18.2 CALCULATING AIR FLOW
18.3 CONTINUOUS FAN OPERATION
H22.2.1
There are circumstances where it may be desirable to know the air
fl
ow delivery through the duct system,
such as when estimating the amount of air
fl
ow available for
air conditioning. This can be done by direct measurement with
electronic or sloped manometers and velometers, or use the
formula in the next column.
H22 2 1
CFM =
Output
1.085 x
∆
T
where:
• CFM is air
fl
ow in cubic feet per minute;
•
∆
T is the temperature rise; and
• O
utput is the furnace output capacity
from the rating plate
.
H22.3.1
When the thermostat continuous fan (G) switch is on without a call for heat or cooling, the indoor fan is
immediately energized. The fan remains energized as long as the call for fan remains without a call for heat or
cooling. This feature allows continuous circulation of air between calls for heating or cooling.
If a callf or heat (W) occurs during continuous fan, the blower will remain energized, the call for heat overrides
the fan.
If a call for cool (Y) occurs simultaneously with the call for fan (G), the call for cool overrides the call for fan.
TABLE 8 - CONTINUOUS
FAN CFM
Input
K/Btu/hr
X13
Motor
HP
Continuous
Fan (CFM)
030-2
1/3
600
040-2
1/3
600
060-3
1/2
600
080-3*
825
080-4**
3/4
850
100-5
865
120-5
1
930
H12.3.5A
NOTE: * 3 TON, ** 4 TON
Содержание 9500-B Series
Страница 27: ...W415 1239 A 03 21 14 27 IOM FIGURE 14A DIRECT VENT TERMINAL CLEARANCES...
Страница 28: ...W415 1239 A 03 21 14 28 IOM IOM FIGURE 14B NON DIRECT VENT TERMINAL CLEARANCES...
Страница 57: ...W415 1239 A 03 21 14 57 IOM 23 0 SERVICE HISTORY 43 1...
Страница 58: ...W415 1239 A 03 21 14 58 IOM IOM 24 0 NOTES 44 1...
Страница 74: ...6 0 NOTES 44 1 W415 1239 A 03 21 14 UM 74...
Страница 75: ...44 1 W415 1239 A 03 21 14 UM 75...