2. Installation and Connection
Express5800/T120d User’s Guide
131
Chapter 2 Preparations
When you have selected a server site, hold the server by its bottom with at least two persons and carry it to
the site, then place it slowly and gently.
Important
•
Do not hold the server by its front bezel to lift the server. The front bezel
may be disengaged and damage the server.
•
Open the stabilizers and secure the server to the site.
•
Do not hold the handle on the redundant power module when carrying the
server.
Cables for the mouse or
other devices are within
easy reach.
At least 150 mm
clearance in front
of/behind the server
100-VAC bipolar
grounded outlet
A Dust-free, clean, and
organized room
The environment that satisfies the following conditions
<Operating>
<Storage>
Ambient temperature:
10
°
C to 40
°
C
5
°
C to 40
°
C
Humidity:
20% to 80%
10% to 80%
Temperature gradient:
±10
°
C/hour
±15
°
C/hour
Air pressure:
749 to 1040 hpa 749 to 1040 hpa
It is recommended to
install UPS to prevent
momentary voltage
drop due to power
failure or lightning
Place having a space enough to fully open the front
door (The front door extrudes about 20 mm from the
right side of the server when fully opened.)
Install the server on the
floor or rigid, flat desk.
Wall outlet that
can connect with
the power cord.
To connect with power outlet
of 200 VAC, use the
separately priced power cord
(K410-162 (03)).
* It is recommended that the server should
be used in a room where temperature is in
the range between 15 to 25ºC.
Open stabilizers to secure
the server.