3. Maintenance

1. It is essential that all RB Bulkhead units are maintained in accordance with the 

requirements of the EN60079-17 standard: (Electrical apparatus for explosive gas 

atmospheres – other than mines).

2.

IMPORTANT

.  No modifications are permitted to the unit, all spare parts must 

be purchased  from  the  manufacturer,  unauthorized  modifications  or  spare 

parts  will invalidate certification and make the equipment dangerous.

3. Isolate  the  RB  Bulkhead  from  the  mains  supply  and  allow  to  cool  before 

carrying out any maintenance work.

For Emergency variants, battery must be isolated/ connected when a 

hazardous environment is NOT present prior to carrying out any maintenance 

work.

4. In the unlikely event of a number of LED’s failing, the light engine assembly must 

be replaced.  This  is  achieved  by  loosening  front  cover  bolts,  disconnecting  the 

white  LED cables to power supply, remove four M6 bolts from rear of light engine 

and pull the light engine assembly clear. Re fitting a light engine is a reversal of 

the above procedure.

5. The  unit  has  one  independent  power  supply,  in  the  event  that  the  power 

supply  needs to be replaced the cables to the LED and mains terminal block will 

need to be  disconnected,  the  four  M6  bolts  released,  then  the  power  supply 

can  then  be removed. Fitting a new power supply is a reversal of the above 

procedure. 

6. Disposal of packaging, RB unit and old LED assemblies should be carried out in 

accordance with national regulations.

PROTECTION/CERTIFICATION

CML13ATEX3007, IEC Ex CML14.0001 & CML21UKEX3099 II 2 GD Ex eb mb 

IIC T4 Gb

Ta -52°C to +55°C (standard variants)

II 2 GD Ex eb mb IIC T4 Gb

Ta -20°C to +46°C (emergency variants)

Ex tb IIIC T98°C Db

IP66 & IP67 Ta = -52°C to +55°C

110V-254V AC or 18-48V AC/18-69V DC

CML 17ATEX4231, IEC Ex CML17.0135 & CML21UKEX4106 II 3 GD Ex ec mc 

IIC T4 Gc

Ta -50°C to +55°C (standard variants)

II 3 GD Ex ec mc IIC T4 Gc

Ta -20°C to +55°C (emergency variants)

Ex tc IIIC T98°C Dc

IP66 & IP67 Ta = -50°C to +55°C
110V-254V AC or 18-48V AC/18-69V DC

7

-

1

2

www.nemalux.com  |   [email protected]  |   Tel 403•242•7475  |   Fax 403•243•6190 

SUBJECT TO CHANGE WITHOUT NOTICE

MADE IN 

UK

Содержание RB Series

Страница 1: ...n 5 Declaration of Conformity Important information The RB series of explosion protected bulkheads are specialist devices certified for use in specific operating environments The units must be install...

Страница 2: ...TEX IEC Ex UKEX cable glands and stopper plugs these must be parallel thread have a minimum of 5 full thread engagement and be of a medium fine tolerance to ISO965 1 and ISO965 3 The cable entry devic...

Страница 3: ...sed the fixing points must be suitable for the conditions of use Nemalux recommends using M6 Marine Grade A4 Stainless Steel fixings not supplied 121 104 302 288 204 220 182 240 220 168 70 20 17 3 3 1...

Страница 4: ...cable into the terminal block Provision has been made for this and identified as the E Earth L1 Live switched L2 Live permanent and N Neutral terminals There are two pairs of contacts for each of thes...

Страница 5: ...emergency variants is disconnected after final manufacturing testing When installing the bulkhead the battery fuse will need to be reconnected and the unit charged for 24 hours and then discharged rep...

Страница 6: ...t the same time LED indication c Self test Carried out at a random time every 3 month Checks the battery s capacity and lamp s condition Performs self recovery for the battery if not at peak capacity...

Страница 7: ...mbly clear Re fitting a light engine is a reversal of the above procedure 5 The unit has one independent power supply in the event that the power supply needs to be replaced the cables to the LED and...

Страница 8: ...ncy 50 60Hz Inrush Current Ipeak 50 20A t 300 s Total Harmonic Distortion 230Vac full load 10 IP Rating IP66 67 Weight std 5Kg 6Kg Dimensions See previous pages for line diagrams ATEX and IECEx and UK...

Страница 9: ...30V MCB Type Rating RB 2 STD RB 2 EM B 10A 11 10 B 16A 17 15 B 20A 25 22 B 25A 35 32 C 10A 24 20 C 16A 34 28 C 20A 49 44 C 25A 58 55 9 12 www nemalux com sales nemalux com Tel 403 242 7475 Fax 403 243...

Страница 10: ...sole responsibility that the product s listed below conform with the relevant provisions of the ATEX directive 2014 34 EU of 20th April 2016 and the UK directive SI 2016 No 1107 as amended Manufacture...

Страница 11: ...014 11 12 www nemalux com sales nemalux com Tel 403 242 7475 Fax 403 243 6190 SUBJECT TO CHANGE WITHOUT NOTICE MADE IN UK And also 2014 35 EU Low Voltage Directive 2014 30 EU EMC Directive Signed Name...

Страница 12: ...2589 P 1 403 242 7475 F F 1 403 243 6190 E info nemalux com W www nemalux com Industrial LED Lighting designed to solve harsh and hazardous lighting challenges 12 12 www nemalux com sales nemalux com...

Отзывы: