W415-1066 / C / 06.22.12
19
• using the self drilling screws, mount switch and bracket as per diagram.
• Connect harness wiring to switches as per picture:
7/8” diameter hole
supply plenum
high limit 250°f
(121°C)
fan on 165°f
(74°C)
fan off 110°f
(43°C)
8
7
9
CAUTION
the preset values on the fan limit Control must not be Changed from the faCtory
setting.
any adjustment to this Control Will affeCt the operating effiCienCy of the
furnaCe and Will void the Warranty Coverage.
• remove the front upper knockout of the chosen side panel.
furnaCe front
right side panel
aCCess point for
fan limit harness
eXample shoWs right side mounting