Commissioning Cycle
•
Function test
•
Self-test
A tri-colour LED indicator displays the light fitting status. The indication colours are shown in
table 1.
a. Commissioning Cycle
•
Starts automatically after 24 hours of uninterrupted charging. If there is a mains failure in this
time the count resets for another 24 hours.
•
3 charge/discharge cycles to optimise battery’s full capacity.
•
Battery is charged for 24 hours before each discharge cycle.
•
No need for manual commissioning
b. Function Test
•
Carried out every 7 days.
•
Checks the function of the battery, lamp and power supply.
•
Lasts for few minutes only.
RL Intelligent Emergency Operation Guide
Operation
The light fitting will carry out the following function
automatically
after installation:
7.
All RL luminaires have terminal blocks suitable for looping 4mm2 cable, only one
cable should be connected to each terminal block connection
8.
The battery fuse is located in the compartment that contains the battery, the fuse is
disconnected after final manufacturing testing. When installing the linear the battery fuse will
need to be reconnected and the unit charged for 24 hours and then discharged (repeated 3
times) to bring the battery up to peak capacity. (Unless an ‘EMX’ intelligent emergency variant
– see notes below)
9.
If a 4 core cable is used on emergency luminaires – L1, L2, N and E the link cable at the front of
the terminal block between L1 and L2 should be removed
10.
During emergency operation the light output and duration will be determined by the
variant purchased
11.
Once wiring is complete replace terminal enclosure covers. Ensure gasket is located neatly in
channel and no wires are trapped between cover and body. Tighten screws to 3Nm
12.
If carrying out Insulation Resistance tests the normal method of insulation testing is to
connect Live and Neutral together and test between this point and Earth to prevent the
risk of damage to the electronic control gear.
5
-
1
2
www.nemalux.com | [email protected] | Tel 403•242•7475 | Fax 403•243•6190
SUBJECT TO CHANGE WITHOUT NOTICE
MADE IN
UK