Figure 5.
NI 6509 Signal Connections
Protecting Inductive Loads
When inductive loads are connected to outputs, a large
counter-electromotive force may occur at switching time because of the
energy stored in the inductive load. These flyback voltages can damage
the outputs and/or the power supply.
To limit these flyback voltages at the inductive load, install a flyback diode
across the inductive load. For best results, mount the flyback diode within
18 inches of the load. Figure 6 shows an example of using an external
flyback diode to protect inductive loads.