GEM-X255 Programming Instructions
Page 37
WI1092E 10/05
NOTES:
(A) 50ms & 20 ms Loop Response only available for zones 1-8.
(B) 2-wire Smoke Detectors only available for zones 1-8. Refer to Installation Instructions (WI1093) for more details.
If 2-wire Smoke Detectors are selected, then Fire must also be selected.
(C) If Fire Alarm Verification is selected, then Fire must also be selected.
DEFAULTS:
The zone options indicated are automatically set after exiting the Easy Menu Driven Mode.
Priority, Selective Bypass, Alarm Output, Auto Reset, Swinger Shutdown
,
Zone Area 1 and Zone Area 2
are enabled for
the total number of zones entered in
“AREA 1 # ZONES = 08” and “AREA 2 # ZONES = 00”
.
Alarm Telco 1
is enabled for the zones if [YES] is entered for “
REPORT ALL ZONES TO CENTRAL ZONES? Y/N
”.
Entry/Exit 1
and
Chime
are enabled for zone numbers entered in
“EXIT / ENTRY ZONES”
.
Exit/Entry Follower
and
Interior Bypass
are enabled for zone numbers entered in
“INTERIOR ZONES”
.
Fire, Pulse Alarm Output and Fire Verification
is enabled for the zone numbers entered in
“FIRE ZONES”
.
2-Wire Smoke Detector is enabled for zone numbers entered in
“2 WIRE FIRE ZONES”
.
Note:
See “Number of Zones
& Keypads per Area” in Easy
Menu Driven program Mode.
ZONE OPTIONS / ZONES 1-96 (ADDRESS 1200-2386)
ZONE OPTIONS / ZONES 1-96
ZONE OPTIONS:
Select zone options for any zone.
1. Select the desired zone option by entering the option number (1-8) for each selected zone.
2. Enter corresponding option number in address location, in Binary (Bit) Format.
NOTE:
Dark shaded data value box shows option not available. Press
U
or
D
to save
NOTE:
See Direct Address Programming Example on page 15.