NAPCO Security Group
NAPCO Gemini C-Series Control Panel Programming Instructions--Volume 1
Page 18
Programming Instructions, Volume 1
FUNCTION MENU -- FIRE KEYPAD
The GEMC-FK1 Fire keypad Function Menu provides access to a variety of Fire system utility functions. Some func-
tions listed below may or may not appear, depending on the type of Code used to enter the Function Menu (see
"
Security, Program & User Codes
" on page 15). For the Burglary Keypad Function Menu, see page 21.
1.
Unlock a Fire keypad
with either a
Master Security Code
,
Dealer Keypad Pro-
gram Code
or a
Fire User Code
as detailed in
UNLOCKING THE FIRE KEYPAD
on page 17. Press
MENU
.
2.
Scroll forward or backward through the functions
using
NEXT
and
PRIOR
,
respectively.
3.
To select and execute a function
, press
ENTER
.
To return to normal keypad operation, press
RESET
.
Note:
The keypad will
automatically exit the
Function Menu
if no activity is detected for longer than 1
minute.
B
=
A
P
=
B
Q
=
C
G
=
D
ZONE DIRECTORY:
Displays the description of each fire zone in the system.
Press
NEXT
and
PRIOR
to scroll through list of fire zones.. Allows zones to be dis-
abled or enabled by pressing
SILENCE
(
DISABLE
) when viewing the selected
zone.
ZONE DISABLE:
Displays disabled fire zones. Press
NEXT
and
PRIOR
to scroll
through list of disabled zones. Pressing
SILENCE
while viewing selected zone will
un-disable the displayed zone.
OUTPUT DIRECTORY:
Displays a listing of the motherboard outputs and up to 40
external output relays and NAC boards in the system. Press
NEXT
and
PRIOR
to
scroll the zone directory. Allows outputs to be disabled or enabled by pressing the
SILENCE
(
DISABLE
) button when viewing the selected output.
OUTPUT DISABLED:
Displays disabled notification circuits. Press
NEXT
and
PRIOR
to scroll through list of disabled notification circuits. Pressing
SILENCE
(
DISABLE
) while viewing selected notification circuit will un-disable the dis-
played circuit.
LOCK KEYPAD:
Master Security Code or Dealer Keypad Program Code or Fire User Code
required to view this
function
) Immediately locks keypad. Must unlock with key or code to affect system
operation.
DISPLAY FIRE LOG:
Displays all fire events in chronological order; use
NEXT
and
PRIOR
buttons to scroll through the log.
DO FIRE DRILL:
Activates a fire drill by forcing the programmed fire drill zone into
alarm.
DO ONE MAN TEST:
(
Master Security Code or Dealer Keypad Program Code
required to view this function
).
Initiates One Man Test mode (refer to page 14).
TEST COMMUNICATOR:
(
Master Security Code
or
Dealer Keypad Program Code
required to view this func-
tion
). Initiates a test report to the central station.
D I S P L A Y Z O N E
D I R E C T O R Y Y / N
D I S P L A Y Z O N E S
D I S A B L E D Y / N
D I S P L A Y O U T P U T
D I R E C T O R Y Y / N
D I S A B L E
O U T P U T Y / N
L O C K
K E Y P A D Y / N
D I S P L A Y F I R E L O G
Y / N
D O F I R E D R I L L
Y / N
D O O N E M A N T E S T
Y / N
T E S T
C O M M U N I C A T O R Y / N
GEMC-FK1 Fire Keypad