NI PS-12/13 Power Supply User Manual and Specifications
|
© National Instruments
|
15
Note
In case of over temperature event, the device shuts down output voltage.
Manual reset of AC power is required to continue operation.
Withstand Voltage
NI PS-12
Input-output .............................................. 3.0 kVAC (20 mA)
Input-FG ................................................... 2.0 kVAC (20 mA)
Output-FG................................................. 500 VAC (20 mA) for 1 min
NI PS-13
Input-output .............................................. 3.0 kVAC (10 mA)
Input-FG ................................................... 2.0 kVAC (10 mA)
Output-FG................................................. 500 VAC (10 mA) for 1 min
Isolation Resistance
NI PS-12 ........................................................... More than 100 M
Ω
at Ta = 25 °C and
70% relative humidity,
Output-FG................................................. 500 VDC
NI PS-13 ........................................................... More than 100 M
Ω
at Ta = 25 °C and
70% relative humidity,
Output-FG................................................. 500 VDC
Vibration
NI PS-12 ........................................................... At non operation, 10-55 Hz, 10 min, 1 cycle,
19.6 m/s
2
constant, X, Y, Z, 1 hour each
NI PS-13 ........................................................... At non operation, 10-55 Hz, 10 min, 1 cycle,
19.6 m/s
2
constant, X, Y, Z, 1 hour each
Safety
This product meets the requirements of the following standards of safety for electrical equipment
for measurement, control, and laboratory use:
•
UL60950-1
•
CSA60950-1
•
EN60950-1
Note
For UL and other safety certifications, refer to the product label or the
Online
Product Certification
section.