Napoleon BGNV36N Скачать руководство пользователя страница 6

6

W415-0275 / E / 07.13.10

2.3 GENERAL 

INFORMATION

4.1

 The installation must conform with local codes or, in 
absence of local codes, the National Gas and Propane 
Installation Code CSA B149.1 in Canada, or the National 
Fuel Gas Code, ANSI Z223.1 / NFPA 54 in the United 
States. Suitable for mobile home installation if installed in 
accordance with the current standard CAN/CSA Z240MH 
Series, for gas equipped mobile homes, in Canada or 
ANSI Z223.1 and NFPA 54 in the United States.

As long as the required clearance to combustibles is 
maintained, the most desirable and benefi cial location for an appliance is in the center of a building, thereby 
allowing the most effi cient use of the heat created. The location of windows, doors and the traffi c fl ow in the 
room where the appliance is to be located should be considered. If possible, you should choose a location 
where the vent will pass through the house without cutting a fl oor or roof joist.

If the appliance is installed directly on carpeting, vinyl tile or other combustible material other than wood 
fl ooring, the appliance shall be installed on a metal or wood panel extending the full width and depth.

If the optional fan or blower is installed, the junction box must be electrically connected and grounded in 
accordance with local codes, use the current CSA C22.1 Canadian Electrical Code in Canada or the ANSI/
NFPA 70 National Electrical code in the United States.

We suggest that our gas 
hearth products be installed 
and serviced by professionals 
who are certified in the U.S. 
by the National Fireplace 
Institute

® (NFI) as NFI Gas 

Specialists

www.nficertified.org

FOR YOUR SATISFACTION, THIS APPLIANCE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION 
AND QUALITY!    

BGNV36

NG

LP

Altitude (FT)

0-4,500

0-4,500

Max. Input (BTU/HR)

17,000 BTU/hr

17,000 BTU/hr

Min. Inlet Gas Supply Pressure

4.5" Water Column

11" Water Column

Max. Inlet Gas Supply Pressure

7" Water Column

13" Water Column

Manifold Pressure (Under Flow Conditions)

3.5" Water Column

10" Water Column

When the appliance is installed at elevations above 4,500 ft, and in the absence of specifi c recommendations from 
the local authority having jurisdiction, the certifi ed high altitude input rating shall be reduced at the rate of 4% for each 
additional 1,000 ft. 

Expansion / contraction noises during heating up and cooling down cycles are normal and to be expected.

This appliance is approved for bedroom and bed-sitting room installation.

No external electricity (110 volts or 24 volts) is required for the gas system operation.

Содержание BGNV36N

Страница 1: ...Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electri...

Страница 2: ...AT 10 5 0 FRAMING 11 5 1 MINIMUM CLEARANCE TO COMBUSTIBLES 12 5 2 MINIMUM MANTEL CLEARANCES 13 5 3 NAILING TAB INSTALLATION 13 6 0 FINISHING 14 6 1 DOOR INSTALLATION REMOVAL 14 6 2 LOG PLACEMENT 15 6...

Страница 3: ...s see LOUVRE INSTALLATION section Glass see DOOR GLASS REPLACEMENT section Door see DOOR INSTALLATION REMOVAL section Logo see LOGO PLACEMENT section Logs see LOG PLACEMENT section Vent see VENTING se...

Страница 4: ...y safety screen or guard removed for servicing must be replaced prior to operating the appliance This appliance is a vented gas fired appliance Do not burn wood or other materials in this appliance It...

Страница 5: ...HE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RAN OUT WITH THE GLASS DOOR OPENED OR REMOVED PROVIDE ADEQUATE CLEARANCE FOR SERVICING AND OPERATING THE APPLIANCE PROVIDE ADEQUATE VENTILA...

Страница 6: ...ptional fan or blower is installed the junction box must be electrically connected and grounded in accordance with local codes use the current CSA C22 1 Canadian Electrical Code in Canada or the ANSI...

Страница 7: ...ONTACTAVEC LES FLAMMESAUTRE QUE CELUI QUI EST FOURNIAVEC CETAPPAREIL PAR LE FABRICANT THE APPLIANCE MUST BE VENTED USING B VENT SEE OWNERS INSTALLATION MANUAL FOR VENTING SPECIFICS L APPAREIL DOIT EVA...

Страница 8: ...vent and an insulated chase is recommended Under extreme vent configurations allow several minutes 5 15 for the flame to stabilize after ignition Provide a means for visually checking the vent connect...

Страница 9: ...ppliance blower off if so equipped 3 3 2 Set controls to high and light the appliance 3 3 3 Wait 5 minutes Light a match and hold to the front of the draft hood Venting action is satisfactory if smoke...

Страница 10: ...AS SUPPLY PIPE TO PREVENT DAMAGING GAS LINE ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT WITH THE GLASS DOOR OPENED OR REMOVED PURGING OF THE GAS SUPPLY LINE SHOU...

Страница 11: ...E GLASS OR PLASTERS OR ANY COM BINATION THEREOF ARE SUITABLE MATERIALS THAT ARE REPORTED AS PASSING ASTM E 136 STANDARD TEST METHOD FOR BEHAVIOUR OF MATERIALS IN A VERTICAL TUBE FURNACE AT 750 C AND U...

Страница 12: ...12 W415 0275 E 07 13 10 37 3 13 5 36 5 1 MINIMUM CLEARANCE TO COMBUSTIBLES 3 6 1 2 5 2 36 3 4 36 1 2 36 1 2 6 2 MIN 13 1 2 INSIDE CHASE OUTSIDE CHASE 13 1 2...

Страница 13: ...4 2 4 10 8 12 12 8 10 7 MANTLE 6 2 4 6 7 TOP OF UNIT COMBUSTIBLE MATERIALS 2x4 2 4 5 3 NAILING TAB INSTALLATION 55 1A Attach the nailing tabs to the corner posts using the 2 sheet metal screws sup pli...

Страница 14: ...OPENINGS LOUVRES OPENINGS OPERATION OF LOUVRES OR DOORS OR ACCESS FOR SERVICE OBSERVE ALL CLEARANCES WHEN APPLYING COMBUSTIBLE MATERIALS BEFORE DOOR IS REMOVED TURN THE APPLIANCE OFF AND WAIT UNTIL AP...

Страница 15: ...n front of the tabs The tabs maintain an air space between the log and firebox back to facilitate com bustion air flow Ensure that the back of the log rests against the brackets on the back wall of th...

Страница 16: ...ect flame Use only certified glowing embers and PHAZERTM logs available from your Continental dealer 32 1 Randomly place the charcoal embers along the front and sides of the log support tray in a real...

Страница 17: ...United States If the appliance was not previously equipped with a blower Route a grounded 2 wire 60hz power cable to the receptacle junction box At this point it must be strain relieved and insulated...

Страница 18: ...wer is thermally activated when turned on it will automatically start approximately 10 minutes after lighting the appliance and will run for approximately 30 45 minutes after the appliance has been tu...

Страница 19: ...ot burner to be lit until the thermo couple has cooled Allow approximately 60 seconds for the thermocouple to cool When lighting and re lighting the gas knob cannot be turned from pilot to off unless...

Страница 20: ...heck that main burner is operating on HI AFTER TAKING PRESSURE READINGS TIGHTEN SCREWS FIRMLY TO SEAL DO NOT OVER TORQUE LEAK TEST 39 3 P I P I L O T N O L O T HI L O F F O A B PILOT SCREW PILOT BURNE...

Страница 21: ...e area surrounding the logs clean by vacuuming or brushing at least once a year 3 Check to see that all burner ports are burning Clean out any of the ports which may not be burning or are not burning...

Страница 22: ...DO NOT TOUCH GLASS UNTIL COOLED CARE MUST BE TAKEN WHEN REMOVING AND DISPOSING OF ANY BROKEN DOOR GLASS OR DAMAGED COMPONENTS BE SURE TO VACUUM UP ANY BROKEN GLASS FROM INSIDE THE APPLIANCE BEFORE OPE...

Страница 23: ...IN PROPERTY DAMAGE OR PERSONAL INJURY WARNING COMMON COMPONENTS REF NO BGNV36 DESCRIPTION 1 W357 0001 PIEZO IGNITOR 2 W680 0004 THERMOPILE 3 W680 0005 THERMOCOUPLE 4 W010 0764 BURNER 5 W010 0800 NATUR...

Страница 24: ...GOLD PLATED 34 HOISS 3 HERITAGE ORNAMENTAL INSETS SATIN CHROME 35 DK36 R DOOR KIT RECTANGULAR BLACK 36 DK36 A DOOR KIT ARCHED BLACK 36 DK36 AG DOOR KIT ARCHES GOLD PLATED 37 DK36 W DOOR KIT WEBBED BL...

Страница 25: ...25 W415 0275 E 07 13 10 5 3 8 2 14 13 37 36 33 1 28 4 9 15 30 32 6 7 40 18 23 24 22 20 21 19 34 35 38...

Страница 26: ...nob is on HI wall switch thermostat is on Thermostat or switch is defective Connect a jumper wire across the wall switch terminals if main burner lights replace switch thermostat Wall switch wiring is...

Страница 27: ...re increase fresh air supply Carbon is being deposited on glass logs or combustion chamber surfaces Air shutter has become blocked Ensure air shutter opening is free of lint or other obstructions Flam...

Страница 28: ...of NAPOLEON with respect to the NAPOLEON gas heater and any other warranties expressed or implied with respect to this product its components or accessories are excluded NAPOLEON neither assumes nor a...

Страница 29: ...29 W415 0275 E 07 13 10 14 0 SERVICE HISTORY 43 1...

Страница 30: ...30 W415 0275 E 07 13 10 44 1 15 0 NOTES...

Страница 31: ...31 W415 0275 E 07 13 10 44 1...

Страница 32: ...32 W415 0275 E 07 13 10 44 1...

Отзывы: