Caution
Do not remove modules unless power has
been switched off or the area is known to be
nonhazardous.
Caution
Substitution of components may impair
suitability for Class I, Division 2, or Zone 2.
Caution
The system must be installed in an enclosure
certified for the intended hazardous (classified)
location, having a tool secured cover/door, where a
minimum protection of at least IP54 is provided.
Special Conditions for Hazardous Locations Use in
Europe and Internationally
The NI 9219 has been evaluated as Ex nA IIC T4 Gc equipment
under DEMKO 07 ATEX 0626664X and is IECEx UL 14.0089X
certified. Each NI 9219 is marked II 3G and is suitable for use
in Zone 2 hazardous locations, in ambient temperatures of -40 °C
≤ Ta ≤ 70 °C. If you are using the NI 9219 in Gas Group IIC
hazardous locations, you must use the device in an NI chassis that
has been evaluated as Ex nC IIC T4, Ex IIC T4, Ex nA IIC T4, or
Ex nL IIC T4 equipment.
NI 9219 Getting Started Guide
|
© National Instruments
|
7