PowerRouter - configuring general system settings
Scenario
The scenario defines the intended use of the system. Only for
specific systems it is possible to change the scenario.
>
In the “Feed-in” scenario the system will feed all its energy
back to the grid.
>
In the “Backup” scenario the system will charge the batteries.
The surplus will be sent to the grid.
>
In the “Self-use” scenario the system will first send the
generated energy to the load and then to the battery. Any
surplus will be sent to the grid.
Alarm 1 / 2
Generates an alarm notification. This notification can be assigned
to a user-selectable relay. These alarms are based on selected
system conditions. To assign the alarm to a user-selectable relay,
please configure relay 1 or 2 via a separate configuration option.
The following system conditions are available:
None
Alarm is not used (default).
Grid voltage
Set trip level to activate the alarm based on the actual grid
voltage.
>
Activate trip limit: when the grid voltage is outside this range,
the alarm will be activated.
>
Deactivate trip limit: when the grid voltage is inside this range,
the alarm will be deactivated.
>
Activation delay: delay time in seconds before the alarm will be
activated (between 0 and 100 seconds).
>
Deactivation delay: delay time in seconds before the alarm will
be deactivated (between 0 and 100 seconds).
>
Maximum active time: maximum time in minutes that the alarm
can be activated (between 0 – 720 minutes).
>
Minimum active time: minimum time in minutes that the alarm
can be activated (between 0 – 720 minutes).
Figure 11: Alarm 1 / 2
Figure 12: Grid voltage