Fire Coil 85
(500-2000)
Page 5
Respect to Return/Supply Header
For the best results, a pump-mounted Fire Coil 85
Boiler should be located within 15 feet (4.6m) of the
supply and return headers. The pump is sized for 30 feet
(9.1m) of piping.
If the appliance must be installed with longer piping
runs, then larger diameter tubing shall be used. Consult
the factory for assistance.
1.8 Locating Appliance for Correct
Horizontal Vent/Ducted Air Distance
from Outside Wall
The forced draft combustion air blower/blowers in
Figure 1. Dimensional Data (standard units).
Air
Vent
Shipping Weight
1
Unit
Conn.
Conn.
Size
A
B
C
D
E
W
V
lbs
kg
500
33¾
85
16¾
43
6½
17
10
25
8
20
6
15
8
20
425
193
750
45¾
116
22¾
53
6½
17
10
25
9½
24
6
15
10
25
505
229
1000
57¾
147
28¾
73
6½
17
10
25
9½
24
8
20
10
25
615
279
1250
68¼
173
34
87
10¼
26
10
25
9
23
8
20
12
30
675
306
1500
78¾
200
39½
100
10¼
26
10
25
9
23
8
20
12
30
760
345
1750
89¼
227
44¾
113
10¼
26
10
25
9
23
8
20
12
30
825
375
2000
99¾
253
49¾
127
10¼
26
10
25
9
23
12
30
14
36
955
434
NOTES:
1. Add 55 lbs (25kg) for pump-mounted units.
Dimensions in inches
cm.
Содержание Fire Coil 85
Страница 23: ...Fire Coil 85 500 2000 Page 23 Figure 19 Fire Coil 85 500 750 Connection Diagram ...
Страница 24: ...National Combustion Co Inc Page 24 Figure 20 Fire Coil 85 1000 Connection Diagram ...
Страница 25: ...Fire Coil 85 500 2000 Page 25 Figure 21 Fire Coil 85 1250 2000 Connection Diagram ...
Страница 37: ...Fire Coil 85 500 2000 Page 37 Figure 23 Sheet Metal Components ...
Страница 38: ...National Combustion Co Inc Page 38 Figure 24 Internal Components ...