Fire Coil 85
(500-2000)
Page 13
proceeding with the installation.
1.
Verify that the appliance is fitted for the proper
type of gas by checking the rating plate. Fire Coil
85 appliances are equipped to operate at elevations
up to 10,000 feet (3050m). Fire Coil 85 appliances
may be adjusted to operate properly at altitudes
above 2500 feet (see
Section 6.6.2
) and the input
will be reduced if the heating value of the gas
supply is below sea level values.
2.
The maximum inlet gas pressure must not exceed
13" W.C (3.2kPa). The minimum inlet gas pressure
is 5" W.C. (1.2kPa).
3.
Refer to
Table 7
, size supply.
4.
Run gas supply line in accordance with all
applicable codes.
5.
Locate and install manual shutoff valves in
accordance with state and local requirements.
6.
A sediment trap must be provided upstream of the
gas controls.
7.
All threaded joints should be coated with piping
compound resistant to action of liquefied
petroleum gas.
8.
The appliance and its individual shutoff valve must
be disconnected from the gas supply piping during
any pressure testing of that system at test pressures
in excess of 1/2 PSIG (3.45kpa).
9.
The unit must be isolated from the gas supply
system by closing its individual manual shutoff
valve during any pressure testing of the gas supply
piping system at test pressures equal to or less than
1/2 PSIG (3.45kpa).
10.
The appliance and its gas connection must be leak
tested before placing it in operation.
11.
Purge all air from gas lines.
WARNING
Do not use open flame to check for leaks. An open
flame could lead to explosion, which could result in
property damage, serious injury or death.
NOTE
: The Fire Coil 85 appliance and all other gas
appliances sharing the gas supply line must be firing at
maximum capacity to properly measure the inlet supply
pressure. The pressure can be measured at the supply
pressure port on the gas valve. Low gas pressure could
be an indication of an undersized gas meter, undersized
gas supply lines and/or an obstructed gas supply line.
SECTION 4A.
Water Connections — Boiler
4A.1 Heating System Piping:
Hot Supply Connections — Boiler
NOTE:
This appliance must be installed in a closed
pressure system with a minimum of 12 psi (82.7kPa)
static pressure at the boiler.
Hot water piping should be supported by suitable
hangers or floor stands. Do not support piping with this
appliance. Due to expansion and contraction of copper
pipe, consideration should be given to the type of
hangers used. Rigid hangers may transmit noise through
the system resulting from the piping sliding in the
hangers. It is recommended that padding be used when
rigid hangers are installed. Maintain 1" clearance to
UNIT
20°F
25°F
30°F
35°F
SIZE
flow
H/L
flow
H/L
flow
H/L
flow
H/L
gpm
feet
gpm
feet
gpm
feet
gpm
feet
500
43
1.7
34
1.1
28
0.9
24
0.7
750
64
3.3
51
2.3
43
1.7
36
1.2
1000
85
5.0
68
3.6
57
3.1
49
2.2
1250
106
8.1
85
6.1
71
4.7
61
3.4
1500
128
10.0
102
7.2
85
5.5
73
4.2
1750
N/R
N/R
119
10.5
99
8.4
85
5.8
2000
N/R
N/R
136
12.5
113
10.4
97
8.3
Metric Equivalent
UNIT
11°C
14°C
17°C
19°C
SIZE
flow
H/L
flow
H/L
flow
H/L
flow
H/L
lpm
m
lpm
m
lpm
m
lpm
m
500
161
0.5
129
0.3
107
0.3
92
0.2
750
241
1.0
193
0.7
161
0.5
138
0.4
1000
321
1.5
257
1.1
214
0.9
184
0.7
1250
401
2.5
322
1.9
269
1.4
231
1.0
1500
483
3.0
386
2.2
322
1.7
276
1.3
1750
N/R
N/R
451
3.2
375
2.6
322
1.8
2000
N/R
N/R
515
3.8
429
3.2
368
2.5
Notes:
gpm = gallons per minute, lpm = liters per minute,
H/L = headloss, ft = headloss in feet, m = headloss in meters.
Maximum temperature rise is 35°F (19°C), as shown. Headloss is
for boiler’s heat exchanger only. N/R = not recommended.
Table 8. Water Flow Requirements — F85H.
Figure 5. Typical Gas Train Configuration.
Содержание Fire Coil 85
Страница 23: ...Fire Coil 85 500 2000 Page 23 Figure 19 Fire Coil 85 500 750 Connection Diagram ...
Страница 24: ...National Combustion Co Inc Page 24 Figure 20 Fire Coil 85 1000 Connection Diagram ...
Страница 25: ...Fire Coil 85 500 2000 Page 25 Figure 21 Fire Coil 85 1250 2000 Connection Diagram ...
Страница 37: ...Fire Coil 85 500 2000 Page 37 Figure 23 Sheet Metal Components ...
Страница 38: ...National Combustion Co Inc Page 38 Figure 24 Internal Components ...