N550 Bakers Oven | Installation Manual
Chimney Requirements
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER
APPLIANCE. DO NOT CONNECT TO ANY AIR DISTRIBUTION DUCT OR SYSTEM.
This stove must be connected to a
6”
(150mm) factory built UL 103 HT chimney (ULC S629, in
Canada) or a code- approved masonry chimney with a flue liner.
An effective vapor barrier at the location where the chimney or component penetrates to the
exterior
of the structure must be maintained as per the installer’s complying
method.
Factory Built Chimney
When a metal prefabricated chimney is used, the manufacturer’s installation instructions must
be
followed. You must also purchase (from the same manufacturer) and install the ceiling support
package or wall pass-through and
“T”
section package, firestops (where needed), insulation shield,
roof flashing, chimney cap, etc. Maintain proper clearance to the structure as recommended by
the manufacturer. The chimney must be the required height above the roof or other obstructions
for safety and proper draft operation. See page 11 for chimney termination requirements.
Figure 6. Factory built chimney requirements