Chapter 1
Installing and Configuring the SCXI-1126
©
National Instruments Corporation
1-19
The SCXI system should now operate properly with your ADE software.
If the test did not complete successfully, refer to the
Troubleshooting the
Self-Test Verification
section for troubleshooting steps.
To configure the frequency range, filter range, threshold level, and
threshold hysteresis of the SCXI-1126, refer to the
section.
Troubleshooting the Self-Test Verification
If the Self-Test Verification did not verify the chassis configuration, check
the following items to successfully complete system configuration:
•
If you get the message
Unable to test chassis at this time
,
you have not designated at least one module as connected to an
E Series DAQ device.
1.
Return to the
Manually Adding and Configuring Modules in
section.
2.
Change the configuration of the cabled module in the system from
not being connected to connected to device
x
.
•
If you get the message
Failed to find
, followed by the module
codes and the message
Unable to communicate with chassis
:
1.
Make sure the SCXI chassis is powered on.
2.
Make sure the cable between the SCXI chassis and E Series DAQ
device is properly connected.
3.
Inspect the cable connectors for bent pins.
4.
Make sure you are using the correct NI cable assembly.
5.
Test the E Series DAQ device to verify it is working properly.
Refer to the E Series DAQ device user manual for more
information.
•
If you get the message
Failed to find
, followed by module codes
and the message
Instead found: module with ID 0Xzz
:
1.
Return to the
Manually Adding and Configuring Modules in
section
and make sure the correct module is in the
specified slot.
2.
Delete the incorrect module as described in the
SCXI-1126 from Measurement & Automation Explorer
section.
3.
Add the correct module as described in the
Configuring Modules in NI-DAQmx
section.