NAPCO Gemini GEM-X255 Скачать руководство пользователя страница 41

L

 NAPCO Security Systems  

X

 

GEM-X255 Installation Instructions 

WI1093C  3/04 

!

 

Page 41

 

exit delay.  If 

D

 is pressed while armed Stay, exit delay will restart and Exit/Entry doors may be opened to permit someone to exit 

(while others remain on premises) without causing an alarm. 
 

Interior (STAY) Bypass

 

(Applies to "GEM-RP" keypads only).  “Interior (Stay) bypass” zones allows freedom of movement inside the premises, while still pro-
viding perimeter partial protection, in ARMED STAY mode by pressing 

E

 before arming.  All zones (including Interior Bypass 

Zones) are all protected with full protection, in ARMED AWAY mode, by arming without the perimeter button.  The next time the zone 
is disarmed, the zone will become a full protected zone. Interior zones can be made to be normally bypassed by enabling "Interior 
Normally Bypassed" and to be unbypassed by pressing 

E

.  The next time the zone is armed, the zone will become a partially 

protected zone.   
 

 

Jumpers

 (Refer to Wiring Diagram for UL configuration.) 

A:  

Cut for dry contacts on the Auxiliary Relay. 

B:  

Cut for dry contacts on the Burglary Relay. 

C:  

Cut for dry contacts on the Reset Relay. 

D:  

Cut if using a PS3002 Power-Supply Module. 

JP5:  

Keypad Configuration Jumper (top-right corner, above micro shield) is installed across top and center pins for normal op-

eration.  When configuring the GEM-RP1CAe2 and GEM-K1CA keypads, move jumper across center and lower pins. 

JP6 & PS:  

For Residential Fire.  See Alarm Outputs. 

JP7:  

2-Wire Fire jumpers.  Select Zones 7 and/or 8 for use as either 2-Wire Fire Zones or Burglary Zones.  Note:  If customizing 

a single-area default program, Zone 8 is configured as a 2-Wire Fire Zone.  In a two-area default program, Zones 7 and 8 
are configured as 2-Wire Fire Zones common to both areas; be sure to move JP7 Zone-7 jumper to the 2-WF position (see 
Wiring Diagram). 

 

Keypad Digital Dialer Test   

A Digital Dialer Test (Central Station Comm. Test) can be initiated from the function menu.  Press 

R

 until “DIGITAL DIALER 

TEST Y/N” is displayed and then press [NEXT/YES] to initiate the transmission of a Test Timer signal.  Note: Test Timer reporting 
codes and

 Report Test Timer on Telco1

 or 

Telco 3

 must be programmed. 

 

Keypad Jumpers:  GEM-RP1CAe2

 (and GEM-K1CA) (Refer to label LA1374 on the circuit board fishpaper for jumper locations and 

a summary of settings) 

JP1:  

Cut to enable Keypad Tamper. 

W1 & W3:  

Cut both to disable touchpad backlighting. 

W2:  

Cut to disable LCD backlighting. 

 

Key Fob Transmitters 
AuxOut Chirp on Key-Fob Arm/Disarm 
Select Bus Output for Key-Fob Chirp 
Disable Aux Out Clear on Disarm 

AuxOut Chirp on Key-Fob Arm/Disarm will cause one 50 mS chirp to sound on arming and two 50mS chirps on disarming.  Use 

the steady output of a siren driver.  Do not use a voice siren driver. 

Burg Output Chirp on Key-Fob Arming will cause one 50 mS chirp to sound on arming and two 50mS chirps on disarming.  Use 

the steady output of a siren driver.  Do not use a voice siren driver. 

Programming a “C as the Key-Fob Aux-1 or Aux-2 option will provide the ability to toggle the Aux. Relay on or off.  If there is an 

Aux. Relay timeout programmed, it will follow this timeout unless toggled off by the key fob.  To provide key-fob-only control, program 
no timeout.  Program Disable AuxOut Clear on Disarm to prevent a disarm from resetting the Aux. Relay. 

Key-fob users can report openings and closings.  Key fobs 1–16 report as Users 180–195, respectively. 

 

Keyfob Zone Assignment 

Keyfobs can be assigned to zones to allow individual reporting.  Each of the 4 keyfob buttons can be assigned to a zone.  For 

example, On button = point 1; Off button = point 2; A1 = point 3; A2 = point 4.  Up to 255 keyfobs can be assigned to the GEM-X255, 
providing multiple wireless panic buttons on a system, each reporting to the Central Station or a pager and/or annunciating on a key-
pad the keyfob zone number with description/location.  To assign a keyfob to a zone, program the keyfob as you would a transmitter, 
entering the keyfob's ID code, check sum and point number at the appropriate zone. 

 

KeyFob or Keypad Garage Door opener control 

The Auxiliary Relay can be programmed to activate for a programmable period of time.  This allows it to be used for access func-

tions such as opening and closing a garage door.  This is achieved through a new KeyFob option, Access control,  by programming  

Access on Aux. Output

 ) into the Aux. 1 or Aux. 2 option locations.  Also program the option Access Control on Auxiliary Output , 

and a time into the Auxiliary Output Access Control duration.  If an Access Control from the keypad is desired, also program a Panel 
Access Code. 

 

KeyFob Disarm Activates Entry Lighting 

Disarming with a KeyFob can activate Remote Relays or X-10 Devices by programming the event EntryRelay Area1, or EntryRe-

lay Area2 on the External Relay Control screen.  This event will cause the programmed outputs to activate on either a KeyFob Disarm 
OR the opening of the Exit Entry zone while the system is armed. 

 

GLOSS

A

RY
 

Содержание Gemini GEM-X255

Страница 1: ...d with K Series keypad GEM K1CA K Series GEM K1CA G E M I N I SYSTEM READY 01 01 03 12 00 AM ARMED COMPUTERIZED SECURITY SYSTEM STATUS R 1 2 3 B 4 5 6 C 7 8 9 0 U NEXT YES P PRIOR NO Q AREA G Classic...

Страница 2: ...ting of alarms over a TCP IP based Intranet or Internet net work Page 30 new Keypad messages System Troubles added to accommodate the new ACM and NetLink systems THIS MANUAL INCLUDES FEATURES WHICH AR...

Страница 3: ...ton operate identically in Program Mode for both keypads The D button and the U button operate identically in Program Mode for both keypads The button and the button operate identically in Program Mod...

Страница 4: ...ation 16 4 Wire Smoke Detectors 17 2 Wire Smoke Detectors 17 Telephone Lines 18 KEYPAD CONFIGURATION MODE 19 Keypad Installation 19 Configuring the Keypads 19 BASIC OPERATION 22 User Codes Zone Descri...

Страница 5: ...ible computer with NAPCO s PCD Windows Quickloader software and PCI2000 computer interface Or the panel may be programmed using the keypad in its secondary mode of operation In keypad programming mode...

Страница 6: ...m 2 SIA 4 3 1 4 2 Express and Point ID Rotary dial TouchToneTM only and TouchToneTM with Rotary backup Three 20 digit telephone numbers Backup Reporting Double Reporting Split Reporting 195 User Codes...

Страница 7: ...t including PGM output PGM Output 5mA 12V Special Application Keypad Current GEM RP1CAe2 GEM K1CA 100mA 35mA if backlighting is disabled cut W1 W2 W3 PGM Output 5mA 12V Special Application Maximum Num...

Страница 8: ...1000 Relay Board single output RBAT4 Rechargeable Battery 12VDC 4AH RBAT6 Rechargeable Battery 12VDC 6AH RBAT7 Rechargeable Battery 12 VDC 7AH RBATH1 Dual Battery Harness RM3008 Relay Module in enclos...

Страница 9: ...riority Do not program any zones for Keyswitch Arming System must be serviced at least once every year Residential Fire and Combination Residential Fire Burglary must program Residential Fire Keypad E...

Страница 10: ...for the machine screws it may be discarded after use Keypad A keypad should be located near each exit entry door The keypad features a handy pull up reference label Before mounting the keypad onto th...

Страница 11: ...her than those required such as the dining room bed rooms utility room furnace room and hallways Heat detectors rather than smoke detectors are recommended in kitchens at tics and garages due to condi...

Страница 12: ...acing to the Ademco 7720 Long Range Wireless System The RM3008 may be used to interface the GEM X255M control panel to the Ademco 7720 transmitter in order to meet UL Central Station Grade A or Grade...

Страница 13: ...mitter to be tested by faulting the zone The transmitter signal strength can be displayed using the DISPLAY RF XMITTER STAT function Enter a Level 3 User Code or enter the Dealer Code press the A butt...

Страница 14: ...1 2 BATTERY The RED and BLACK flying leads must be connected to a 12VDC 4 6 or 7 AH Rechargeable Battery to serve as backup power in the event of AC Power Failure NOTE To calculate the available stan...

Страница 15: ...cable run from the panel to the farthest keypad daisy chained or home run is less than 1000 feet The maximum distance for seven keypads is 300 feet using 22 AWG wire NOTE When running keypad wire avoi...

Страница 16: ...nnect the device controlled by the programmable output between terminal 15 and terminal 14 15 RESET OUTPUT EXPANDED ZONE CONFIGURATION The GEM X255 Control Panel may be expanded up to 255 zones This m...

Страница 17: ...cation is de sired to reset the smoke detectors select this option for the desired fire zone Do not use in UL installations See page 9 NOTE Do not program Fire Alarm Verification in California 2 W IR...

Страница 18: ...RATION Where more than two 2 wire smoke detector zones are required select any of Zones 1 6 for 2 wire fire as follows 1 Program the selected zone s 1 6 for 2 Wire Smoke Detectors and Fire 2 Cut the l...

Страница 19: ...he GEM RP1CAe2 GEM K1CA Configuration Mode 1 Move jumper JP1 located at the upper center of the control panel board from Pins 1 2 top two to Pins 2 3 bottom two NOTE See the Wiring Diagram 2 After abo...

Страница 20: ...r see Keypad Programming Workbook similar to its keypad address If no other EZMs are to be used designate the keypad as Group 01 at the EZM ADDRESS 00 display In multiple EZM systems enter an assigned...

Страница 21: ...NAPCO Security Systems Inc 333 Bayview Avenue Amityville New York 11701 For Sales and Repairs call toll free 800 645 9445 For direct line to Technical Service call toll free 800 645 9440 Internet http...

Страница 22: ...that is easily activated when needed and dormant at other times Intended for the occasional or temporary user repairman etc who would otherwise be denied access to the premises It may then be used to...

Страница 23: ...er to the user to return to the keypad and disarm 2 GEM RP1CAe2 GEM K1CA keypads only An S in the display e g EXIT TIME XXX S will appear as a re minder that the system is being armed with the Service...

Страница 24: ...can press the R or A button until TO DE LAY AUTO ARM PRESS 1 4 N is displayed Enter the number of hours to delay arming followed by the U or D button If DELAY AUTO ARM Y N is displayed press the NEXT...

Страница 25: ...the zone number The zone will be unbypassed the next time the system is disarmed Security Bypass Zones programmed for Selective Bypass may be removed from the system prior to arming as follows 1 Ente...

Страница 26: ...r s authority level will be suppressed and will not display 2 Press the PRIOR NO button to skip a function press the NEXT YES button to execute it DISPLAY ZN FAULTS Press the YES button to identify al...

Страница 27: ...then disarm GUARD TOUR ON OFF A Guard Tour schedule is programmable through Napco s PCD Windows Quickloader software Guard Tour is toggled on and off by pressing P When Guard Tour is toggled on the pr...

Страница 28: ...s events scroll back using the PRIOR button DISPLAY FIRE LOG Displays most recent fire events Line 1 displays event and date Line 2 displays time area and zone To check previous fire events scroll bac...

Страница 29: ...the YES button to check the status of up to 255 transmitters The keypad will display zone number Z01 Z96 transmitter ID code number 6 digits point number PT1 PT4 9 for unsupervised status of transmit...

Страница 30: ...EYPAD ACM TAMPER Keypad or ACM cover opened NNN is keypad number address E12 NN BURG EZM TRBL Expansion zone module failure NN module number E13 NN BURG EZM TAMPER EZM module cover re moved NN module...

Страница 31: ...lid time to be entered into the Aux Output Access Control in the Time Selection Screen If Access Control on Aux Output is selected entering the Access Code see User Code Programming in Easy Menu Drive...

Страница 32: ...the system The Ambush Zone will automatically report when programmed to report an alarm Ambush Type 1 a 2 digit prefix code this type must not be used in a SIA CP 01 compliant system Enable as follows...

Страница 33: ...on schedule and a rearm delay is programmed see Time Selection the panel will automatically rearm after the delay if no activity has been detected Auto Output Test Upon Arming Required for UL Mercant...

Страница 34: ...ing machine The answering machine will pick up on its programmed number of rings as usual Note The number of rings programmed into the panel must exceed that of the answering machine Disable Answering...

Страница 35: ...me transmission would occur for Zone 15 25 35 etc Cold Start Caution Erases the entire program codes schedules etc leaving the panel as it came right out of the box Access Location 4093 then press the...

Страница 36: ...adionics Fast Radionics BFSK Universal High Speed Radionics Modem 2 Osborne Hoffman Quickalert Formats Ademco Slow Silent Knight Slow Silent Knight Fast Sescoa Vertex DCI Franklin Slow Franklin Fast S...

Страница 37: ...n this case the report code received is not indicative of a system trouble but is an indication of a successful transmission Should the transmis sion fail the keypad will display E03 00 COMM FAIL This...

Страница 38: ...ay E Lugs E3 E4 E5 E7 E9 E10 E14 E18 E19 E22 E9 See Fire Lug E10 See Burglary Lug E19 See Veri Phone Silence All Outputs During Audio Session E22 Common terminal for Reset Relay Use Napco Part No WL1...

Страница 39: ...el to monitor the phone line A failure will display as E08 00 TELCO LINE1 FAIL Program this system trouble to activate the Burglary Output If a time is entered in Telco Line Test Delay the line will b...

Страница 40: ...A fire condition that has not been restored will cause the zone number and description to scroll To reset acknowledge the con dition enter a valid code then press the C button If Keypad Fire is progr...

Страница 41: ...hpad backlighting W2 Cut to disable LCD backlighting Key Fob Transmitters AuxOut Chirp on Key Fob Arm Disarm Select Bus Output for Key Fob Chirp Disable Aux Out Clear on Disarm AuxOut Chirp on Key Fob...

Страница 42: ...n a system where openings are on 24 hour protection zones and access is only allowed if the zone is Bypassed by an authorized User and then Unbypassed when done A typical application would be a wareho...

Страница 43: ...e Direct Address Program Mode Advance to the PROG screen then change the 6 digit code as required The Download Security Code is the six digit code required to establish connection to the PCD Windows S...

Страница 44: ...ore dialing rather than look for a nonstandard dial tone Contact the telephone equipment supplier to find out how long a delay is required before dialing Select Pre Dial Delay by pro gramming one D fo...

Страница 45: ...ne Remote Panic See Panic Zone Report Digital Dialer Exit Error Recent Closing A Recent Closing transmission is sent if an alarm occurs within two 2 minutes after the expiration of the Exit Time If th...

Страница 46: ...in the programmed Sensor Watch time a system trouble will result and E22 NN PIR SENSOR TRBL will be displayed at the key pad where NN are the zone number s Select the RESET SENSOR MSG function to rese...

Страница 47: ...ter Ringback When a closing report is successfully received the central station will acknowledge by returning a kissoff signal When the kis soff is received by the communicator a 2 second ringback ton...

Страница 48: ...anel leaves the factory with no zones programmed for Auto Reset If Enable CP 01 Features is selected in the Easy Programming menu all non fire zones will not be programmed for Auto Reset System Troubl...

Страница 49: ...is programmed for Double or Split Reporting Private telephone systems may require a Dial Tone Detection E or Pre Dial Delay D followed by an access number to obtain an outside line See Access Number f...

Страница 50: ...if both are selected Note that if Backup Reporting is also selected the communicator will alternate between TouchTone and rotary dial to reach Telephone 1 then Telephone 2 See Backup Report on Telco...

Страница 51: ...rammable each with its dedicated Authority Level and Access Byte The Authority Level comprises an Option Code Refer to Programming Manual WI1092 for descriptions of levels and options If reporting to...

Страница 52: ...tire Group If Enable Local Alarm on First ZoneAND Trip Address 2419 is programmed a trip on any Zone of the Group will cause an alarm output and alarm display at the keypad there will be no communicat...

Страница 53: ...mum required capacity 1 STANDBY CURRENT STANDBY CURRENT Amps DEVICE QTY EACH TOTAL GEM X255 1 X 0 120 GEM EZM4 8 X 0 050 GEM EZM8 X 0 050 GEM RP1CAe2 GEM K1CA X 0 100 GEM RP1CAe2 GEM K1CA 1 X 0 035 RM...

Страница 54: ...cessary use this wiring legend to relocate wire leads to their proper terminals Enter wire identification number or color code in WIRE NUMBER column and enter wire function in DESCRIPTION col umn opti...

Страница 55: ...DOWNLOAD 3 DISPLAY RF XMITTER STAT 3 N RELAY CONTROL 1 2 3 O USER MODE NOTES A Displays only with faulted Zones present B Displays only with bypassed Zones present C Displays only with Help Phones in...

Страница 56: ...EST DISPLAY PHONE S DISPLAY SYS TRBL DISPLAY FIRE ALARM DISPLAY FIRE TRBL DISPLAY OP CL ACTIVATE OVERVIEW ACTIVATE CHIME ACTIVATE WATCH ACTIVATE GUARD TOUR RESET SYSTEM TRBL RESET SENSOR MSG START EXI...

Страница 57: ...S ENTER ZONE 00 E AUX OUTPUT ZONES ENTER ZONE 00 E SENSOR WATCH ZNS ENTER ZONE 00 E KP SNDR ALRM ZNS ENTER ZONE 00 E AUTO BYP RENT ZN ENTER ZONE 00 E ENABLE NO EOLR ZONES Y N E ENABLE TELCO LINE TEST...

Страница 58: ...X GEM X255 Installation Instructions L NAPCO Security Systems WI1093C 3 04 Page 58 NOTES...

Страница 59: ...ins 1 2 SYSTEM READY Move Jumper JP5 from Pins 1 2 to Pins 2 3 Wait about 15 seconds 01 OUT OF SYSTEM JP5 is located at the top right corner of the circuit board If a Compatibility Number other than 0...

Страница 60: ...X GEM X255 Installation Instructions L NAPCO Security Systems WI1093C 3 04 Page 60 GEM X255 WIRING DIAGRAM...

Страница 61: ...minimum default is 30 seconds If an attempt is made to change the Entry Delay time to less than 30 seconds the time will be entered as 30 seconds The maximum programmable time is 255 seconds The pane...

Страница 62: ...lt Find can not be initiated from an armed panel and all digital dialer reporting in same area is inhibited while in Fault Find Fault Find Central Station Reporting Code is located at address 0887 Key...

Страница 63: ...bled 4 All zones are programmed with report codes and as burg fire alarm types depending on whether they were selected as fire zones Zones not selected as fire are burg type 5 The reporting format is...

Страница 64: ...onnect the equipment Users should ensure for their own protection that the electrical ground connections of the power utility telephone lines and internal metallic water pipe system if present are con...

Страница 65: ...ssary the user should consult the dealer or an experienced radio television technician for additional suggestions The user may find the following booklet prepared by the Federal Communications Commiss...

Страница 66: ...X GEM X255 Installation Instructions L NAPCO Security Systems WI1093C 3 04 Page 66 Notes...

Страница 67: ...L NAPCO Security Systems X GEM X255 Installation Instructions WI1093C 3 04 Page 67 Notes...

Страница 68: ...her assumes nor au thorizes any other person purporting to act on its behalf to modify to change or to assume for it any other warranty or liability concerning its products In no event shall NAPCO be...

Отзывы: