9.0 maintenance

9.1 

oxygen depletion sensor pilot cleaning

!

WARNING

• 

Turn off the gas and electrical power before servicing the appliance.

• 

Appliance may be hot. Do not service until appliance has cooled.

• 

Do not use abrasive cleaners on glass.

• 

Do not paint the pilot assembly.

This appliance and its venting system should be inspected before use and at least annually by a qualifi ed 
service person. The following suggested checks should be performed by a qualifi ed technician. The appliance 
area must be kept clear and free of combustible materials, gasoline, or other fl ammable vapors and liquids. 
The fl ow of combustion and ventilation air must not be obstructed.

1.

 

In order to properly clean the burner and pilot assembly, remove the logs, rocks and/or glass to ex-
pose both assemblies.

2.

 

Keep the control compartment, media, burner, air shutter opening and the area surrounding the appli-
ance clean by vacuuming or brushing, at least once a year.

3.

 

Check to see that all burner ports are burning. Clean out any of the ports which may not be burning 
or are not burning properly. 

4.

 

Check to see that the pilot fl ame is large enough to engulf the fl ame sensor and/or thermocouple / 
thermopile as well as it reaches the burner.

5.  

If your appliance is equipped with a safety barrier, cleaning may be necessary due to excessive lint / 
dust from carpeting, pets, etc. simply vacuum using the brush attachment.

6.

  

If your appliance is equipped with relief doors, ensure the system performs effectively. Check that the 
gasket is not worn or damaged. Replace if necessary.

7.

 

Replace the cleaned logs, rocks or glass. Failure to properly position the media may cause carboning 
which can be distributed in the surrounding living area, inside the fi rebox and on exterior surfaces sur-
rounding vent termination.

8.

 

Check to see that the main burner ignites completely on all ports when turned on. A 5 to 10 second 
total light-up period is satisfactory. If ignition takes longer, consult your local authorized dealer / dis-
tributor.

9.

 

Visually inspect the appliance for carbon build up. Using a small whisk or brush, brush off the carbon 
and vacuum up or sweep into garbage.

10.

This step is not applicable for Vent Free appliances: 

Check to see that the appliance is vent-

ing correctly. Ensure chimney system is safe and unobstructed. (If for any reason the vent air intake 
system is disassembled, re-install and re-seal per the instructions provided for the initial installation).

Caution: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and 
dangerous operation. Verify proper operation after servicing.

note:

This procedure must be performed by a qualified 
service person!

Inspect the pilot for any visible contamination or 
debris (usually lint, pet hair, spider webs, carpet 
fibre, etc.) and remove.

Disconnect the pilot from the pilot tubing line, 
using the appropriate wrench. Blow out the 
housing in the same direction as the gas flow. 
Re-install the pilot tube, turn on the gas and 
check for leaks.

If this does not improve the performance, replace 
the ODS with an exact replacement. The device is 
tamper resistant with no field serviceable parts.

CORRECT PILOT FLAME 

Flame contacts thermocouple 

correctly (clean, stable and 

pronounced blue flame).

INCORRECT PILOT FLAME

Flame lifts off thermocouple

(flame becomes unstable with 

more of an orange tip).

ADD IMAGE 

HERE

Содержание Knightsbridge VF Series

Страница 1: ...our gas supplier call the re department Installation and service must be performed by a quali ed installer service agency or the supplier This is an unvented gas red heater that uses air oxygen from t...

Страница 2: ...burns A physical barrier is recommended if there are at risk individuals in the house To restrict access to an appliance or stove install an adjustable safety gate to keep toddlers young children and...

Страница 3: ...anemia those under the in uence of alcohol those at high altitudes are more affected by carbon monoxide than others Failure to keep the primary air opening s of the burner s clean may result in sootin...

Страница 4: ...er installation 15 6 1 switch and bracket installation 16 7 0 operation 17 8 0 adjustment 18 8 1 venturi adjustment 18 8 2 ame characteristics 18 9 0 maintenance 19 9 1 oxygen depletion sensor pilot c...

Страница 5: ...nough fresh air is available This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use with other gases unless a certi ed kit is used...

Страница 6: ...equipped with a power cord it must be connected into a properly grounded receptacle The grounding prong must not be removed from the cord plug As long as the required clearance to combustibles is main...

Страница 7: ...ndards ANSI Z21 11 2 2016 VOLUME II for Unvented Room Heaters A 6 B 6 C 2 D 4 L O T N O P O I F F O L IH FLAME ADJUSTMENT NOT FOR USE WITH SOLID FUEL SERIAL NUMBER GVFS60 W385 0184 I ON OFF CONTROL IG...

Страница 8: ...kid SHIPPINGBRACKET 1 5 shipping bracket The top casting is not fastened to the appliance assembly It simply sits on the appliance as a lid For shipping purposes it is held in place by plastic strappi...

Страница 9: ...truction unless provisions are provided for adequate combustion and ventilation air The National Fuel Gas Code ANSI Z223 1 NFPA 54 de nes a con ned space as a space whose volume is less than 50 cubic...

Страница 10: ...Code ANSI Z223 1 NFPA54 or the applicable local code Room Volume Length x Width x Height Max BTU hr Room Volume x 1000 50 If for example The length of the rooms is 5 feet 1 5m The width of Room 1 is 1...

Страница 11: ...res above 1 2 PSIG Valve settings have been factory set do not change Installation and servicing to be done by a quali ed installer Move the appliance into position and secure If equipped with a ex co...

Страница 12: ...a convenient location Route a 2 strand solid core millivolt wire from the valve to the wall switch or millivolt thermostat The recommended maximum lead length depends on wire size WIRE SIZE MAX LENGTH...

Страница 13: ...nt repeat in reverse order and ensure bottom locating tabs engage on either leg SCREEN SECURING BOLTS CAST FRONT SECURING BOLTS BOTTOM LOCATING TABS TOP FRONT RETAINER 5 0 nishing 5 1 cast front remov...

Страница 14: ...place onto the front of the burner Care should be taken to shred the embers into thin small irregular pieces as only the exposed edges of the bre hairs will glow when exposed to direct ame however ca...

Страница 15: ...side of the blower housing F Remove the 2 screws from the side of the blower housing that you want the switch to be located on and re secure the on off switch Because the blower is thermally activated...

Страница 16: ...W415 1966 07 08 19 EN 16 blower installation 6 1 switch and bracket installation 1 3 CONNECT THE TWO WIRES TO THE SWITCH TERMINALS 2...

Страница 17: ...n repeat steps E through I J With pilot lit turn gas knob counter clockwise to the ON position K If equipped with the ame adjustment valve push and turn the knob to high L Turn on all electrical power...

Страница 18: ...re yellow ame but can lead to carbonization Opening the air shutter will cause a more blue ame but can cause ame lifting from the burner ports The ame may not appear yellow immediately allow 15 to 30...

Страница 19: ...d logs rocks or glass Failure to properly position the media may cause carboning which can be distributed in the surrounding living area inside the rebox and on exterior surfaces sur rounding vent ter...

Страница 20: ...replacement parts a photocopy of the original invoice will be required to honour the claim When ordering replacement parts always give the following information Model Serial Number of appliance Instal...

Страница 21: ...urner ori ce 38 NG W456 0053 Burner ori ce 53 P W662 0001 ODS pilot assembly NG W680 0004 Thermopile W725 0030 Valve NG W725 0031 Valve P W662 0005 ODS pilot assembly P W357 0001 Piezo ignitor W135 08...

Страница 22: ...ar exactly as illustrated 2 1 Stocked Stocked F60 Thermostatic remote 6 3 1 2 4 5 6 8 7 8 F45 On off remote 7 GDS819KT Sandstone decorative brick panels ANI K Metallic black andirons 5 W660 0081 Therm...

Страница 23: ...y Use one of the methods described in ANSI Z223 1 NFPA 54 or the applicable local code Flame is impinging on the logs or combustion chamber Check that the logs are correctly positioned Open air shutte...

Страница 24: ...nk Pilot ame is not large enough Supply pressure too low Service or replace Oxygen Depletion Sensor System Correct piping and or regulator to provide correct pressure Ensure adequate supply pressure T...

Страница 25: ...aused by mechanical systems such as exhaust fans furnaces clothes dryers etc Any damages to the appliance combustion chamber heat exchanger plated trim or other components due to water weather damage...

Страница 26: ...W415 1966 07 08 19 EN 26 notes...

Страница 27: ...EN W415 1966 07 08 19 27 notes...

Страница 28: ...TI IN NG G O OV VE ER R 4 40 0 Y YE EA AR RS S A A A O O O O O OF F F F F F H H H H H H H HO O O O O OM M M M ME E E E E C C CO OM M MF F FO OR RT T P PR RO OD DU UC CT TS S 7200 Route Transcanadienne...

Отзывы: