflow
1000
(Min cool airflow to Kfactor)
Airflow Setting
COOl
HEAt
Minimum Cooling Airflow
200
(0 to max cool airflow)
Maximum Heating Airflow
1000
(Min heat airflow to Kfactor)
Minimum Heating Airflow
200
(0 to max heat airflow)
Go to "bAL"
Airflow Balance
CLOs
(close)
Min
(minimum flow)
mA
(maximum flow)
OPEn
(fully opened)
Close Motor
130
(see note)
Minimum Airflow
133
(same as Close Motor)
Maximum Airflow
135
(see note)
Open Motor
135
(same as Maximum Airflow)
Motor Overide
Auto
(automatic)
OPEn
(open)
CLOs
(close)
FLOl
(airflow low)
FLOh
(airflow high)
Exit menu and return
to normal operation
Range depends on air flow scale
from previous step:
(1) = 100 ‐ 9995
(10) = 10.0 ‐ 999.5
(100) = 1.0 ‐ 99.9
Adjusts the offset of the airflow
reading. Offset range depends on
selected air flow scale in Conf menu.
(1) =
+/‐500
(10) =
+/‐50.0
(100) =
+/‐5.00
Displays the airflow based on the
Kfactor. Range depends on air flow
scale in Conf menu:.
(1) = 100‐9995
(10) = 10.0 ‐ 999.5
(100) = 1.00 ‐ 99.95
AV.100
AV.106
MSV.41
AV.101
AV.103
AV.102
AV.105
AV.104
MSV.47
MSV.37
AV.114
AV.114
AV.112
AV.112
"HEAt"
Returns to
run mode
Flow value depends on the actual mode of the system :
Heating = heating airflow
Cooling = cooling airflow
Go to "mot"
Go to "mot"
Go to "mot"
Go to "mot"
When balancing , use only two of
the four modes available ; either:
Close Motor and Open Motor
or
Minimum Airflow and Maximum
Airflow (more precise)
*** To save any changes, press on TRL and on TDU ***
*** To the previous step without saving, press
on TRL and TDU ***
End
(exit menu)
mot
§
(motor)
VAV Config
= scroll menu items
Exit menu and return
to normal operation
Motor Overide
Auto
(automatic)
OPEn
(open)
CLOs
(close)
Returns to
run mode
§
=
mot
(Motor
position) is not
functional on motor
less models such as
EVCB14NDT2. Ignore
the option.
*** To save any changes, press on TRL and on TDU ***
*** To the previous step without saving, press on TRL and TDU ***