background image

4

Dashboard 

When all the basic settings have been made, press “Install”. The configuration will be 

written to the PowerRouter and the system will reset to activate the configuration.

The main panel of the installation tool is a dashboard that 

provides you information about the current status of the 

PowerRouter. Advanced settings can be made via the drop-down 

menu that opens when you hover over the word “Advanced” in the 

upper-right corner.

Hover over the icons and a mouse-over status panel will appear 
with additional information as explained below:

Grid

>  

Module status: shows the status of the AC module in the 
system. Only intended for diagnostics during service.

>  

Grid voltage: shows the current grid voltage.

>  

Frequency: shows the current grid frequency.

>  

Grid Power: shows the output power of the grid module.

>  

5 latest grid disconnection events

Solar

>  

Module status: shows the status of the system’s internal solar 
module.

>  

Voltage and current of each solar string at this moment.

Local out

>  

Module status: shows the status of the system’s AC module.

>  

Voltage island mode: shows the current local out voltage.

>  

Frequency: shows the local out frequency.

>  

Local power: shows the actual load on local out.

Battery

>  

Module status: shows the status of the system’s internal 
battery module.

>  

Battery type: shows battery type.

>  

Autonomy time: shows autonomy time at the current rate of 
power consumption.

>  

State of charge: shows the current battery charge level, in 
percent.

>  

Voltage: shows battery voltage (charging or discharging).

>  

Current: shows battery current (charging or discharging).

>  

Temperature: shows reading from battery temperature sensor 
(should be mounted at positive battery clamp).

Internet

>  

MAC address: shows the system’s MAC address.

2

Weiter

Zurück

Figure 8: Dashboard

Advanced

Содержание PowerRouter

Страница 1: ...u may download the installation tool from the website www PowerRouter com you will need your login details for this website The software installation tool can be used to configure PowerRouters with fi...

Страница 2: ...gure a new system using the installation wizard The wizard automatically detects whether you are connected to a new PowerRouter system The wizard guides you through the minimal required settings to ge...

Страница 3: ...the battery itself or on the battery specification sheet Maximum depth of discharge DOD backup Enter the maximum depth of discharge allowed during a grid failure This defines the percentage of the bat...

Страница 4: ...output power of the grid module 5 latest grid disconnection events Solar Module status shows the status of the system s internal solar module Voltage and current of each solar string at this moment Lo...

Страница 5: ...guring the system display Backlight When auto mode is selected the display will switch off after it has not been used for two minutes When always on is selected the display will never switch off Displ...

Страница 6: ...ser selectable relay please configure relay 1 or 2 via a separate configuration option The following system conditions are available None Alarm is not used default Grid voltage Set trip level to activ...

Страница 7: ...e deactivated Activation delay delay time in seconds before the alarm will be activated between 0 and 100 seconds Deactivation delay delay time in seconds before the alarm will be deactivated between...

Страница 8: ...e how much power is connected as additional load to be switched on in watts Activate on load support activates if the percentage of the defined power of the load is available as an energy surplus Deac...

Страница 9: ...relay Set relay signal type Normal default user selectable relay is activated when switched on Pulse activates the user selectable relay for a defined duration of between 1 and 10 seconds when switche...

Страница 10: ...ed the system complies with the EEG2012 regulations in Germany by limiting its grid output power to 70 of nominal power by default The limitation can be optimized by entering the installed solar power...

Страница 11: ...tery specification sheet capacity value of the battery discharged in 10 hours Maximum depth of discharge DOD Enter the maximum depth of discharge allowed during a grid failure This defines the percent...

Страница 12: ...ctly Incorrect settings can damage the batteries At fixed float the batteries are charged with a constant voltage This can be used in a backup application where batteries may be charged over a long pe...

Страница 13: ...consumption percentage since at lower discharge powers more energy can be extracted from the battery If the maximum discharge power is set too low not all the available battery energy is used In an id...

Страница 14: ...take up to 15 minutes depending on which modules will be updated During this period the system will not be operational The installation tool already includes the latest firmware versions so no intern...

Страница 15: ...loc Solar power www hoppecke com Battery type Number of batteries Battery pack size C10 Ah Maximum charge current Bulk voltage Float voltage 6V 4 OPzV 250 4x 205 Ah 41 A 28 8 V 27 0 V 6V 5 OPzV 300 4x...

Отзывы: