EN-3P LIQUID LEVEL CONTROL RELAY

Features

Ÿ

Controls Level of Conductive Liquids in 
Pump Up (Fill) or Pump Down (Drain) 
Applications. 

Ÿ

Adjustable Sensitivity from 5K to 100K 
ohms.

Ÿ

Dual Voltage 120 or 220 VAC Supply.

Ÿ

LED Status Indication.

Ÿ

Protects Pumps from Dry Running.

The  EN-3P  is  a  dual-probe  conductive  liquid  level 
control designed to  monitor the levels of conductive 
liquid  and control the actuation of pumps or valves to 
regulate  levels.    It  is  also  suitable  for  protecting 
submersible pumps against dry running or protecting 
tanks from an"overflow". This device can also be used 
to control dosing of liquids in mixing processes and to 
protect  heating  elements  in  the  event  of  non 
immersion.
The  sensitivity  can  be  adjusted  within  the  range  of 
5KΩ to 100KΩ by rotating the knob on the unit. This 
sets the level at which the relay determines whether 
liquid is present at the probe or not. 
The EN-3P   is dual voltage, it can be used with either 
120 or 220 VAC.

Description

Voltage supply

To use a 220 VAC voltage supply use the terminals T1 
and T3. To use a 120 VAC voltage connect the supply to 
terminals  T1  and  T2.  After  the  supply  voltage  is 
connected the green LINE LED will turn ON. 

Operation

 220 VAC

120 VAC

T1

T1

T3

T3

T2

T2

PUMP DOWN (DRAIN) APPLICATION

The  relay  energizes  when  the  liquid  level  comes  in 
contact  with  the  high  probe  (PH)  and  remains 
energized until the liquid level falls below the lower 
probe  (PL).  To  use  this  application  place  a  wire 
between terminals F/D and PC.

F/D PC

PUMP UP (FILL) APPLICATION

The relay energizes when the liquid level falls below 
the  low  probe  (PL)  and  remains  energized  until  the 
liquid level comes in contact with the high probe (PH).   
To  use  this  application  leave  terminals  F/D  and  PC 
disconnected.

PUMP DRY RUNNING PROTECTION

To protect the pump from dry running use the same 
connections  as  the  Pump  Down  (Drain)  application 
and connect the contact between NO and C in series 
with the pump starter control.

F/D PC

F/D PC

SENSITIVITY ADJUSTMENT

To  adjust  the  sensitivity  within  the  range  of  5KΩ  to 
100KΩ  rotate the knob on the unit. This sets the level 
at  which  the  relay  determines  whether  liquid  is 
present  at  the  probe  or  not.    For  water  it ’s 
recommended to set the sensitivity adjustment at 50K 
Ω .  To set the sensitivity follow the next procedure: 

SENSITIVITY

75K

100K

5K

50K

25K

DANGER!

Potentially hazardous voltages are present. Electrical 

shock can cause death or serious injury.

Installation should be done by qualified personnel 

following all National, State & Local Codes.

BE SURE TO REMOVE ALL POWER SUPPLYING THIS 

EQUIPMENT BEFORE CONNECTING OR 

DISCONNECTING THE WIRING.

READ THE INSTRUCTIONS BEFORE INSTALLING OR 

OPERATING THIS DEVICE.

 KEEP THIS MANUAL FOR FUTURE REFERENCE.

Содержание EN-3P

Страница 1: ...SINCE 1973 www nassarelectronics com The best solutions for automation and protection User Manual LIQUID LEVEL CONTROL RELAY MODEL EN 3P ...

Страница 2: ...OWN DRAIN APPLICATION The relay energizes when the liquid level comes in contact with the high probe PH and remains energized until the liquid level falls below the lower probe PL To use this application place a wire betweenterminalsF DandPC F D PC PUMPUP FILL APPLICATION The relay energizes when the liquid level falls below the low probe PL and remains energized until the liquidlevelcomesincontac...

Страница 3: ... M Contactor Overload Relay OL SW Switch CB Circuit Breaker 1 Use cable size 12 to 18 AWG to wire the probes 2 Use 3 different cable colors to prevent a mixup with the probes 3 The probe PC should not be more than 8 inches below from probe PL 4 The probe PH should not be more than 48 feet higher than probe PL Probe installation PC PL PH PROBE CABLES PROBE CABLE BRONCE PROBE TIGHTENING SCREW HIGH P...

Страница 4: ...ted correctly when following this steps but continues experiencing problems with the operation it indicates that the problem is not the EN 3P The problem comes from the installation or an issue with the wiring common issues with the installation or wiring include A A bad connection with the cables B A bad connection with the probes C The liquid resistance is too high above 100K ohms 3 Connect term...

Страница 5: ...CTION WHETHER BASED IN CONTRACT INFRINGEMENT NEGLIGENCE STRICT LIABILITY OTHER TORT OR OTHERWISE SHALL NASSAR ELECTRONIC S LIABILITY TO THE BUYER AND OR ITS CUSTOMERS EXCEED THE PRICE TO THE BUYER OF THE SPECIFIC GOODS MANUFACTURED OR SERVICES PROVIDED BY NASSAR ELECTRONICS GIVING RISE TO THE CLAIM OR CAUSE OF ACTION THE BUYER AGREES THAT IN NO EVENT SHALL NASSAR ELECTRONIC S LIABILITY TO THE BUYE...

Отзывы: