Electrical Circuit and Wiring Information
B-1
Appendix B
Electrical Circuit and Wiring Information
B-
For electrical circuit and wiring information that you need to provide to the contractor
and/or facilities personnel responsible for wiring the power at the system installation
site, see:
•
“Fault Protection Requirements” on page B-1
•
“Grounding Considerations” on page B-1
•
“Circuit Wiring Diagrams” on page B-3
•
“Electrical Power Connectors” on page B-9
Fault Protection Requirements
Each enclosure in Express5800/320Ma 3.2 GHz, 3.6 GHz, or Dual-Core systems
contains internal fault/overload current protection. However, the system relies on the
power distribution system at your site for protection against potential faults in the power
cords and the wiring in the system base.
•
If you are using a pair of PDUs in the cabinet, use 30A or less circuit breakers in
each power distribution branch that feeds the PDUs.
•
To connect a single system to power, use 20A or less circuit breakers in each power
distribution branch that feeds the systems.
Grounding Considerations
The system obtains an earth reference ground through the power cords attached to the
system. Similarly, each peripheral device connected to the system obtains ground
through its power cord. For each peripheral device, you must ensure that a
high-integrity safety-ground conductor is installed as part of the wiring system (in
accordance with U.S. national electric code NFPA 70 or the equivalent). The
international safety standard (EN60950) for electronic data processing (EDP)
equipment also requires a ground conductor, but calls it a protective earth (PE) ground.
Depending upon local conditions, ground potentials may differ between the system
base and any peripheral devices connected to the system base. All grounds in the
system must return to the same reference point in the power distribution system, as
close as possible to zero (0) volt potential relative to earth reference ground. Earth
Содержание Express5800/320Ma
Страница 1: ...NEC Solutions America Inc NR573 Express5800 320Ma Site Planning Guide...
Страница 10: ...Preface x Express5800 320Ma Site Planning Guide...
Страница 18: ...System Documentation 1 8 Express5800 320Ma Site Planning Guide...
Страница 40: ...Connecting a System Directly to a UPS 5 6 Express5800 320Ma Site Planning Guide...
Страница 50: ...Sample PDU Usage Calculation 7 6 Express5800 320Ma Site Planning Guide...
Страница 52: ...System Specifications A 2 Express5800 320Ma Site Planning Guide Figure A 1 Pedestal System Front View asys006a...
Страница 77: ...Standards Compliance Standards Compliance C 3 VCCI Note BSMI Note...
Страница 78: ...Standards Compliance C 4 Express5800 320Ma Site Planning Guide...