Getting Started with NI Integrated Steppers and NI 73xx Motion Controllers

1.

Boot the NI PXI embedded controller into the real-time operating system. The PXI 
controller automatically boots into LabVIEW RT Safe Mode when no software is installed. 
LabVIEW RT Safe Mode loads with the basic real-time operating system and automatically 
attempts to connect to the network using DHCP. If DHCP is not available, the controller 
connects to the network with a link-local IP address.

Tip

You can connect a monitor to the PXI to display startup messages such as the 

IP address and MAC address.

2.

Launch Measurement & Automation Explorer (MAX) on the development computer by 

clicking the MAX icon on the desktop (

), or by selecting 

Start»All Programs»

National Instruments»Measurement & Automation

.

3.

Expand the 

Remote Systems 

branch. MAX lists the PXI controller as the model name of 

the controller followed by the MAC address (for example, 

NI-PXI-8104 00802f108562

).

Tip

Record the PXI controller MAC address, located on the side of the controller, 

for use in identifying the controller. The label also can be removed and placed on the 
front of the controller for easier access. If you have connected the PXI controller to a 
monitor, the MAC address also appears when the PXI system boots up.

4.

Select the 

System Settings 

tab and type a descriptive name for the system in the 

Name

 

field.

5.

(Optional) Complete this step only if the target has an empty IP address (0.0.0.0). Select the 

Network Settings

 tab and select 

DHCP or Link Local 

from the 

Configure IPv4 Address

 

list to assign an IP address or select 

Static 

to specify a static IP address in the 

IPv4 Address

 

section.

6.

Click 

Save

 on the toolbar and let MAX reboot the system.

7.

When the new system name appears under 

Remote Systems

, expand the controller item in 

the tree, right-click 

Software

, and select 

Add/Remove Software

.

8.

Install the LabVIEW Real-Time software and NI-Motion on the RT target. Go to 

ni.com/info

 and enter 

etspc

 for the latest information about supported software.

9.

Click 

Next

 to install the selected software on the controller. Click 

Help

 if you need 

information about installing recommended software sets.

10. Wait for installation to complete, then click 

Finish

.

11. Expand the 

Devices and Interfaces

 item under the PXI system. 

12. Right-click the remote motion controller icon and select 

Map to Local Machine

. This 

assigns a local board ID to the remote motion controller in the host system. 

13. Mapping the remote controller into the local system allows you to configure the controller 

through MAX exactly as you would a controller that is in the host system. You can initialize 
the controller, download firmware, and use the interactive and configuration panels exactly 
as you would on a controller installed in the host machine. You also can write VIs using the 
remote motion controller through the local board ID assigned to it.

Содержание 73 Series

Страница 1: ...on Controllers Only 5 NI UMI 7772 7774 and NI ISM 74xx Configuration and Installation 7 Step 1 Connect and Configure the UMI 7772 7774 7 Step 2 Connect the Drive Command Signals to the UMI 7772 7774 9...

Страница 2: ...ion and Configuration 30 Step 1 Update Firmware on the Motion Controller 30 Step 2 Configure the NI Motion Controller 31 Step 3 Test the Motor In MAX 32 Where to Go Next 33 Worldwide Support and Servi...

Страница 3: ...One of the following software packages and documentation LabVIEW 8 5 or later LabWindows CVI 8 5 or later Microsoft Visual C 6 0 Microsoft Visual Basic 6 0 Figure 1 shows the hardware connections usi...

Страница 4: ...you can use them with the corresponding version of NI Motion Refer to Step 1 Update Firmware on the Motion Controller in the Software Installation and Configuration section for detailed instructions S...

Страница 5: ...r into the slot The connection may be tight but do not force the controller into place Note Check that the bracket of the device aligns with the hole in the back panel rail of the computer chassis 6 S...

Страница 6: ...the system in the Name field 5 Optional Complete this step only if the target has an empty IP address 0 0 0 0 Select the Network Settings tab and select DHCP or Link Local from the Configure IPv4 Addr...

Страница 7: ...se this board ID for any VIs that run on the host and use the remote motion controller 15 Close MAX NI UMI 7772 7774 and NI ISM 74xx Configuration and Installation This section covers the hardware set...

Страница 8: ...d with integrated steppers 3 Connect the positive lead of the 24 V external power supply to the V terminal and the negative lead to the C terminal then connect the V terminal to the Viso terminal and...

Страница 9: ...Connect the integrated stepper Dir wire green to the DB15M cable pin 12 wire light green which corresponds to the UMI 7772 7774 Dir CCW terminal 4 Connect the integrated stepper Step wire orange and...

Страница 10: ...nnect the Drive Fault Signal to the UMI 7772 7774 Complete the following optional steps to connect the drive fault signal to monitor the NI integrated stepper for faults Note If you do not connect the...

Страница 11: ...t the encoder wires to the DB25M cable as indicated in Table 1 Table 1 NI ISM to UMI 7772 7774 Connections NI ISM Signal Name NI ISM Wire Color DB25M Wire Number Color UMI 7772 7774 Signal Name A blue...

Страница 12: ...ack wire to the power supply V connector 4 Connect the NI UMI power supply ground common terminal and NI PS 12 13 power supply ground connections to ensure a common reference Step 7 Configure the NI I...

Страница 13: ...for the DIP switch settings that this document uses Table 2 DIP Switch Settings Setting Name Switch Position Corresponding Value Running Current 100 Idle Current 50 Self Test Off Step Noise Filter 2...

Страница 14: ...on the NI ISM 7400 7401 7402 is unused NI recommends removing and insulating this wire 1 Cut off the NC wire 2 Insulate the end of the wire if there is any exposed metal remaining Load Inertia 0 4X St...

Страница 15: ...D does not flash or turn solid green turn off all power verify the connections and try again 3 Verify that the V LED on the UMI 7772 7774 illuminates If the 24 VDC power supply has also been connected...

Страница 16: ...slot NI 7330 NI 7340 or NI 7350 motion controller UMI 7764 SH68 C68 S cable to connect your NI UMI and motion controller 5 V power supply for the UMI 7764 Snap on ferrite bead for the power supply cab...

Страница 17: ...n Note If you are using a Real Time OS install LabVIEW Real Time on the development computer before installing NI Motion so that the RT support files install Complete the following steps to install th...

Страница 18: ...he device into place 5 Attach the front panel of the PXI controller to the front panel mounting rails of the chassis with the slot screws on the chassis Caution Always power on the computer containing...

Страница 19: ...T Safe Mode when no software is installed LabVIEW RT Safe Mode loads with the basic real time operating system and automatically attempts to connect to the network using DHCP If DHCP is not available...

Страница 20: ...re the controller through MAX exactly as you would a controller that is in the host system You can initialize the controller download firmware and use the interactive and configuration panels exactly...

Страница 21: ...ou must set the DIP switches to the following settings to match the polarity configuration for the integrated steppers Inhibit Input S2 Active Low Inhibit Output S1 Active Low The UMI 7764 DIP switch...

Страница 22: ...wire green to the Motion I O terminal block Direction CCW 1 terminal BP4 BP3 BP2 BP1 GND 5 V TRIG4 TRIG3 TRIG2 TRIG1 ASSY186343A 01 UMI 7764 FWDLIM1 HOME1 REVLIM1 INHIN1 GND AOUT1 AOGND INHOUT1 STEP C...

Страница 23: ...to the Motion I O terminal block 5V terminal Figure 14 shows the connections Figure 14 NI ISM 7400 7401 7402 to UMI 7764 Drive Command Connections 1 STEP 2 STEP 3 DIR 4 DIR 5 EN 6 EN 7 OUT 8 OUT 9 N...

Страница 24: ...IN3 GND AOUT3 AOGND INHOUT3 STEP CW 3 DIR CCW 3 5 V GND ENCA3 ENCA3 ENCB3 ENCB3 INDEX3 INDEX3 AXIS3 REQUIRED INPUTS 5V GND AIGND AREF AIN4 AIN3 AIN2 AIN1 FWDLIM2 HOME2 REVLIM2 INHIN2 GND AOUT2 AOGND I...

Страница 25: ...o UMI 7764 Cable Drive Enable Connections Step 4 Optional Connect the Drive Fault Signal to the UMI 7764 Complete the following optional steps to connect the drive fault signal to monitor the NI integ...

Страница 26: ...uded connector 2 Connect the encoder wires to the UM 7764 Motion I O terminal block as indicated in Table 3 Table 3 NI ISM to UMI 7764 Motion I O Terminal Block Connections NI ISM Signal Name Wire Col...

Страница 27: ...er Supply Terminals 1 Connect the an AC input cable to the line neutral and ground connectors 2 Connect the integrated stepper V red wire to the power supply V connector 3 Connect the integrated stepp...

Страница 28: ...wing figure shows the DIP switch location and functions Note If you change the DIP switch settings you must power cycle the NI ISM for the new settings to take effect Figure 19 NI ISM 7400 7401 7402 D...

Страница 29: ...unused NI recommends removing and insulating this wire for optimal operation 1 Cut off the NC wire 2 Insulate the end of the wire if there is any exposed metal remaining Step Noise Filter 2 MHz Step...

Страница 30: ...controller Step 1 Update Firmware on the Motion Controller Firmware is software that is loaded onto the motion controller Firmware allows you to update the motion controller with new features and upd...

Страница 31: ...6 Click Axis Configuration and set Type to Stepper 7 Click the Stepper Settings tab on the bottom of the window and set Stepper steps per revolution to 25 000 Note The Stepper steps per revolution se...

Страница 32: ...the Motor In MAX You will now move the motor using the NI motion controller and MAX Select the 1 D Interactive panel in the Configuration tree and change the settings to match those shown in Figure 2...

Страница 33: ...oints This document is task based and takes you through each phase of designing and executing a motion application NI Motion Function Help Contains function reference information for C and Visual Basi...

Страница 34: ...ers Visit ni com services for NI Factory Installation Services repairs extended warranty calibration and other services Visit ni com register to register your National Instruments product Product regi...

Отзывы: