EN
W415-2753 / A / 07.20.20
5
installation planning
2.1
installation option 1 - open enclosure (enclosure stops short of the ceiling)
2.2
installation option 2 - front opening
NOT suitable for Dynamic Heat Control™ Plus
ceiling
2-4”
6” min.
DYNAMIC HEAT
CONTROL™ AIR
OUTLET OPEN-
ING IS HOT WHEN
APPLIANCE IS
OPERATING!
Air outlet opening
must
be located out of reach of
the user. Air outlet
must
not be
restricted by furnishings or decor.
RECOMMENDED
Wall mounted
object (picture
frame, appli-
ance, etc.)
Installation Option 1
(open enclosure) leaves a complete air outlet opening above the enclosure to provide the
necessary air circulation path for the
Dynamic Heat Control™
system. This has been found to be well accepted
with respect to fi nal appearance and offer minimal distraction. It also allows for effi cient circulation of air within the
room. This option offers the simplest method for framing and installation. Limit the air outlet opening height to 4”
to reduce the risk of items inadvertly falling into the enclosure.
The air outlet opening must extend around the
entire perimeter, or the entire front face of the enclosure, where the enclosure runs from wall to wall.
MINIMUM AIR OUTLET OPENING DIMENSIONS
EX36
EX42
(Q x R)*
112 sq. in. minimum (Q
must
be 2-3”)
L
72”
* Grills, grates, louvers, or other covers are only permitted if the free area is equal to or greater than
the required minimum opening size listed above.
Wall mounted
object (picture
frame, appli-
ance, etc.)
ceiling
enclosure top
must
be installed
2-3”
0-1.5” Max.
6” min.
Air outlet opening is required to be
centered with the appliance.
ALTERNATIVE
(Q x R)*
DYNAMIC HEAT
CONTROL™ AIR
OUTLET OPEN-
ING IS HOT WHEN
APPLIANCE IS
OPERATING!
Front air outlet opening
must
be located out of reach of the
user. Air outlet
must
not be
restricted by furnishings or
decor.
Installation Option 2
(front opening) requires an air outlet opening to be framed no more than 1.5” below the
enclosure top to avoid trapping heat in the upper areas and the air outlet opening centered on the appliance center.
Minimum air outlet opening dimensions
must
be followed.
Framing the air outlet opening lower will overheat the
appliance, the enclosure, and fi nishing material.
L
2 1/2”
min.
Suitable for Dynamic Heat Control™ Plus