 NAPCO Security Systems  

X

 

GEM-X255 Installation Instructions 

WI1093C  3/04 

!

 

Page 33

 

 

Anti-Jam Time 

If the communicator does not detect a dial tone within 12 seconds, the Anti-Jam feature will be activated.  That is, the communi-

cator will go off line for a 16-second anti-jam interval in order to free the telephone circuit from an incoming call, then make another 
12-second attempt at dial-tone detection.  If still unsuccessful, the communicator will again go off line for 16 seconds, then proceed to 
dial anyway. 

 

Areas 
Zone Area 1-Zone Area 8 
Priority Area Arming 

Although the default program will automatically set up Zones 1 through 8 for Zone Area 1, the panel may be partitioned into eight 

areas.  Each zone must be assigned to at least one area.  At least one zone must be assigned to Area 1.  If a burglary zone is se-
lected for both areas, that common zone will not arm until both areas are armed.  If any zone disarms, the common zone will disarm. 

In a multiple-area system, be sure to also program: 

Enable User Code by Area (see User Codes/Authority Levels); 

Keypad Area Assignments 

Bell Control (determines which bells an area may silence); 

Subscriber Opening/Closing ID Numbers and Event ID Numbers (if reporting); 

System Trouble Subscriber ID Number 

If Priority Area Arming is selected, the Priority Area must be armed before the Arming Area can be armed. 

 

Arm Lug (Lug E4) 

Lug E4 (ARM) will go to approximately 1Vdc when all areas in the system are armed.  This lug may be used for auxiliary equip-

ment.  (For use, refer to the instructions furnished with the device.) 

 

Auto-Bypass 

(Do not program for UL installations.) 

Auto-Bypass Re-entry

 

Zones programmed for Auto-Bypass will be bypassed (automatically removed) if in trouble when arming.  A momentary beep will 

sound at the keypad to warn that the system has been armed without the protection of the auto-bypassed zone.  (Note that the exit/
entry door must be closed before arming, otherwise the Exit/Entry Zone will be auto-bypassed).  

Note:  

A zone in trouble that is not 

programmed for Auto-Bypass will cause an alarm on arming after a 10-second arming delay. 

If Auto-Bypass Re-entry is selected, securing a zone that is programmed for Auto-Bypass, while armed, will cause that zone to 

re-enter the system in an armed state. 

 

Auto Disarm / Rearm Delay 

If the panel was auto-disarmed on schedule and a rearm delay is programmed (see Time Selection), the panel will automatically 

rearm after the delay if no activity has been detected. 

 

Auto Output Test Upon Arming

 (Required for UL Mercantile installations.) 

This will activate the Burglary Output briefly 10 seconds after the area is armed.  If the alarm does not sound, the device may be 

defective. 

 

Automatic Interior Bypass / Easy Exit

  

Convert from Away to Stay based on no egress through exit door.  Default is enabled.  This feature will cause all Interior-1 Zones 

to automatically be bypassed if the Exit/Entry doors are not opened during the exit-delay period.  If the 

U

 button is pressed while 

armed, exit delay will restart and the Exit/Entry doors may be opened to permit someone to exit (while others remain on the premises) 
without causing an alarm.  This feature must be enabled in CP-01 installations.  This feature is enabled in the factory program and it 
is also enabled when "Enable CP-01 Features" is selected in the Easy Program Menu.   

 

AUXOUT CHIRP ON KEYFOB ARM/DISARM  

If enabled, when arming with a keyfob, the PGM2 output chirps.  See also 

Select Burg Output for Keyfob Chirp

.  This feature 

will cause a 1-chirp indication on arming and 2-chirp indication on disarming.  Connect steady input (burglary) of external siren driver 
to the panel’s Auxiliary Alarm Output.  

Note:  

Do not use an external voice siren driver.

 

 

Auto-Reset

 

Auto-Reset After Burg Output Timeout 

If a zone detects an alarm condition and is selected for Auto-Reset, it will automatically rearm itself as soon as the alarm condi-

tion is cleared.  Auto-Reset may be delayed to occur after the Burglary Output timeout period by selecting Auto-Reset After Burglary 
Output Timeout and Auto-Reset.  Zones that are not programmed for Auto-Reset will not be capable of signaling another alarm until 
(a) the cause of the alarm has been corrected and (b) the control panel is disarmed.  Also see Swinger Shutdown. 

 

Auxiliary Relay   See Alarm Outputs 

 

Backup Reporting Telco #1 / Telco #2 

If Backup Reporting is selected and the communicator does not reach the first telephone number after two attempts, seven at-

tempts will be made to reach the second telephone number.  Enter Subscriber Identification Numbers for Telephone 2 and other infor-
mation required for Telephone 2.  Also program Backup Report on Telco 2.  Any zone programmed to report to Telco 1 will backup 
report to Telco 2.  

Note:  

Subscriber Identification Numbers for both Telephones 1 and 2 must be entered, even if they are the same 

 
 
 

GLOSS

A

RY
 

Содержание Gemini GEM-X255

Страница 1: ...d with K Series keypad GEM K1CA K Series GEM K1CA G E M I N I SYSTEM READY 01 01 03 12 00 AM ARMED COMPUTERIZED SECURITY SYSTEM STATUS R 1 2 3 B 4 5 6 C 7 8 9 0 U NEXT YES P PRIOR NO Q AREA G Classic...

Страница 2: ...ting of alarms over a TCP IP based Intranet or Internet net work Page 30 new Keypad messages System Troubles added to accommodate the new ACM and NetLink systems THIS MANUAL INCLUDES FEATURES WHICH AR...

Страница 3: ...ton operate identically in Program Mode for both keypads The D button and the U button operate identically in Program Mode for both keypads The button and the button operate identically in Program Mod...

Страница 4: ...ation 16 4 Wire Smoke Detectors 17 2 Wire Smoke Detectors 17 Telephone Lines 18 KEYPAD CONFIGURATION MODE 19 Keypad Installation 19 Configuring the Keypads 19 BASIC OPERATION 22 User Codes Zone Descri...

Страница 5: ...ible computer with NAPCO s PCD Windows Quickloader software and PCI2000 computer interface Or the panel may be programmed using the keypad in its secondary mode of operation In keypad programming mode...

Страница 6: ...m 2 SIA 4 3 1 4 2 Express and Point ID Rotary dial TouchToneTM only and TouchToneTM with Rotary backup Three 20 digit telephone numbers Backup Reporting Double Reporting Split Reporting 195 User Codes...

Страница 7: ...t including PGM output PGM Output 5mA 12V Special Application Keypad Current GEM RP1CAe2 GEM K1CA 100mA 35mA if backlighting is disabled cut W1 W2 W3 PGM Output 5mA 12V Special Application Maximum Num...

Страница 8: ...1000 Relay Board single output RBAT4 Rechargeable Battery 12VDC 4AH RBAT6 Rechargeable Battery 12VDC 6AH RBAT7 Rechargeable Battery 12 VDC 7AH RBATH1 Dual Battery Harness RM3008 Relay Module in enclos...

Страница 9: ...riority Do not program any zones for Keyswitch Arming System must be serviced at least once every year Residential Fire and Combination Residential Fire Burglary must program Residential Fire Keypad E...

Страница 10: ...for the machine screws it may be discarded after use Keypad A keypad should be located near each exit entry door The keypad features a handy pull up reference label Before mounting the keypad onto th...

Страница 11: ...her than those required such as the dining room bed rooms utility room furnace room and hallways Heat detectors rather than smoke detectors are recommended in kitchens at tics and garages due to condi...

Страница 12: ...acing to the Ademco 7720 Long Range Wireless System The RM3008 may be used to interface the GEM X255M control panel to the Ademco 7720 transmitter in order to meet UL Central Station Grade A or Grade...

Страница 13: ...mitter to be tested by faulting the zone The transmitter signal strength can be displayed using the DISPLAY RF XMITTER STAT function Enter a Level 3 User Code or enter the Dealer Code press the A butt...

Страница 14: ...1 2 BATTERY The RED and BLACK flying leads must be connected to a 12VDC 4 6 or 7 AH Rechargeable Battery to serve as backup power in the event of AC Power Failure NOTE To calculate the available stan...

Страница 15: ...cable run from the panel to the farthest keypad daisy chained or home run is less than 1000 feet The maximum distance for seven keypads is 300 feet using 22 AWG wire NOTE When running keypad wire avoi...

Страница 16: ...nnect the device controlled by the programmable output between terminal 15 and terminal 14 15 RESET OUTPUT EXPANDED ZONE CONFIGURATION The GEM X255 Control Panel may be expanded up to 255 zones This m...

Страница 17: ...cation is de sired to reset the smoke detectors select this option for the desired fire zone Do not use in UL installations See page 9 NOTE Do not program Fire Alarm Verification in California 2 W IR...

Страница 18: ...RATION Where more than two 2 wire smoke detector zones are required select any of Zones 1 6 for 2 wire fire as follows 1 Program the selected zone s 1 6 for 2 Wire Smoke Detectors and Fire 2 Cut the l...

Страница 19: ...he GEM RP1CAe2 GEM K1CA Configuration Mode 1 Move jumper JP1 located at the upper center of the control panel board from Pins 1 2 top two to Pins 2 3 bottom two NOTE See the Wiring Diagram 2 After abo...

Страница 20: ...r see Keypad Programming Workbook similar to its keypad address If no other EZMs are to be used designate the keypad as Group 01 at the EZM ADDRESS 00 display In multiple EZM systems enter an assigned...

Страница 21: ...NAPCO Security Systems Inc 333 Bayview Avenue Amityville New York 11701 For Sales and Repairs call toll free 800 645 9445 For direct line to Technical Service call toll free 800 645 9440 Internet http...

Страница 22: ...that is easily activated when needed and dormant at other times Intended for the occasional or temporary user repairman etc who would otherwise be denied access to the premises It may then be used to...

Страница 23: ...er to the user to return to the keypad and disarm 2 GEM RP1CAe2 GEM K1CA keypads only An S in the display e g EXIT TIME XXX S will appear as a re minder that the system is being armed with the Service...

Страница 24: ...can press the R or A button until TO DE LAY AUTO ARM PRESS 1 4 N is displayed Enter the number of hours to delay arming followed by the U or D button If DELAY AUTO ARM Y N is displayed press the NEXT...

Страница 25: ...the zone number The zone will be unbypassed the next time the system is disarmed Security Bypass Zones programmed for Selective Bypass may be removed from the system prior to arming as follows 1 Ente...

Страница 26: ...r s authority level will be suppressed and will not display 2 Press the PRIOR NO button to skip a function press the NEXT YES button to execute it DISPLAY ZN FAULTS Press the YES button to identify al...

Страница 27: ...then disarm GUARD TOUR ON OFF A Guard Tour schedule is programmable through Napco s PCD Windows Quickloader software Guard Tour is toggled on and off by pressing P When Guard Tour is toggled on the pr...

Страница 28: ...s events scroll back using the PRIOR button DISPLAY FIRE LOG Displays most recent fire events Line 1 displays event and date Line 2 displays time area and zone To check previous fire events scroll bac...

Страница 29: ...the YES button to check the status of up to 255 transmitters The keypad will display zone number Z01 Z96 transmitter ID code number 6 digits point number PT1 PT4 9 for unsupervised status of transmit...

Страница 30: ...EYPAD ACM TAMPER Keypad or ACM cover opened NNN is keypad number address E12 NN BURG EZM TRBL Expansion zone module failure NN module number E13 NN BURG EZM TAMPER EZM module cover re moved NN module...

Страница 31: ...lid time to be entered into the Aux Output Access Control in the Time Selection Screen If Access Control on Aux Output is selected entering the Access Code see User Code Programming in Easy Menu Drive...

Страница 32: ...the system The Ambush Zone will automatically report when programmed to report an alarm Ambush Type 1 a 2 digit prefix code this type must not be used in a SIA CP 01 compliant system Enable as follows...

Страница 33: ...on schedule and a rearm delay is programmed see Time Selection the panel will automatically rearm after the delay if no activity has been detected Auto Output Test Upon Arming Required for UL Mercant...

Страница 34: ...ing machine The answering machine will pick up on its programmed number of rings as usual Note The number of rings programmed into the panel must exceed that of the answering machine Disable Answering...

Страница 35: ...me transmission would occur for Zone 15 25 35 etc Cold Start Caution Erases the entire program codes schedules etc leaving the panel as it came right out of the box Access Location 4093 then press the...

Страница 36: ...adionics Fast Radionics BFSK Universal High Speed Radionics Modem 2 Osborne Hoffman Quickalert Formats Ademco Slow Silent Knight Slow Silent Knight Fast Sescoa Vertex DCI Franklin Slow Franklin Fast S...

Страница 37: ...n this case the report code received is not indicative of a system trouble but is an indication of a successful transmission Should the transmis sion fail the keypad will display E03 00 COMM FAIL This...

Страница 38: ...ay E Lugs E3 E4 E5 E7 E9 E10 E14 E18 E19 E22 E9 See Fire Lug E10 See Burglary Lug E19 See Veri Phone Silence All Outputs During Audio Session E22 Common terminal for Reset Relay Use Napco Part No WL1...

Страница 39: ...el to monitor the phone line A failure will display as E08 00 TELCO LINE1 FAIL Program this system trouble to activate the Burglary Output If a time is entered in Telco Line Test Delay the line will b...

Страница 40: ...A fire condition that has not been restored will cause the zone number and description to scroll To reset acknowledge the con dition enter a valid code then press the C button If Keypad Fire is progr...

Страница 41: ...hpad backlighting W2 Cut to disable LCD backlighting Key Fob Transmitters AuxOut Chirp on Key Fob Arm Disarm Select Bus Output for Key Fob Chirp Disable Aux Out Clear on Disarm AuxOut Chirp on Key Fob...

Страница 42: ...n a system where openings are on 24 hour protection zones and access is only allowed if the zone is Bypassed by an authorized User and then Unbypassed when done A typical application would be a wareho...

Страница 43: ...e Direct Address Program Mode Advance to the PROG screen then change the 6 digit code as required The Download Security Code is the six digit code required to establish connection to the PCD Windows S...

Страница 44: ...ore dialing rather than look for a nonstandard dial tone Contact the telephone equipment supplier to find out how long a delay is required before dialing Select Pre Dial Delay by pro gramming one D fo...

Страница 45: ...ne Remote Panic See Panic Zone Report Digital Dialer Exit Error Recent Closing A Recent Closing transmission is sent if an alarm occurs within two 2 minutes after the expiration of the Exit Time If th...

Страница 46: ...in the programmed Sensor Watch time a system trouble will result and E22 NN PIR SENSOR TRBL will be displayed at the key pad where NN are the zone number s Select the RESET SENSOR MSG function to rese...

Страница 47: ...ter Ringback When a closing report is successfully received the central station will acknowledge by returning a kissoff signal When the kis soff is received by the communicator a 2 second ringback ton...

Страница 48: ...anel leaves the factory with no zones programmed for Auto Reset If Enable CP 01 Features is selected in the Easy Programming menu all non fire zones will not be programmed for Auto Reset System Troubl...

Страница 49: ...is programmed for Double or Split Reporting Private telephone systems may require a Dial Tone Detection E or Pre Dial Delay D followed by an access number to obtain an outside line See Access Number f...

Страница 50: ...if both are selected Note that if Backup Reporting is also selected the communicator will alternate between TouchTone and rotary dial to reach Telephone 1 then Telephone 2 See Backup Report on Telco...

Страница 51: ...rammable each with its dedicated Authority Level and Access Byte The Authority Level comprises an Option Code Refer to Programming Manual WI1092 for descriptions of levels and options If reporting to...

Страница 52: ...tire Group If Enable Local Alarm on First ZoneAND Trip Address 2419 is programmed a trip on any Zone of the Group will cause an alarm output and alarm display at the keypad there will be no communicat...

Страница 53: ...mum required capacity 1 STANDBY CURRENT STANDBY CURRENT Amps DEVICE QTY EACH TOTAL GEM X255 1 X 0 120 GEM EZM4 8 X 0 050 GEM EZM8 X 0 050 GEM RP1CAe2 GEM K1CA X 0 100 GEM RP1CAe2 GEM K1CA 1 X 0 035 RM...

Страница 54: ...cessary use this wiring legend to relocate wire leads to their proper terminals Enter wire identification number or color code in WIRE NUMBER column and enter wire function in DESCRIPTION col umn opti...

Страница 55: ...DOWNLOAD 3 DISPLAY RF XMITTER STAT 3 N RELAY CONTROL 1 2 3 O USER MODE NOTES A Displays only with faulted Zones present B Displays only with bypassed Zones present C Displays only with Help Phones in...

Страница 56: ...EST DISPLAY PHONE S DISPLAY SYS TRBL DISPLAY FIRE ALARM DISPLAY FIRE TRBL DISPLAY OP CL ACTIVATE OVERVIEW ACTIVATE CHIME ACTIVATE WATCH ACTIVATE GUARD TOUR RESET SYSTEM TRBL RESET SENSOR MSG START EXI...

Страница 57: ...S ENTER ZONE 00 E AUX OUTPUT ZONES ENTER ZONE 00 E SENSOR WATCH ZNS ENTER ZONE 00 E KP SNDR ALRM ZNS ENTER ZONE 00 E AUTO BYP RENT ZN ENTER ZONE 00 E ENABLE NO EOLR ZONES Y N E ENABLE TELCO LINE TEST...

Страница 58: ...X GEM X255 Installation Instructions L NAPCO Security Systems WI1093C 3 04 Page 58 NOTES...

Страница 59: ...ins 1 2 SYSTEM READY Move Jumper JP5 from Pins 1 2 to Pins 2 3 Wait about 15 seconds 01 OUT OF SYSTEM JP5 is located at the top right corner of the circuit board If a Compatibility Number other than 0...

Страница 60: ...X GEM X255 Installation Instructions L NAPCO Security Systems WI1093C 3 04 Page 60 GEM X255 WIRING DIAGRAM...

Страница 61: ...minimum default is 30 seconds If an attempt is made to change the Entry Delay time to less than 30 seconds the time will be entered as 30 seconds The maximum programmable time is 255 seconds The pane...

Страница 62: ...lt Find can not be initiated from an armed panel and all digital dialer reporting in same area is inhibited while in Fault Find Fault Find Central Station Reporting Code is located at address 0887 Key...

Страница 63: ...bled 4 All zones are programmed with report codes and as burg fire alarm types depending on whether they were selected as fire zones Zones not selected as fire are burg type 5 The reporting format is...

Страница 64: ...onnect the equipment Users should ensure for their own protection that the electrical ground connections of the power utility telephone lines and internal metallic water pipe system if present are con...

Страница 65: ...ssary the user should consult the dealer or an experienced radio television technician for additional suggestions The user may find the following booklet prepared by the Federal Communications Commiss...

Страница 66: ...X GEM X255 Installation Instructions L NAPCO Security Systems WI1093C 3 04 Page 66 Notes...

Страница 67: ...L NAPCO Security Systems X GEM X255 Installation Instructions WI1093C 3 04 Page 67 Notes...

Страница 68: ...her assumes nor au thorizes any other person purporting to act on its behalf to modify to change or to assume for it any other warranty or liability concerning its products In no event shall NAPCO be...

Отзывы: