background image

W415-1968 / 06.26.19

EN

8

  

general information

1.4 dimensions

19

1

/

4

" 9

5

/

8

"

25

3

/

8

"

15

3

/

4

"

Содержание Arlington GVFS20-1N

Страница 1: ...annot reach your gas supplier call the fire department Installation and service must be performed by a quali ed installer service agency or the supplier This is an unvented gas red heater that uses ai...

Страница 2: ...burns A physical barrier is recommended if there are at risk individuals in the house To restrict access to an appliance or stove install an adjustable safety gate to keep toddlers young children and...

Страница 3: ...ase anemia those under the influence of alcohol those at high altitudes are more affected by carbon monoxide than others Failure to keep the primary air opening s of the burner s clean may result in s...

Страница 4: ...wer installation 15 6 1 blower installation and connection 15 6 2 switch connections 15 7 0 operation 16 8 0 adjustment 17 8 1 venturi adjustment 17 8 2 flame characteristics 17 9 0 maintenance 18 9 1...

Страница 5: ...turn off the appliance if not enough fresh air is available This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use with other gases...

Страница 6: ...e absence of local codes use the current ANSI NFPA 70 National Electric Code In the case where the blower is equipped with a power cord it must be connected into a properly grounded receptacle The gro...

Страница 7: ...EL FUEL S S B SA SA 45 45o o SA SA CL CLEA EAR RA ANC NCE E T TO O C CO OM MB BU USTIB BL LE E M MA ATE TE A A A R RIA IAL LS S 4 2 2 TO 0 BTU h BTU h 18 000 BTU h 18 000 BTU h ANIFOLD PRESSURE IFOLD...

Страница 8: ...W415 1968 06 26 19 EN 8 general information 1 4 dimensions 19 1 4 9 5 8 25 3 8 15 3 4...

Страница 9: ...r uncon ned spaces This appliance shall not be installed in a confined space or unusually tight construction unless provisions are provided for adequate combustion and ventilation air The National Fue...

Страница 10: ...r for proper operation poor fuel combustion can result Carbon Monoxide is a result of poor fuel combustion If additional fresh air is required use one of the methods described in the National Fuel Gas...

Страница 11: ...ures above 1 2 PSIG Valve settings have been factory set do not change Installation and servicing to be done by a quali ed installer Move the appliance into position and secure If equipped with a flex...

Страница 12: ...d in a convenient location Route a 2 strand solid core millivolt wire from the valve to the wall switch or millivolt thermostat The recommended maximum lead length depends on wire size WIRE SIZE MAX L...

Страница 13: ...n order to reinstall the cast front Ensure that the tabs on the underside of the front t behind the front legs 5 2 screen installation and removal A Unscrew the four screws one in each corner securing...

Страница 14: ...only logs specifically approved with this appliance may result in property damage or personal injury Logs must be placed in their exact location in the appliance Do not modify the proper log positions...

Страница 15: ...d in step A 6 0 optional blower installation 2 3 4 4 5 1 7 7 8 9 SEE LOCATION AND CLEARANCES IN INSTRUCTION MANUAL A Cut and remove the tie securing the blower switch wires to the heat shield B Connec...

Страница 16: ...n repeat steps E through I J With pilot lit turn gas knob counter clockwise to the ON position K If equipped with the flame adjustment valve push and turn the knob to high L Turn on all electrical pow...

Страница 17: ...but can lead to carbonization Opening the air shutter will cause a more blue flame but can cause flame lifting from the burner ports The flame may not appear yellow immediately allow 15 to 30 minutes...

Страница 18: ...logs rocks or glass Failure to properly position the media may cause carboning which can be distributed in the surrounding living area inside the firebox and on exterior surfaces sur rounding vent te...

Страница 19: ...screws Care should be taken not to damage the gas pipe When removing and replacing the orifice using a 9 16 socket wrench a 7 8 back up wrench must be used on the manifold located below the housing t...

Страница 20: ...replacement parts a photocopy of the original invoice will be required to honour the claim When ordering replacement parts always give the following information Model Serial Number of appliance Instal...

Страница 21: ...NG Oxygen depletion sensor system P Pilot bracket On off switch Screen Side casting Majolica Brown Top casting Majolica Brown Bracket collector Front casting Metallic Black Yes Yes Yes GZ552 Replaceme...

Страница 22: ...tly as illustrated 1 1 Stocked Stocked 2 3 4 F45 F45 6 F60 F60 6 Thermostatic remote control bulk GS 65KT On off remote On off remote bulk Thermostatic remote control Blower kit GDSLL KT Leg levelling...

Страница 23: ...se one of the methods described in ANSI Z223 1 NFPA 54 or the applicable local code Flame is impinging on the logs or combustion chamber Check that the logs are correctly positioned Open air shutter t...

Страница 24: ...Pilot flame is not large enough Supply pressure too low Service or replace Oxygen Depletion Sensor System Correct piping and or regulator to provide correct pressure Ensure adequate supply pressure T...

Страница 25: ...caused by mechanical systems such as exhaust fans furnaces clothes dryers etc Any damages to the appliance combustion chamber heat exchanger plated trim or other components due to water weather damage...

Страница 26: ...W415 1968 06 26 19 EN 26 14 0 notes...

Страница 27: ...EN W415 1968 06 26 19 27 notes...

Страница 28: ...TI IN NG G O OV VE ER R 4 40 0 Y YE EA AR RS S A A A O O O O O OF F F F F F H H H H H H H HO O O O O OM M M M ME E E E E C C CO OM M MF F FO OR RT T P PR RO OD DU UC CT TS S 7200 Route Transcanadienne...

Отзывы: