Electronic pellet burner controller  - NPBC-V6T-2

The   controller   uses   another   method   of  

intermediate   cleaning,

  in   which   the   fire   is   not

extinguished, but only increases the power of the fan or activates the FC output to activate some
cleaning  mechanism.  The  necessary settings  for  this  cleaning   method   are  set  from  the  menu

"Service settings" »"Burning Setup "» "Fuel X" »" Intermediate cleaning "

. The parameters

which must be set are: the time during which the intermediate cleaning procedure is repeated, the
fan speed to be maintained during cleaning, how long to clean and whether to use the FC output
for another mechanism for cleaning. During this cleaning the pellet delivery do not stop.

User Manual / ver. 1.2     

 

http://www.naturela-bg.com/en/

 

page 10 of 41

Содержание NPBC-V6T

Страница 1: ...Electronic pellet burner controller NPBC V6T 2 ELECTRONIC CONTROLLER FOR PELLET STOVE WITH WATER JACKET NPBC V6T 2 SOFTWARE VERSION 58 29 User Manual ver 1 2 http www naturela bg com en page 1 of 41...

Страница 2: ...Changed and updated version to 58 29 Added option for changing the set temperature with gestures and swiping up down left right on the screen Making the device use extremely comfortable and more effi...

Страница 3: ...s not saved No need to use a smartphone or a computer when connecting the Wi Fi module to the home Internet network The name of the home Wi Fi network can be selected directly from the screen of the c...

Страница 4: ...e of the water in the boiler the signal from RT input from the universal room thermostat or temperature measured in the room There it is installed additional control module with room thermostat functi...

Страница 5: ...power up to 180W Central heating installation circulation pump power up to 180W Optional Analogue output 0 10V for frequency inverter to power up a powerful air fan Photo sensor to detect the burning...

Страница 6: ...Electronic pellet burner controller NPBC V6T 2 User Manual ver 1 2 http www naturela bg com en page 6 of 41...

Страница 7: ...er heater pump OD Input for switch for Forced stop with normally open or normally closed contact or for vacuum switch pressure switch with normally closed contact FC Fan for cleaning or linear actuato...

Страница 8: ...r is transferred to the pellets and the necessary oxygen is delivered to ignite the fuel Usually during Stage 2 the fan is set at a lower speed not to cool the flame and after a more stable fire to in...

Страница 9: ...ll not use the heater When switching off the burner whether from the On Off button by timer or via OD input it immediately goes to extinguish procedure The fuel delivery is stopped and the fans contin...

Страница 10: ...ings for this cleaning method are set from the menu Service settings Burning Setup Fuel X Intermediate cleaning The parameters which must be set are the time during which the intermediate cleaning pro...

Страница 11: ...ntroller s main screen appears after turning the power supply on User Manual ver 1 2 http www naturela bg com en page 11 of 41 Time Boiler s water temperature External stop activated input OD Heater O...

Страница 12: ...ature of the active timers Current calculated power of the burner A calibrating constant parameter for the auger motor s capacity must be set to assure the correct value of the burner s power The cali...

Страница 13: ...onnection Active room thermostat Set temperature is reached dditional control module with room thermostat function NRC 8 SV On Active FC output FC Active additional output AUX Active DHW Pump Active C...

Страница 14: ...the incorrectly entered parameter will restore its old possible value The selection of another parameter for editing can be done with the or buttons by pressing them in one or the other direction The...

Страница 15: ...ll mark it and the second one will switch over it User Manual ver 1 2 http www naturela bg com en page 15 of 41 Exit to the mainscreen button Return button Alfanumeric key board Caps change button Ser...

Страница 16: ...s which must be pressed for more than 5 seconds to unlock the screen User Manual ver 1 2 http www naturela bg com en page 16 of 41 Select mode button Button to change the set temperature Main menu but...

Страница 17: ...a gesture from left to right When the current screen is a graph of the pellets consumption with a gesture from bottom to top goes to the graph from the previous day and back with a gesture from top t...

Страница 18: ...ges of the burner The working stages are described as follows below in Table 1 Table1 Work phase Work phase 1 Cleaning 6 Power P1 2 Feeding 7 Power P2 3 Ignition 8 Power P3 4 Unfolding fire 9 Addition...

Страница 19: ...ill continue to operate in Timers mode according the active timers Changing the set temperature for heating the water in the boiler By pressing the button when the controller is in Main screen the use...

Страница 20: ...er is in the Pellet consumption screen opens the the Information screen The same can be done with a gesture slide on the left The set temperature of the boiler and the consumption of pellets from its...

Страница 21: ...r Access point The modem is waiting for the local WiFi network s SSID and password APAssociated The modem is connected to a router Internet Access Established internet connection Connected The modem i...

Страница 22: ...xt registered event The messages that are possible to appeared on this screen are shown in table 2 The messages from 1 to 13 will also appear and as a message for an error on the bottom line of the ma...

Страница 23: ...the Diagnostics screen has been reset If is pressed from the Diagnostics screen go to the front Information screen The same can be done with a gesture sliding on the right When the error messages appe...

Страница 24: ...automatically set after setting the date After exiting the menu if there is a change of the hour or the minutes the seconds automatically reset When only the date has changed the seconds do not reset...

Страница 25: ...room thermostat etc The time in the column On must be before the time in the column Off If necessary set the Off time first to provide larger range for the On setting Information whether the timers a...

Страница 26: ...Settings for the circulation pumps work of the external heating installations For the Central heating pump with row On you can set the minimum temperature of the boiler to which the pump can turn on w...

Страница 27: ...The temperature of the water in the water heater is lower than the set temperature in the installation area for DHW row WH set temp minus row Hysteresis After reaching the set temperature the circula...

Страница 28: ...ps or to fill up the installations with fluid The maximum time for manual control is about 6 minutes After that the controller turn off outputs and go to the previous screen This mode can be used for...

Страница 29: ...firm and the data is sent to the WiFi module When you press the button to scan nearby WiFi networks the screen below displays information about the number of all of the found networks When the scan is...

Страница 30: ...is replaced by the symbol for security reasons After entering all digits from the access code you must press the button to confirm it If the code is correct the Service Settings sub menu screen is di...

Страница 31: ...cuum switch which must be with normally closed contact If it is open first stopped pellets feeding the main fan is increased to 100 and if it last more than 66 sec the burner is switched off General S...

Страница 32: ...long duration as it is set in the menu Service Settings Power Modulation parameter Duration After the maximum time for suspension has expired if the thermostat remains activated the burner is extingui...

Страница 33: ...driven by linear actuators which need power supply for one direction of movement and when the power failure they return back The added pause is in order to wait for the grate to return to its starting...

Страница 34: ...dose You must have in mind that if there is an activated alarm that does not allow the burner to be turn on the frost protection function will not activate and the burner will not ignite The function...

Страница 35: ...V6T 2 Inputs Status This is a service screen that displays the status of all controller inputs in real time User Manual ver 1 2 http www naturela bg com en page 35 of 41 Power switch for output SF At...

Страница 36: ...aning row Stop and in case of an alarm back burning row Alarm The setting for additional fan or other cleaning mechanism are common to all fuels and can be changed from menu Service settings Additiona...

Страница 37: ...mum possible power that burner can achieve The power P2 should be 50 from P3 and P1 to be 20 from P3 With these settings the controller will be able smoothly to modulate the power of the burner in ran...

Страница 38: ...g mechanism connected to the output FC is set from menu Service setting Additional cleaning You must have in mind that when setting FC pause or FC AUX is selected the actual duration of the intermedia...

Страница 39: ...xecutive module does not work In this case you have to look how the green LED of the executive module flashes MCU Status Normally it will light up on and off with a pause for 0 5 seconds and if it fla...

Страница 40: ...Flame Detection Ignition C 5 60 20 Extinction C 5 90 40 min 5 60 5 Power Modulation P3 T C 2 30 10 P2 T C 1 29 05 P1 T C 0 28 00 Duration minutes 0 120 20 Overheating C 00 20 8 Cleaning Start Fan seco...

Страница 41: ...0 100 50 Exhaust fan speed 0 100 50 Setup 3 Feed seconds 0 1 25 0 5 0 Cycle seconds 4 120 30 Fan speed 0 100 100 Exhaust fan speed 0 100 100 Suspend Feed seconds 0 1 25 0 2 0 Cycle seconds 4 120 120...

Отзывы: