19
W415-0811 / A / 04.28.10
45"
MINIMUM
2" CLEARANCE TO COMBUSTIBLES
7"
20" MINIMUM INSIDE DIMENSION
7"
Care should be taken to maintain suf
fi
cient clearance for
the vent installation. A horizontal vent installation requires
a minimum height of 45" using
fl
exible vent pipe, to the
underside of the enclosure top including the 2" clearance
to combustibles
4.3 COUNTER TOP / BAR INSTALLATION
When
fi
nishing the appliance, combustible material
may rest directly on the top extension.
NOTE: Maximum weight tolerance is 400 lbs,
provided that it is evenly distributed across the
top extensions of the appliance.
In order to achieve a counter top or bar type
appearance with the minimum height allowed,
framing must be non-combustible and may be done
with metal studding attached to the top extension
sides or the upper frame of the appliance.
* The top extension may be removed if non-
combustible framing is faced with a non-combustible
material placed
fl
ush with the front face of the
appliance and extending from the top of the
appliance. (Example: cement board - not supplied).
Combustible counter / bar tops must maintain a
minimum of 38" from the base of the appliance to the
underside of the top.
NOTE: Wolf Steel trim and/or surround kits
will not totally cover the top extension of the
appliance. In order to obtain a smooth transition
from the trim / surround to the wall, it is
recommended that the top extension be removed
and the appliance be installed following the
above procedure.