background image

2

 

 

Gas Piping 

C

onnections 

 

 

Water Piping 

C

onnections 

 

 

C

ondensate Drain 

C

onnection 

A condensate drain pipe must be connected to the 1/2” condensate outlet fitting at 
the bottom of the unit and water must be poured into the exhaust connection to fill 
the condensate trap. 

 

The end of the 1/2   (NPT) plastic piping should drain into a laundry tub or into a floor 

drain. 

 

 

Do not submerge the end of the 
pipe in water. 

 
 
 
 

N

ote 

Syphon 

Condensate Outlet 

Water 

Floor drain 

Example: 

Gas meter 

425 CFH 

 

Boiler 

195 CFH 

+ Furnace 

58.8 CFH 

+ Domestic 

gas 

stove 

63.7CFH 

* 1 CFH=1,020 Btuh 

 

1/2" rigid pipe can be used; refer to the sizing tables in the Installation & 
Operation Manual for limitations. Avoid using 1/2" corrugated connectors 
or tubing as noise may occur. 

B

uilt-in Water Fill 

C

onnection 

Navien NCB boiler is equipped with 
an auto-feeding water connection 
and motorized feeding valve. 
Therefore, installation of additional 
system water fill connection is not 
necessary in most cases. 

N

ote 

Backflow 
Preventer 

Make-up 
Water 

External Water Fill 

C

onnection 

Air Separator

Circulator

Expansion Tank

To System

Make-up 

Water

From 
System

Warning 

Water Piping 

C

onnections 

Space Heating System 

DHW System 

Install the included 3/4 in, maximum 30 
psi pressure relief valve on the space 
heating supply. 
   
An ASME approved HV pressure relief 
valve for space heating system is 
supplied with the boiler. 

The DHW pressure relief valve is 
not supplied, but is required.   
 

Install an approved 3/4 in, 
maximum 150 psi pressure relief 
valve on the hot water outlet. 

Pressure Relief Valve

Pressure 
Relief 
Valve 

Cold Water 

Supply 

DHW 
Supply 

Space 
Heating 
Supply

Space 
Heating 
Return 

DHW 
Supply 

Cold 

Water 

Inlet 

 

Built-in  

Water Feeder 

Connection 

Flow Restrictor 

(

for DHW system

)

Flow Rate 

(

GPM

)

 and Water Pressure 

(

psi

)

 

Orange 
Yellow 
Blue 

The boiler has a built-in flow restrictor at 
the cold water inlet adapter to limit the 
overall DHW flow. Three additional flow 
restrictors are provided

ent flow 

rates. 

Refer to the following graph and install 
an appropriate restrictor for your DHW 
system. See the Installation & Operation 
Manual (page 21, 22) for detailed 
procedures.  

Flow Restrictors (Orange, Yellow, and Blue) 

Ensure that the Air Vent Cap is removed 

System will not be properly filled 
without the air vent cap removed. Air in 
the system may cause malfunctions 
and system overheating.    

a. Direct to the
    external drain

c. To the laundry tub

d. To the laundry
     Tub via a condensate pump

b. To the drain via
     A neutralizer 

System Fill 

C

onnection 

The Navien NCB boilers 
have a built-in air vent 
on top of the internal 
circulator to purge air 
from the boiler system. 

Th
ha
on
cir
fro

Air Vent Cap

Before filling the boiler, remove the air vent cap to 
allow the system to fill properly. Replace the cap 
when the system is full. 