background image

13

Self-use

With this setting you can set specify battery settings for self-use 
optimization.

>  

Max. depth of discharge. to the default setting is 50%; this 
value is preferable for daily use. The battery will not be 
discharged beyond 50%. The number of charging cycles that 
lead batteries can undergo before reaching the end of their 
service life decreases with the depth of discharge. 50% is 
recommended as a default value, depending of the exact type 
of battery.

>  

Support backup: if the local out is not used, you can disable 
this function. In that case the system will go to standby if the 
grid is down and the batteries are fully charged.

>

   Limit battery to maximum discharge power: With the battery 

power limiter enabled, the system will not use the battery to 
feed peak loads. This provides extra protection for the battery. 
 
Using a lower battery power for self-use compensation 
increases the lifetime of the batteries, because the batteries 
are not discharged as quickly. It also improves the self-use 
consumption percentage, since at lower discharge powers 
more energy can be extracted from the battery.

  

If the maximum discharge power is set too low, not all the 
available battery energy is used. In an ideal situation the 
maximum allowed depth of discharge should be reached at the 
end of the night. 
 
When batteries are discharged at high power levels, 

voltage 

drops can occur. These can result in under-voltage errors and 
potentially damage the battery. Such voltage drops can be 
prevented by limiting the discharge power.

Winter mode
With the winter mode enabled, batteries will not be used during 
wintertime. This period can be defined by setting a start date 
and an end date. During the winter the solar power available is 
so limited that your batteries will most likely never become fully 
charged or are not used at all. Accordingly, batteries will be run 
at lower SOC levels or will remain discharged for weeks between 
the maintenance charging cycles. Not using the batteries during 
the winter will protect them against damage and will increase 
their service life. The maintenance charge mode remains active in 
order to keep the batteries fully charged.

Figure 28: Self-use

Figure 29: Winter mode

Содержание PowerRouter

Страница 1: ...u may download the installation tool from the website www PowerRouter com you will need your login details for this website The software installation tool can be used to configure PowerRouters with fi...

Страница 2: ...gure a new system using the installation wizard The wizard automatically detects whether you are connected to a new PowerRouter system The wizard guides you through the minimal required settings to ge...

Страница 3: ...the battery itself or on the battery specification sheet Maximum depth of discharge DOD backup Enter the maximum depth of discharge allowed during a grid failure This defines the percentage of the bat...

Страница 4: ...output power of the grid module 5 latest grid disconnection events Solar Module status shows the status of the system s internal solar module Voltage and current of each solar string at this moment Lo...

Страница 5: ...guring the system display Backlight When auto mode is selected the display will switch off after it has not been used for two minutes When always on is selected the display will never switch off Displ...

Страница 6: ...ser selectable relay please configure relay 1 or 2 via a separate configuration option The following system conditions are available None Alarm is not used default Grid voltage Set trip level to activ...

Страница 7: ...e deactivated Activation delay delay time in seconds before the alarm will be activated between 0 and 100 seconds Deactivation delay delay time in seconds before the alarm will be deactivated between...

Страница 8: ...e how much power is connected as additional load to be switched on in watts Activate on load support activates if the percentage of the defined power of the load is available as an energy surplus Deac...

Страница 9: ...relay Set relay signal type Normal default user selectable relay is activated when switched on Pulse activates the user selectable relay for a defined duration of between 1 and 10 seconds when switche...

Страница 10: ...ed the system complies with the EEG2012 regulations in Germany by limiting its grid output power to 70 of nominal power by default The limitation can be optimized by entering the installed solar power...

Страница 11: ...tery specification sheet capacity value of the battery discharged in 10 hours Maximum depth of discharge DOD Enter the maximum depth of discharge allowed during a grid failure This defines the percent...

Страница 12: ...ctly Incorrect settings can damage the batteries At fixed float the batteries are charged with a constant voltage This can be used in a backup application where batteries may be charged over a long pe...

Страница 13: ...consumption percentage since at lower discharge powers more energy can be extracted from the battery If the maximum discharge power is set too low not all the available battery energy is used In an id...

Страница 14: ...take up to 15 minutes depending on which modules will be updated During this period the system will not be operational The installation tool already includes the latest firmware versions so no intern...

Страница 15: ...loc Solar power www hoppecke com Battery type Number of batteries Battery pack size C10 Ah Maximum charge current Bulk voltage Float voltage 6V 4 OPzV 250 4x 205 Ah 41 A 28 8 V 27 0 V 6V 5 OPzV 300 4x...

Отзывы: