Actuator

 

Specification & Installation Instructions

 

 

BM-N-210803

 

 

       

 

 

Technical Data 

BM000N  BM000FN  BM000FFN  BM060N  BM060FN  BM060FFN  BM020N  BM020FN  BM020FFN 

Running time through 90º 

15 sec 

6 sec 

3 sec 

15 sec 

6 sec 

3 sec 

15 sec 

6 sec 

3 sec 

Power consumption 

10 VA 

10 VA 

10 VA 

18VA Peak, 

10VA 

18VA Peak, 

10VA 

18VA Peak, 

10VA 

10 VA 

10 VA 

10 VA 

Torque 

50 in.lb. [5,6 Nm] at rated 

voltage 

35 in.lb. 

[3,9 Nm] at 

rated voltage 

50 in.lb. [5,6 Nm] at rated 

voltage 

35 in.lb. 

[3,9 Nm] at 

rated voltage 

50 in.lb. [5,6 Nm] at rated 

voltage 

35 in.lb. 

[3,9 Nm] at 

rated voltage 

Fail safe - Enerdrive 

No 

Yes 

No 

Auxiliary switches 

No 

Yes (2) 

Ingress protection 

IP22 equivalent to Nema type 2, IP54 equivalent to Nema type 3R if water tight 

inlet bushings (not supplied NEP617) are installed 

IP22 equivalent to Nema type 2 

Feedback 

4 to 20 mA or 2 to 10 VDC adjustable (default setting: 4 to 20mA) 

Power supply 

22 to 26 VAC or 28 to 32 VDC 

Electrical connection 

18 AWG [0.8 mm

2

] minimum 

Inlet bushing 

2 inlet bushing of 13/16 in [20.6 mm] 

Control signal 

Analog, Digital or Pulse with modulation (PWM) programmable (default setting:  Analog control signal) 

Angle of rotation 

0 to 90 degrees, mechanically adjustable (default setting: 90º stroke) 

Direction of rotation 

Reversible, Clockwise (CW) or Counterclockwise (CCW) (default setting: CW direction) 

Ambient temperature 

-22ºF to +122ºF [-30º C to +50º C] 

Storage temperature 

-22ºF to +122ºF [-30º C to +50º C] 

Relative Humidity 

5 to 95 % non condensing. 

Weight 

3 lbs. [1.4 kg] 

Warning: Do not press the clutch when actuator is powered 

 

Dimensions

 

 

 
 

Dimension 

Inches  Metric (mm) 

1.50 

38.1 

3.64 

92.5 

6.60 

167.5 

model 000 & 060 

3.02 

76.8 

model 020 

3.81 

96.8 

 

Caution 

We  strongly  recommend  that  all  Neptronic

®

  products  be  wired  to  a  separate  transformer  and  that  transformer  shall  service  only  Neptronic

®

  products.  This  precaution  will 

prevent interference with, and/or possible damage to incompatible equipment. 
When multiple actuators are wired on a single transformer, polarity must be observed. Long wiring runs create voltage drop which may affect the actuator performance. 

 

1

 

Enerdrive System

 U.S.A. Patent #5,278,454 

 

Feature: 

 

Mounts easy on round  & square shaft (with option 

–8). 

 

External clutch for manual adjustments. 

 

Maintenance free. 

 

Position indicator. 

 

Control signal fully programmable. 

 

Auto stroke on power up 

 

Brushless DC driven motor. 

 

Fail safe by 

Enerdrive System

1

 

(on model 060). 

 

Auxiliary switches (on model 020) 

BM000N 
BM020N 
BM060N 

BM000FN 
BM020FN 
BM060FN 

BM000FFN 
BM020FFN 
BM060FFN 

 
 
 

Содержание BM000N

Страница 1: ... 90 degrees mechanically adjustable default setting 90º stroke Direction of rotation Reversible Clockwise CW or Counterclockwise CCW default setting CW direction Ambient temperature 22ºF to 122ºF 30º C to 50º C Storage temperature 22ºF to 122ºF 30º C to 50º C Relative Humidity 5 to 95 non condensing Weight 3 lbs 1 4 kg Warning Do not press the clutch when actuator is powered Dimensions Dimension I...

Страница 2: ...ntrol In this mode the actuator is sensitive to induced electrical voltages from external sources To prevent such interference if the signal on pins 4 and 3 on TB1 are from an external 24 Vac source install a resistor 2 2kohm 0 5W between pins 4 and 1 and another of 2 2kohms 0 5W between pins 3 and 1 of TB1 These resistors are included Input Signal and Feedback setup Input Signal Feedback Analog M...

Страница 3: ...g 1 Remove power and put all dip switches OFF default setting 2 Apply power and within 10 seconds press and release the reset button The LED should be blinking 3 Select the control signal with dip switches Digital or Analog Modes PWM Mode Move switch No1 ON and then OFF Digital On Off or 3 point floating 5 sec pulse default setting Move switch No2 ON and then OFF Analog Default 25 sec pulse Stroke...

Страница 4: ...EP 5 Press and release the reset button to memorize the new minimum voltage The LED blinks 6 Apply new maximum voltage It can be any value between 3 to 10 Vdc this value should be greater than the new minimum value 7 Press and release the reset button to memorize the new maximum voltage The LED blinks The Zero and span calibration process is complete Note To reset zero and span to 2 to 10 Vdc defa...

Отзывы: