Nemtek FG7C Скачать руководство пользователя страница 1

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

INSTALLERS MANUAL 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Revision 1.3 
11 December 2018 

GROUP OF COMPANIES

 

FG7C CONTROLLER

 for DRUID 25/28 NETWORKS

 

Содержание FG7C

Страница 1: ...INSTALLERS MANUAL Revision 1 3 11 December 2018 GROUP OF COMPANIES FG7C CONTROLLER for DRUID 25 28 NETWORKS ...

Страница 2: ...3 OPENING THE FG7C 3 4 HARDWARE 5 INSTALLING THE FG7C 6 7 THE DISPLAY BOARD 8 9 COMMUNICATION BOARDS 10 12 PROGRAMMING THE FG7C 12 16 MAPPING 17 20 FIRMWARE UPGRADE 20 THE FG7 WEB INTERFACE 21 22 THIRD PARTY INTEGRATION 22 DOCUMENT REVISION HISTORY 23 ...

Страница 3: ...printed circuit boards and software to provide the required functionality Warning Test the functionality of the system after configuration and before commissioning OPENING THE FG7C Panel mount type On one of the long sides of the FG7C are two slots Insert a 6 5mm screw driver into one of the slots and turn the screw driver until the lid with the display pops up on that side Now repeat this with th...

Страница 4: ...7C are two openings with retaining clips Insert a 6 5mm screw driver into the bottom part of one of the openings and push the retainer clip back until the lid with the display pops up on that side Now repeat this with the other opening You should now be able to carefully remove the lid ...

Страница 5: ...n to the control unit Under the dark blue control unit is the battery which is required for the clock during power failures You will find jumpers connectors and led s on the board for selecting connecting and indicating The control unit host the software and has all communication ports on board The touchscreen is the standard display used on the stand alone units without Druid FenceProbe or third ...

Страница 6: ...at the bottom of the base or two cut outs on the side of the base INSTALLING THE PANEL MOUNT FG7C The panel mount FG7C is designed to be mounted flush in wooden walls or dry walling A cut out has to be made in these walls of 195mm x 130 mm Before installing the base of the FG7C into the wall make sure that all cut outs required for the wiring are done on the base that the wiring to the FG7C is ful...

Страница 7: ...nect the wiring between the lid and the base so that it can be fully removed Turn the top wing clamp screw anti clockwise until the wing clamp comes back into its base cavity do not fully unscrew the wing clamp screw since it will detach and can fall inside the wall Repeat for the bottom wing clamp and remove the base from the wall opening Wing clamp and Wing clamp screw ...

Страница 8: ...r supply Watch Dog timer 2 JP3 1 Positioned to the left for auto reset with transmission failure of the control unit Positioned to the right for no auto reset of the control unit PUSH BUTTONS ON DISPLAY BOARD There are two push buttons on the green board The one is marked SW2 5V_RESET and the other SW1 B3_RESET The 5V_RESET button is used to manually power the control unit on and off this is usual...

Страница 9: ...vation of the HDMI port can be done via the web interface see the FG7 web interface A USB mouse connected to the USB port of the FG7 should be used for operating the system when using an HDMI display or the USB port can be used for the touch screen part of a touch screen monitor The resolution of the display if possible should be set to 1920 x 1080 The picture of the site image should be 1000 x 65...

Страница 10: ...e control unit LED2 If flashing indicates transmission of data from the control unit to the Nemlink LED3 If flashing indicates receiving of data from the taut wire to the control unit LED4 If flashing indicates transmission of data from the control unit to the taut wire LED5 5V supply indicator CONNECTORS Con 1 Ribbon cable connection to Con1 of display board Con 2 Ribbon cable connection to Con2 ...

Страница 11: ...LED S ON COMMUNICATION BOARD LED1 If flashing indicates transmission of data from RS485 or TTL lines to the control unit LED2 If flashing indicates receiving of data from the control unit to the RS 485 or TTL lines LED3 If flashing indicates receiving of data from the taut wire to the control unit LED4 If flashing indicates transmission of data from the control unit to the taut wire CONNECTORS Con...

Страница 12: ...and select Installer enter the appropriate PIN number and press Enter Check that Installer stays on the screen and has not revert back to select 2 Press the System tab on the top of the screen and use the and markers next to the number of energizers to select the correct number of energizers in the network Press Save No of Energizers 3 If jumper JP1 and JP3 on the display board are set to auto res...

Страница 13: ... 3 If jumper 2 of the 16 8 4 2 1 jumpers is removed then the IO card will have a net address of 35 etc Note 2 The FG7 scans through the network address at a rate of twenty addresses per second The fewer the addresses utilised on the system the faster the system response Because an energizer only updates its own parameters once a second there is little point in updating the FG7 display faster than ...

Страница 14: ...then show a tick indicating that the setting is selected The following settings can be selected Audible alarm Alarm Sensor mode Show sync loss Nemlink Proxy AbsoluteIO Failsafe Off LV AUDIBLE ALARM The buzzer inside the FG7 is enabled when the Audible Alarm tick box is ticked The buzzer will sound when there is an alarm or service condition If unticked the buzzer is disabled ALARM SENSOR MODE If t...

Страница 15: ... IO card The last command from the User or from the IO card dictates the system state When AbsoluteIO is ticked the control of the mapped energizer s is taken away from the User of the FG7 and is now given to the input of the IO card The only way to now give commands to the energizer s from the FG7 screen is to first untick AbsoluteIO on the system tab FAILSAFE When third party software or Nemtek ...

Страница 16: ...t and touch the screen at the start point and end point of the gate Press View to confirm your entry 7 You can randomly do all energizers zones and gates using steps 3 to 6 above 8 When you are happy with the zone and gate lines press Save 9 The system will automatically load this graphic layout on power up You may after entering Installer mode edit any sector independently and then re save 10 The...

Страница 17: ...l activate relay 3 14 Fence 1 or Fence 2 or Gate Alarm activates relay3 2 4 8 5 The combination of any alarm condition note 1 that will activate relay 4 32 Only Tamper Alarm activates relay 4 6 The combination of any alarm condition note 1 that will activate relay 5 4 Only Fence 2 Alarm activates relay 5 7 The combination of any alarm condition note 1 that will activate relay 6 2048 Mains present ...

Страница 18: ...he numbers are associated with each alarm state Energizer State Number COMMS FAIL 1 FENCE 1 ALARM 2 FENCE 2 ALARM 4 GATE ALARM 8 SERVICE ALARM 16 TAMPER ALARM 32 SYNC FAILURE 64 ZONE 1 ON 128 ZONE 1 HIGH VOLTAGE 256 ZONE 2 ON 512 ZONE 2 HIGH VOLTAGE 1024 MAINS PRESENT 2048 PANIC ALARM 4096 Multiple energizers addresses can communicate with single IO card addresses i e a fence alarm on Zone 1 of an...

Страница 19: ...er in HV LV mode 16 32 128 4 Inputs that are valid on this IO card note 4 51 Inputs 1 2 5 and 6 are used 1 2 16 32 5 The Energizer Address that IO card 34 will communicate with unless global 2 Energizer 2 6 The above sequence repeated etc etc Notes 4 Table 4 has a number associated with each IO card input 5 Select the appropriate numbers and add them for the inputs to be recognized If the number i...

Страница 20: ... GLOBAL HIGH LOW VOLTAGE 32 ADD SEE NOTE 5 128 Input 7 Can only be utilized through application software Input 8 Can only be utilized through application software LOADING A MAPPING FILE The mapping files can be loaded on to the FG7 through the web interface see the FG7 web interface Please note that if failsafe is ticked the mapping files are disabled FIRMWARE UPGRADE A firmware upgrade can be don...

Страница 21: ... computer Viewing of mapping files You can view the mapping files which are present in the FG7 by entering on the address bar in the browser the IP address followed by itoemap txt or etoimapplus txt depending on which file is required As an example with the IP address of the control unit being 10 0 0 20 one would enter in the browser 10 0 0 20 itoemap txt or alternatively 10 0 0 20 etoimapplus txt...

Страница 22: ...owser 10 0 0 20 nemupload cgi 2 Enter the installer password The installer configuration screen will appear 3 Click on HDMI or LCD screen as required The display will change to HDMI or LCD touchscreen ENERG APP TW APP TWNODE APP It is possible to toggle through the web interface the application in the FG7 The FG7 should have been set for the use with energizers ENERG APP but by clicking on TW APP ...

Страница 23: ...mmunication to the FG7 fails then control would be given to the mapping of the inputs of the IO card s and not to the FG7 User see AbsoluteIO Please also read the section Failsafe of this manual if third party integration or Nemtek FenceProbe is used DOCUMENT REVISION HISTORY Revision 1 0 26 April 2018 Revision 1 1 Added Failsafe 24 May 2018 Revision 1 2 Removed calibration 6 June 2018 Revision 1 ...