background image

cFP-20xx Quick Start Guide

8

ni.com

Mounting the Backplane in a Standard 19-in. Rack

1. Fasten the rack-mount bracket to the back of the cFP-BP-

x

 using the captive 

screws on the bracket.

2. Bolt the rack-mount accessory to a standard 19-in. rack.

 NA

TIO

NA

INS

TR

UM

EN

TS

Содержание cFP-20xx

Страница 1: ...EW RT controller Mounting hardware DIN rail panel mount or rack mount accessory I O module s cFP BP x backplane connector blocks cables 11 30 VDC power supply Accessories Ethernet cable number 2 Phill...

Страница 2: ...erminal on the cFP BP x backplane to the system safety ground The backplane PE ground terminal has the following symbol stamped beside it Connect the backplane PE ground terminal to the system safety...

Страница 3: ...rance 4 slots 246 mm 9 68 in 8 slots 441 mm 17 4 in Cooling Outline 51 mm 2 in Cooling Outline 51 mm 2 in Min 182 mm 7 18 in 106 mm 4 18 in Cabling Clearance Cooling Outline 51 mm 2 in All Around 4 sl...

Страница 4: ...mount plates to the back of the cFP BP x using a number 2 Phillips screwdriver and the 8 32 5 16 in countersink screws shipped with the kit Caution Do not use screws longer than 5 16 in to fasten the...

Страница 5: ...on 5 cFP 20xx Quick Start Guide 104 78 mm 4 1 in 63 50 mm 2 5 in 22 23 mm 0 9 in 33 15 mm 1 3 in 129 54 mm 5 1 in 311 40 mm 12 3 in 387 60 mm 15 3 in 407 80 mm 16 1 in 127 00 mm 5 0 in 440 94 mm 17 4...

Страница 6: ...Rail NI recommends DIN rail mounting for the cFP BP 4 only Use panel mounting or rack mounting for the cFP BP 8 The DIN rail mounting kit is NI part number 778614 01 1 Fasten the DIN rail clip to the...

Страница 7: ...2 Insert one edge of the DIN rail into the deeper opening of the DIN rail clip 3 Press down firmly on the backplane to compress the spring until the clip locks in place on the DIN rail 4 Connect the...

Страница 8: ...m Mounting the Backplane in a Standard 19 in Rack 1 Fasten the rack mount bracket to the back of the cFP BP x using the captive screws on the bracket 2 Bolt the rack mount accessory to a standard 19 i...

Страница 9: ...ruments Corporation 9 cFP 20xx Quick Start Guide 3 Connect the PE ground terminal on the cFP BP x to safety ground Caution Disconnect power before removing the backplane from the bracket NA TIO NA L I...

Страница 10: ...with the NI logo at the top and align the captive screws on the controller with the holes on the backplane 3 Seat the card edge at the back of the controller in the card edge connector on the backpla...

Страница 11: ...National Instruments Corporation 11 cFP 20xx Quick Start Guide NAT IONAL INSTRU MEN TS...

Страница 12: ...O module with the holes on the backplane 2 Press firmly to seat the I O module on the backplane 3 Using a number 2 Phillips screwdriver with a shank of at least 64 mm 2 5 in length tighten the captive...

Страница 13: ...accessories while power is applied to them 1 Wire field devices as described in the I O module and connector block operating instructions Caution Hazardous voltage wiring should be performed by quali...

Страница 14: ...ter Caution To prevent data loss and to maintain the integrity of your Ethernet installation do not use a cable longer than 100 m If you are using a 100 Mbps Ethernet National Instruments recommends u...

Страница 15: ...using a backup power supply connect the positive lead to V2 and the negative lead to one of the C terminals The cFP 20xx uses the power supply with the higher voltage level V2 is isolated from the oth...

Страница 16: ...0xx is ready to be configured If you have already assigned an IP address to the cFP 20xx the STATUS LED turns off and the A B C and D LEDs come on for about 15 seconds as LabVIEW RT starts up Once the...

Страница 17: ...e installed 2 Close all other applications 3 Insert the National Instruments FieldPoint Software CD into the CD ROM drive on your computer 4 Follow the onscreen instructions to complete the installati...

Страница 18: ...mum power to connected I O modules 9 W Maximum number of banks Determined by network topology Memory cFP 2000 16 MB nonvolatile 16 MB DRAM cFP 2010 32 MB nonvolatile 32 MB DRAM cFP 2020 32 MB nonvolat...

Страница 19: ...r requirements cFP 2020 6 1 W 1 1 I O module power requirements Physical Characteristics Screw terminal wiring 16 26 AWG copper conductor wire with 7 mm 0 28 in of insulation stripped from the end Tor...

Страница 20: ...Sinusoidal IEC 60068 2 6 10 500 Hz 5 g Operating shock IEC 60068 2 27 50 g 3 ms half sine 18 shocks at 6 orientations 30 g 11 ms half sine 18 shocks at 6 orientations Safety This product meets the re...

Страница 21: ...CC 47 CFR Part 15B Class A emissions ICES 001 Class A emissions For EMC compliance operate this device with shielded cabling CE Compliance This product meets the essential requirements of applicable E...

Страница 22: ...Cable Connector Pinouts Pin Connector 1 Connector 2 Normal Connector 2 Crossover 1 white orange white orange white green 2 orange orange green 3 white green white green white orange 4 blue blue blue 5...

Страница 23: ...elephone support outside the United States contact your local branch office Australia 1800 300 800 Austria 43 662 457990 0 Belgium 32 0 2 757 0020 Brazil 55 11 3262 3599 Canada 800 433 3488 China 86 2...

Страница 24: ...n on ni com legal for more information about National Instruments trademarks Other product and company names mentioned herein are trademarks or trade names of their respective companies For patents co...