![Naturela NPBC-V6T Скачать руководство пользователя страница 22](http://html1.mh-extra.com/html/naturela/npbc-v6t/npbc-v6t_user-manual_711007022.webp)
Electronic pellet burner controller - NPBC-V6T-2
Diagnostic
Pressing the "►" button when the controller is in one of the text information screens, goes to the
"Diagnostics" screen, which is a list of information about all the registered errors and the exact
time and date of its occurrence. If there are more than 4 entries, the next or previous page is
displayed with the “▼” or “▲” buttons. Scrolling from a text information screen to the
"Diagnostics" screen can also be done by a gesture – slide to the left and the changing of the pages
with diagnostic data - by sliding up and down the screen length.
By pressing the button for more than 2 seconds, the diagnostic information is cleared and
displayed message
“No information” and save the time and the date of the reset. When
“Diagnostics “ screen is displayed you can see an entry with the event “Start”
,
fixing
the date and
the time from which is going to begin the new diagnostic information. The star symbol mark the
next registered event.
The messages that are possible to appeared on this screen are shown in table 2. The messages from
1 to 13 will also appear and as a message for an error on the bottom line of the main screen.
Table 2
Message
Cleaning the
error
Description
1
Back burning
Button
The thermostat for back burning has been activated
2
Off boiler TS
automatically Boiler's temperature sensor is disconnected
3
Short boiler TS
automatically Boiler's temperature sensor is on short
4
Boiler Frost
Button
The temperature in the boiler is below 0°C
5
Ignition Fail
Button
6
Off RB Sensor
automatically The back burning temperature sensor is disconnected
7
Short RB Sensor
automatically The back burning temperature sensor is on short
8
Off WH Sensor
automatically DHW temperature sensor is disconnected
9
Short WH Sensor
automatically DHW temperature sensor is on short
10
Off PT Sensor
automatically pt100 high temperature sensor is disconnected
11
Short PT Sensor
automatically pt100 high temperature sensor is on short
12
High Flue gas temp
Button
The exhaust temperature is too high
User Manual / ver. 1.2
http://www.naturela-bg.com/en/
page 22 of 41