Electronic pellet burner controller – NPBC-V3C-1/ NPBC-V4C-1/ NPBC-V4E-1

Common Factory Settings for all types of fuel:

Equipment 

– Enable/disable the additional mechanisms and sensors of the burner's configuration and

set the polarity of the room thermostat's and the OD input's contacts:

General Settings

 – Set the internal auger motor's active time (Burner Feeder), the maximum allowed 

set temperature for the boiler, the main auger's capacity and pending time for FC output, if necessary. 

The internal auger motor always starts at the same time with the main auger and works for as long as it
is set in this menu. Its active time in seconds is:

T

ia

=

T

fa

Operation

100

+

Extra Sec

where: T

ia

 is the internal auger motor's active time;

T

fa

 is the fuel auger's active time (main auger).

Instead of powerful cleaning fan, the FC output can control a mechanical cleaning actuator. During the
cleaning procedures where the FC output is active, the actuator moves in one direction to push out the
ashes. After the procedure is over the controller cuts the power supply to the FC output and the
actuator needs time to get back to its initial position. Put a check sign on the parameter FC output and

User Manual / ver 3.11

   

http://www.naturela-bg.com/en/

 

page 28 of 37

Put a check sign if the burner

works with an internal auger motor

Put check signs if the CH installation

has a room thermostat and its

contact is normally opened (NO)

Put a check sign if the burner

works with a high temperature

sensor for the exhaust gases

Put a check sign if the burner

works with an external stop switch

connected to the OD input

with normally closed contact (NC)

Check this box if the controller

comands a pump for

the hot water installation

The internal auger motor

will work 1.5 times longer

than the main auger

Additional seconds for

the internal auger's active time

If checked, every procedure where

FC output was supplied will be 

followed by the same amount of

time without any voltage to it

Set this parameter to assure the

accuracy of the statistical information

for pellet consumption.

Check the instructions how to

calibrate the auger motor on page 20.

Check this box if the controller

comands a pump for

the central heating installation

Содержание NPBC-V4E-1

Страница 1: ...pellet burner controller NPBC V3C 1 NPBC V4C 1 NPBC V4E 1 Electronic Pellet Burner Controller NPBC V3C 1 NPBC V4C 1 NPBC V4E 1 SOFTWARE VERSION 56 27 User Manual ver 3 11 http www naturela bg com en p...

Страница 2: ...n 10 minutes or less the burner will remain off because otherwise the extinguishing procedure may begin before the fire is stabilized If OD input activates during Ignition or Unfolding procedures the...

Страница 3: ...unctionality and a new improved executive module NPBC V4 or NPBC V4E This models most important advantages are Clearer and intuitive user interface with modern looking menus and 6 control buttons Addi...

Страница 4: ...s runs up to two circulation pumps for the heating installation and for the hot water heater installation All of the controlled mechanisms must work on 220VAC or 110VAC mains power supply Important NP...

Страница 5: ...hermostat for better control of the burning process according to the room temperature USB interface for connection with a computer NPBC V3C 1 NPBC V4C 1 INPUTS AND OUTPUTS DESCRIPTION Outputs Inputs F...

Страница 6: ...Electronic pellet burner controller NPBC V3C 1 NPBC V4C 1 NPBC V4E 1 User Manual ver 3 11 http www naturela bg com en page 6 of 37...

Страница 7: ...Electronic pellet burner controller NPBC V3C 1 NPBC V4C 1 NPBC V4E 1 User Manual ver 3 11 http www naturela bg com en page 7 of 37...

Страница 8: ...Electronic pellet burner controller NPBC V3C 1 NPBC V4C 1 NPBC V4E 1 User Manual ver 3 11 http www naturela bg com en page 8 of 37...

Страница 9: ...r turns off and the burner goes to Unfolding fire phase to stabilize the fire If the pellets do not ignite during the set time for this the burner loads a new portion and makes a new attempt for ignit...

Страница 10: ...r detects that the fire is off the burner goes to cleaning phase and after that in initial state During the cleaning phase the main fan works on 100 of its power If there is an additional powerful cle...

Страница 11: ...oto sensor The messages on the bottom line of the screen appear in different colors depending on the type of information they provide white text for the date green for the current work phase and red U...

Страница 12: ...information Level of illumination measured by the photo sensor Exhaust fan s speed Information about the upcoming action of the timer If there are no active timers or the burner is in Standby mode the...

Страница 13: ...Clean 5 Suspend 10 Extinguishing While in Standby mode the burner doesn t work If it was working right before switching to this mode it will instantly start the extinguishing procedure It needs some t...

Страница 14: ...timers set the burner remains off and a warning message is displayed on the screen As soon as any of the timers is activated the burner will switch to Timers mode automatically How to change the set...

Страница 15: ...orresponding date for the currently displayed information and below is the total consumption for this day Information about some of the current parameters While on Pellet consumption screen press the...

Страница 16: ...s current state can be any of the following Idle No connection with WiFi router Access point The modem is waiting for the local WiFi network s SSID and password APAssociated The modem is connected to...

Страница 17: ...disappear after the reason for the message is no longer present Others can be dismissed by holding the left navigation button for more than 2 seconds while on main screen Table 2 Message Cleaning the...

Страница 18: ...rent menu caused changes in some of the parameters from a different menu the controller displays warning messages For example Parameter settings NPBC V3C 1 NPBC V4C 1 has two main groups of parameters...

Страница 19: ...or next editable parameter The up and down navigation buttons change the currently selected parameter s value or put remove a check sign The parameter s type could be any of the following editable nu...

Страница 20: ...esponding to the selected row Set Time Date The time format is 23 59 and the date format is dd mm yy The day of the week is automatically calculated after setting the date After confirming the setting...

Страница 21: ...be active and there should not be any errors that require the burner to stay off The time in the column On must be before the time in the column Off If necessary set the Off time first to provide larg...

Страница 22: ...nformation to be displayed for each field from the following list Flame level Level of illumination measured by the photo sensor Exhaust fan Current speed of the exhaust fan Timers If there are any ac...

Страница 23: ...in the boiler gets lower than the difference between Pump On and Hysteresis With the settings on the above screen the pump will turn off when the temperature of the water in the boiler gets lower tha...

Страница 24: ...heating installation works with a room thermostat and if it activates the CH pump stops If both installations don t need more heat the burner switches to Suspend power level If any of the installatio...

Страница 25: ...nds are not enough repeat this step several times When the auger is full stop the manual feeding 3 Place a bucket or another tank at the end of the auger motor to collect the pellets 4 Start the manua...

Страница 26: ...menu helps with its initial setting or when changing the WiFi network Press the Menu button to exit this screen without making any changes Press the down navigation button to start the Access point mo...

Страница 27: ...its input Press the up or down navigation button to change the value for each position and the left right buttons to switch between positions Confirm the code with the Menu button Some of the paramete...

Страница 28: ...over the controller cuts the power supply to the FC output and the actuator needs time to get back to its initial position Put a check sign on the parameter FC output and User Manual ver 3 11 http www...

Страница 29: ...level the burner automatically switches to it If the difference doesn t increase the burner works on Suspend power level for as long as it is set in the parameter Duration min While on Suspend if the...

Страница 30: ...Setup If a high temperature sensor pt100 is connected to the controller s PT input it will monitor the temperature of the exhaust gases If it gets higher than the value of the parameter Warning in thi...

Страница 31: ...k the check box enter the code and then repeat it If you use less than 6 digits make sure to leave the same ones when you repeat the code If it is correctly set the next access to the Factory Settings...

Страница 32: ...ain Set the time interval between two automatic cleaning procedures from the parameter Cycle min Ignition This menu contains all of the required parameters to set the ignition If the first ignition at...

Страница 33: ...ettings for these power levels are identical Set the active time of the auger to load a portion of pellets Feed Sec and the cycle Cycle Sec between two portions The exact amount of the fuel as well as...

Страница 34: ...se it periodically to clean the ashes Put a check sign on the line Activate to enable these procedures on the line Change fans to enable the usage of the fans during this procedure and or on the line...

Страница 35: ...ormally it should blink on 0 5 seconds If this is the case the problem might be in the connection between the modules If the LED is blinking on 2 4 seconds there is no software in the Executive module...

Страница 36: ...ty kg h 0 5 60 0 10 0 Flame Detection Ignition level 0 150 100 seconds 10 240 20 Extinction level 0 150 40 seconds 10 240 60 Power Modulation P3 T C 2 30 10 P2 T C 1 29 05 P1 T C 0 28 00 Duration minu...

Страница 37: ...Cycle seconds 4 120 30 Fan speed 0 100 50 Exhaust fan speed 0 100 50 Setup 3 Feed seconds 0 1 25 0 5 0 Cycle seconds 4 120 30 Fan speed 0 100 100 Exhaust fan speed 0 100 100 Suspend Feed seconds 0 1 2...

Отзывы: