* Within the appliance enclosure a 6" (152mm) clearance
between the top of the vent pipe and combustible materials is
required. All other clearances within the enclosure, including
where the vent pipe exits the enclosure are subject to 2" (51mm)
to the sides and bottom and 3" (76mm) to the top for horizontal
and 1" (25mm) for vertical.
** See venting section.
2"
51mm
6"
152mm *
0” IF NON-COMBUSTIBLE
FINISHING IS USED SUCH
AS BRICK AND STONE.
3"
76mm
48"
121.9cm
MINIMUM
PLUS RISE**
NON-COMBUSTIBLE
COMBUSTIBLE
COMBUSTIBLE
TOP OF ENCLOSURE
(COMBUSTIBLE)
STEEL STUD
FRAME
26 1/2"
67.3cm
MINIMUM
TOP OF
APPLIANCE
OPENING
25 3/4"
65.4cm
58"
147.3cm
MINIMUM
ENCLOSURE
HEIGHT
2"
51mm
HEAT
SHIELD
SINGLE-SIDED
TOP OF ENCLOSURE
(COMBUSTIBLE)
STEEL STUD
FRAME
MINIMUM
HEIGHT
OF
NON-COMBUSTIBLE
MATERIAL
MINIMUM
ENCLOSURE
HEIGHT
HEAT SHIELD
NON-COMBUSTIBLE
MATERIAL