background image

Compliance with the Essential Health and Safety Requirements has been assessed 

by reference to the following harmonised/designated standards - 

EN 60079-7 : 2015 + A1 : 2018   

EN 60079-31 : 2014        

EN 60079-0 : 2018 
EN 60079-18 : 2015 + A1 : 2017 
EN 60079-1:2014 

1

1

-

1

2

www.nemalux.com  |   [email protected]  |   Tel 403•242•7475  |   Fax 403•243•6190 

SUBJECT TO CHANGE WITHOUT NOTICE

MADE IN 

UK

And also 2014/35/EU - Low Voltage Directive, 2014/30/EU - EMC Directive 

Signed

  

Name

Barry 

Thompson 

Position 

Director

Dated

Serial number

Содержание RB Series

Страница 1: ...n 5 Declaration of Conformity Important information The RB series of explosion protected bulkheads are specialist devices certified for use in specific operating environments The units must be install...

Страница 2: ...TEX IEC Ex UKEX cable glands and stopper plugs these must be parallel thread have a minimum of 5 full thread engagement and be of a medium fine tolerance to ISO965 1 and ISO965 3 The cable entry devic...

Страница 3: ...sed the fixing points must be suitable for the conditions of use Nemalux recommends using M6 Marine Grade A4 Stainless Steel fixings not supplied 121 104 302 288 204 220 182 240 220 168 70 20 17 3 3 1...

Страница 4: ...cable into the terminal block Provision has been made for this and identified as the E Earth L1 Live switched L2 Live permanent and N Neutral terminals There are two pairs of contacts for each of thes...

Страница 5: ...emergency variants is disconnected after final manufacturing testing When installing the bulkhead the battery fuse will need to be reconnected and the unit charged for 24 hours and then discharged rep...

Страница 6: ...t the same time LED indication c Self test Carried out at a random time every 3 month Checks the battery s capacity and lamp s condition Performs self recovery for the battery if not at peak capacity...

Страница 7: ...mbly clear Re fitting a light engine is a reversal of the above procedure 5 The unit has one independent power supply in the event that the power supply needs to be replaced the cables to the LED and...

Страница 8: ...ncy 50 60Hz Inrush Current Ipeak 50 20A t 300 s Total Harmonic Distortion 230Vac full load 10 IP Rating IP66 67 Weight std 5Kg 6Kg Dimensions See previous pages for line diagrams ATEX and IECEx and UK...

Страница 9: ...30V MCB Type Rating RB 2 STD RB 2 EM B 10A 11 10 B 16A 17 15 B 20A 25 22 B 25A 35 32 C 10A 24 20 C 16A 34 28 C 20A 49 44 C 25A 58 55 9 12 www nemalux com sales nemalux com Tel 403 242 7475 Fax 403 243...

Страница 10: ...sole responsibility that the product s listed below conform with the relevant provisions of the ATEX directive 2014 34 EU of 20th April 2016 and the UK directive SI 2016 No 1107 as amended Manufacture...

Страница 11: ...014 11 12 www nemalux com sales nemalux com Tel 403 242 7475 Fax 403 243 6190 SUBJECT TO CHANGE WITHOUT NOTICE MADE IN UK And also 2014 35 EU Low Voltage Directive 2014 30 EU EMC Directive Signed Name...

Страница 12: ...2589 P 1 403 242 7475 F F 1 403 243 6190 E info nemalux com W www nemalux com Industrial LED Lighting designed to solve harsh and hazardous lighting challenges 12 12 www nemalux com sales nemalux com...

Отзывы: