GEM-X255 Installation Instructions
WI1093C 3/04
!
Page 33
Anti-Jam Time
If the communicator does not detect a dial tone within 12 seconds, the Anti-Jam feature will be activated. That is, the communi-
cator will go off line for a 16-second anti-jam interval in order to free the telephone circuit from an incoming call, then make another
12-second attempt at dial-tone detection. If still unsuccessful, the communicator will again go off line for 16 seconds, then proceed to
dial anyway.
Areas
Zone Area 1-Zone Area 8
Priority Area Arming
Although the default program will automatically set up Zones 1 through 8 for Zone Area 1, the panel may be partitioned into eight
areas. Each zone must be assigned to at least one area. At least one zone must be assigned to Area 1. If a burglary zone is se-
lected for both areas, that common zone will not arm until both areas are armed. If any zone disarms, the common zone will disarm.
In a multiple-area system, be sure to also program:
•
Enable User Code by Area (see User Codes/Authority Levels);
•
Keypad Area Assignments
•
Bell Control (determines which bells an area may silence);
•
Subscriber Opening/Closing ID Numbers and Event ID Numbers (if reporting);
•
System Trouble Subscriber ID Number
If Priority Area Arming is selected, the Priority Area must be armed before the Arming Area can be armed.
Arm Lug (Lug E4)
Lug E4 (ARM) will go to approximately 1Vdc when all areas in the system are armed. This lug may be used for auxiliary equip-
ment. (For use, refer to the instructions furnished with the device.)
Auto-Bypass
(Do not program for UL installations.)
Auto-Bypass Re-entry
Zones programmed for Auto-Bypass will be bypassed (automatically removed) if in trouble when arming. A momentary beep will
sound at the keypad to warn that the system has been armed without the protection of the auto-bypassed zone. (Note that the exit/
entry door must be closed before arming, otherwise the Exit/Entry Zone will be auto-bypassed).
Note:
A zone in trouble that is not
programmed for Auto-Bypass will cause an alarm on arming after a 10-second arming delay.
If Auto-Bypass Re-entry is selected, securing a zone that is programmed for Auto-Bypass, while armed, will cause that zone to
re-enter the system in an armed state.
Auto Disarm / Rearm Delay
If the panel was auto-disarmed on schedule and a rearm delay is programmed (see Time Selection), the panel will automatically
rearm after the delay if no activity has been detected.
Auto Output Test Upon Arming
(Required for UL Mercantile installations.)
This will activate the Burglary Output briefly 10 seconds after the area is armed. If the alarm does not sound, the device may be
defective.
Automatic Interior Bypass / Easy Exit
Convert from Away to Stay based on no egress through exit door. Default is enabled. This feature will cause all Interior-1 Zones
to automatically be bypassed if the Exit/Entry doors are not opened during the exit-delay period. If the
U
button is pressed while
armed, exit delay will restart and the Exit/Entry doors may be opened to permit someone to exit (while others remain on the premises)
without causing an alarm. This feature must be enabled in CP-01 installations. This feature is enabled in the factory program and it
is also enabled when "Enable CP-01 Features" is selected in the Easy Program Menu.
AUXOUT CHIRP ON KEYFOB ARM/DISARM
If enabled, when arming with a keyfob, the PGM2 output chirps. See also
Select Burg Output for Keyfob Chirp
. This feature
will cause a 1-chirp indication on arming and 2-chirp indication on disarming. Connect steady input (burglary) of external siren driver
to the panel’s Auxiliary Alarm Output.
Note:
Do not use an external voice siren driver.
Auto-Reset
Auto-Reset After Burg Output Timeout
If a zone detects an alarm condition and is selected for Auto-Reset, it will automatically rearm itself as soon as the alarm condi-
tion is cleared. Auto-Reset may be delayed to occur after the Burglary Output timeout period by selecting Auto-Reset After Burglary
Output Timeout and Auto-Reset. Zones that are not programmed for Auto-Reset will not be capable of signaling another alarm until
(a) the cause of the alarm has been corrected and (b) the control panel is disarmed. Also see Swinger Shutdown.
Auxiliary Relay See Alarm Outputs
Backup Reporting Telco #1 / Telco #2
If Backup Reporting is selected and the communicator does not reach the first telephone number after two attempts, seven at-
tempts will be made to reach the second telephone number. Enter Subscriber Identification Numbers for Telephone 2 and other infor-
mation required for Telephone 2. Also program Backup Report on Telco 2. Any zone programmed to report to Telco 1 will backup
report to Telco 2.
Note:
Subscriber Identification Numbers for both Telephones 1 and 2 must be entered, even if they are the same
GLOSS
A
RY
Содержание Gemini GEM-X255
Страница 58: ...X GEM X255 Installation Instructions L NAPCO Security Systems WI1093C 3 04 Page 58 NOTES...
Страница 60: ...X GEM X255 Installation Instructions L NAPCO Security Systems WI1093C 3 04 Page 60 GEM X255 WIRING DIAGRAM...
Страница 66: ...X GEM X255 Installation Instructions L NAPCO Security Systems WI1093C 3 04 Page 66 Notes...
Страница 67: ...L NAPCO Security Systems X GEM X255 Installation Instructions WI1093C 3 04 Page 67 Notes...